DFS1/DFS2 Power Installation Guide
37
Issue Number: 2
Saf
e
Pr
Mecha
El
Te
Table 4-2 Upstream fuse ratings
Supply cable sizes
The cable sizes in Table 4-3 and Table 4-4 are calculated using IEC60364-5-52:2009. table B.52.5,
for XLPE or EPR insulation. The cables are assumed to be arranged in a single layer on a perforated
horizontal or vertical cable tray system.
Model
No. of drive
modules fitted
Input current
A
Upstream
fuse rating
A
Fuse type
Short circuit
current rating
xxxx-DFS1G4EN
1
155
160
gG
100
xxxx-DFS1H4EN
1
177
200
gG
100
xxxx-DFS1J4EN
1
232
250
gG
100
xxxx-DFS1K4EN
1
267
315
gG
100
xxxx-DFS1L4EN
1
332
400
gG
100
xxxx-DFS1M4EN
1
397
500
gG
100
xxxx-DFS1N4EN
1
449
500
gG
100
xxxx-DFS1P4EN
1
492
630
gG
100
xxxx-DFS1Q4EN
1
539
630
gG
100
xxxx-DFS2L4EN
2
631
800
gG
100
xxxx-DFS2M4EN
2
657
800
gG
100
xxxx-DFS2N4EN
2
853
1000
gG
70
xxxx-DFS2P4EN
2
935
1000
gG
70
xxxx-DFS2Q4EN
2
1024
1250
gG
40
xxxx-DFS166EN
1
83
100
gG
80
xxxx-DFS176EN
1
104
125
gG
80
xxxx-DFS186EN
1
149
160
gG
80
xxxx-DFS196EN
1
171
200
gG
80
xxxx-DFS1A6EN
1
202
250
gG
80
xxxx-DFS1B6EN
1
225
250
gG
80
xxxx-DFS1C6EN
1
256
315
gG
80
xxxx-DFS1D6EN
1
302
315
gG
80
xxxx-DFS1E6EN
1
329
400
gG
100
xxxx-DFS2A6EN
2
384
400
gG
100
xxxx-DFS2B6EN
2
427
500
gG
100
xxxx-DFS2C6EN
2
486
500
gG
100
xxxx-DFS2D6EN
2
574
630
gG
100
xxxx-DFS2E6EN
2
625
800
gG
100
Cables sizes must comply with local wiring regulations and are the responsibility of the
installer. The cable sizes shown in Table 4-3 and Table 4-4 are for guidance only.
The current-carrying capacity of cables is affected by the mounting method and grouping.
A larger cable size may be required to avoid excessive temperature or voltage drop.
WARNING
NOTE