DFS1/DFS2 Power Installation Guide
39
Issue Number: 2
Saf
e
Pr
Mecha
El
Te
Table 4-4 Motor output cable sizes and connections
4.7
Motor requirements
No. of phases: 3
Maximum voltage:
400 V drive: 480 V
690 V drive: 690 V
4.8
Output short circuit protection
The drive modules are provided with fast-acting electronic short-circuit protection which limits the
fault current to typically no more than five times the rated output current and interrupts the current in
approximately 20 μs. No additional short-circuit protection devices are required. Refer to the
Unidrive M700, M701, M702 Control User Guide. CT Part Number: 0478-0353.
Model
Output
current
A
Motor cable
size
(mm²)
Terminals
Connection
Connectable cable
sizes
xxxx-DFS1G4EN
150
1 x 50
Drive motor
terminals
M10 x 17 AF nut
Maximum crimp
size 2 x 150 mm²
xxxx-DFS1H4EN
184
1 x 70
xxxx-DFS1J4EN
221
1 x 95
xxxx-DFS1K4EN
266
1 x 95
xxxx-DFS1L4EN
320
1 x 150
xxxx-DFS1M4EN
361
1 x 185
xxxx-DFS1N4EN
437
1 x 240
xxxx-DFS1P4EN
487
2 x 95
xxxx-DFS1Q4EN
507
2 x 95
xxxx-DFS2L4EN
640
2 x 150
xxxx-DFS2M4EN
722
2 x 185
Output sharing
choke terminals
1 x 11 mm hole
1 or 2 cables,
up to 240 mm²,
with M10 lug
xxxx-DFS2N4EN
874
2 x 240
xxxx-DFS2P4EN
974
3 x 150
xxxx-DFS2Q4EN
1014
3 x 150
xxxx-DFS166EN
86
1 x 16
Drive module
motor terminals
M10 x 17 AF nut
Maximum crimp
size 2 x 150 mm²
xxxx-DFS176EN
108
1 x 25
xxxx-DFS186EN
125
1 x 35
xxxx-DFS196EN
155
1 x 50
xxxx-DFS1A6EN
172
1 x 50
xxxx-DFS1B6EN
197
1 x 70
xxxx-DFS1C6EN
225
1 x 95
xxxx-DFS1D6EN
275
1 x 120
xxxx-DFS1E6EN
305
1 x 120
xxxx-DFS2A6EN
344
1 x 150
Output sharing
choke terminals
1 x 11 mm hole
1 or 2 cables,
up to 240 mm²,
with M10 lug
xxxx-DFS2B6EN
394
1 x 185
xxxx-DFS2C6EN
450
1 x 240
xxxx-DFS2D6EN
550
2 x 120
xxxx-DFS2E6EN
610
2 x 120