5.4 INCOMING POWER CONNECTION
5
5.4 INCOMING POWER CONNECTION
• For 1 phase supply, power should be connected to L1/L, L2/N.
• For 3 phase supplies, power should be connected to L1, L2, and L3.
Phase sequence is not important.
• For compliance with CE and C Tick EMC requirements, a symmetrical
shielded cable is recommended.
• A fixed installation is required according to IEC61800-5-1 with a suitable
disconnecting device installed between the AD700E and the AC Power
Source. The disconnecting device must conform to the local safety code /
regulations (e.g. within Europe, EN60204-1, Safety of machinery).
• The cables should be dimensioned according to any local codes or
regulations. Guideline dimensions are given in section 10.2.
• Suitable fuses to provide wiring protection of the input power cable
should be installed in the incoming supply line, according to the data in
section 10.2 Rating Tables. The fuses must comply with any local codes
or regulations in place. In general, type gG (IEC 60269) or UL type J
fuses are suitable; however in some cases type aR fuses may be required.
The operating time of the fuses must be below 0.5 seconds.
• Where allowed by local regulations, suitably dimensioned type B MCB
circuit breakers of equivalent rating may be utilised in place of fuses,
providing that the clearing capacity is sufficient for the installation.
• When the power supply is removed from the drive, a minimum of 30
seconds should be allowed before re-applying the power. A minimum
of 5 minutes should be allowed before removing the terminal covers or
connection.
• The maximum permissible short circuit current at the AD700E
Power terminals as defined in IEC60439-1 is 100kA.
• An optional Input Choke is recommended to be installed in the supply
line for drives where any of the following conditions occur:
- The incoming supply impedance is low or the fault level / short circuit
current is high
- The supply is prone to dips or brown outs
- An imbalance exists on the supply (3 phase drives)
- The power supply to the drive is via a busbar and brush gear system
(typically overhead Cranes).
• In all other installations, an input choke is recommended to ensure
protection of the drive against power supply faults. Part numbers are
shown in the table.
Supply
Frame Size
AC Input Inductor
230 Volt
1 Phase
1
AD07-L1016-20
2
AD07-L1025-20
3
N/A
400 Volt
3 Phase
2
AD07-L3006-20
2
AD07-L3010-20
3
AD07-L3036-20
4
AD07-L3050-20