2019.02 / p
Electric Power Generation
50
Installation and maintenance
D510 C
Digital voltage regulator
4243 en -
≤ 7%
≥ 7%
Fault
Fault
Yes
Absence of voltage
Check the power supply is present
on the AVR
Green "POWER ON" LED active
Check the regulation mode
Check the wiring and the
supply voltage between
12 and 30 Volts
Check whether the measured
voltage 7% of UN
Yes
No
Check the polarity of the exciter field
Modify the wiring,
then reboot the
machine if
necessary
Check the exciter field connections
Modify the exciter field wiring or
replace it if faulty
Check the diode bridge
Replace the diode bridge if faulty
OK
Fault
Replace the AVR
Generator and control running
Start voltage regulation
No
6 - FAULT FLOW CHARTS