![Nidec Leroy-Somer D510 C Installation And Maintenance Manual Download Page 41](http://html1.mh-extra.com/html/nidec/leroy-somer-d510-c/leroy-somer-d510-c_installation-and-maintenance-manual_1687795041.webp)
2019.02 / p
Electric Power Generation
41
Installation and maintenance
D510 C
Digital voltage regulator
4243 en -
Warning: A wrong setting of the PID can damage the alternator.
PID setting methodology:
Please use Transient Test:
1
2
3
4
5
6
Initial conditions:
• Proportionnal = 10
• Integral = 0
• Derivative = 0
• Gain = 100
• Scale = 1
1
2
3
4
5
6
Adjust the proportional part to obtain a response as given in the figure below.
1
2
3
4
5
6
Adjust the integral part to have the output voltage in steady states equal to desired voltage
(reference voltage).
1
2
3
4
5
6
Adjust the derivative part to obtain response without oscillations.
1
2
3
4
5
6
Adjust the gain if necessary.
1
2
3
4
5
6
Change the scale value if the setting is unsuccessful and go back to step
1
2
3
4
5
6
.
400V
2
3
4