7.2 EXTENDED P
ARAMETERS
Par
Description
Minimum
Maximum
Default
Units
P-20
Preset Frequency / Speed 1
-P-01
P-01
5.0
Hz / RPM
P-21
Preset Frequency / Speed 2
-P-01
P-01
25.0
Hz / RPM
P-22
Preset Frequency / Speed 3
-P-01
P-01
40.0
Hz / RPM
P-23
Preset Frequency / Speed 4
-P-01
P-01
P-09
Hz / RPM
Preset Speeds / Frequencies selected by digital inputs depending on the setting of P-15
If P-10 = 0, the values are entered as Hz. If P-10 > 0, the values are entered as RPM.
NOTE: Changing the value of P-09 will reset all values to factory default settings
P-24
2
nd
Deceleration Ramp Time (Fast Stop)
0.00
600.0
0.00
s
This parameter allows an alternative deceleration ramp down time to be programmed into the AD700E, which can be selected by digital inputs
(dependent on the setting of P-15) or selected automatically in the case of a mains power loss if P-05 = 2 or 3.
When set to 0.00, the drive will coast to stop.
P-25
Analog Output Function Select
0
10
8
-
DIGITAL OUTPUT MODE. LOGIC 1 = +24V DC
0 : Drive Enabled (Running).
Logic 1 when the AD700E is enabled (Running)
1 : Drive Healthy.
Logic 1 When no Fault condition exists on the drive
2 : At Target Frequency (Speed).
Logic 1 when the output frequency matches the setpoint frequency
3: Drive Tripped.
Logic 1 when the drive is in a fault condition
4 : Output Frequency >= Limit.
Logic 1 when the output frequency exceeds the adjustable limit set in P-19
5 : Output Current >= Limit.
Logic 1 when the motor current exceeds the adjustable limit set in P-19
6 : Output Frequency < Limit.
Logic 1 when the output frequency is below the adjustable limit set in P-19
7 : Output Current < Limit.
Logic 1 when the motor current is below the adjustable limit set in P-19
ANALOG OUTPUT MODE
8 : Output Frequency (Motor Speed).
0 to P-01, resolution 0.1Hz
9 : Output (Motor) Current.
0 to 200% of P-08, resolution 0.1A
10 : Output Power.
0 – 200% of drive rated power.
P-26
Skip frequency hysteresis band
0.0
P-01
0.0
Hz / RPM
P-27
Skip Frequency Centre Point
0.0
P-01
0.0
Hz / RPM
The Skip Frequency function is used to avoid the AD700E operating at a certain output frequency, for example at a frequency which causes
mechanical resonance in a particular machine. Parameter P-27 defines the centre point of the skip frequency band, and is used in conjunction
with P-26. The AD700E output frequency will ramp through the defined band at the rates set in P-03 and P-04 respectively, and will not hold
any output frequency within the defined band. If the frequency reference applied to the drive is within the band, the AD700E output frequency
will remain at the upper or lower limit of the band.
P-28
V/F Characteristic Adjustment Voltage
0
P-07
0
V
P-29
V/F Characteristic Adjustment
Frequency
0.0
P-09
0.0
Hz
This parameter in conjunction with P-28 sets a frequency point at which the voltage set in P-29 is applied to the motor. Care must be taken to
avoid overheating and damaging the motor when using this feature.