7 PARAMETERS
7.1 STANDARD PARAMETERS
7 P
ARAMETERS - 7.1
Par
Description
Minimum
Maximum
Default
Units
P-01
Maximum Frequency / Speed Limit
P-02
500.0
50.0 (60.0)
Hz / RPM
Maximum output frequency or motor speed limit – Hz or RPM. If P-10 >0, the value entered / displayed is in RPM
P-02
Minimum Frequency / Speed Limit
0.0
P-01
0.0
Hz / RPM
Minimum speed limit – Hz or RPM. If P-10 >0, the value entered / displayed is in RPM
P-03
Acceleration Ramp Time
0.00
600.0
5.0
s
Acceleration ramp time from zero Hz / RPM to base frequency (P-09) in seconds.
P-04
Deceleration Ramp Time
0.00
600.0
5.0
s
Deceleration ramp time from base frequency (P-09) to standstill in seconds. When set to 0.00, the value of P-24 is used.
P-05
Stopping Mode
0
3
0
-
Selects the stopping mode of the drive, and the behaviour in response to a loss of mains power supply during operation.
Setting
On Disable
On Mains Loss
0
Ramp to Stop (P-04)
Ride Through (Recover energy from load to maintain operation)
1
Coast
Coast
2
Ramp to Stop (P-04)
Fast Ramp to Stop (P-24), Coast if P-24 = 0
3
Ramp to Stop (P-04) with AC Flux Braking Fast Ramp to Stop (P-24), Coast if P-24 = 0
P-06
Energy Optimiser
0
1
0
-
0 : Disabled
1 : Enabled.
When enabled, the Energy Optimiser attempts to reduce the overall energy consumed by the drive and motor by reducing the
output voltage during constant speed, light load operation. The Energy Optimiser is intended for applications where the drive may operate for
some periods of time with constant speed and light motor load, whether constant or variable torque.
P-07
Motor Rated Voltage / Back EMF
at rated speed (PM / BLDC)
0
250 / 500
230 / 400
V
For Induction Motors, this parameter should be set to the rated (nameplate) voltage of the motor (Volts).
For Permanent Magnet or Brushless DC Motors, it should be set to the Back EMF at rated speed.
P-08
Motor Rated Current
Drive Rating Dependent
A
This parameter should be set to the rated (nameplate) current of the motor
P-09
Motor Rated Frequency
25
500
50 (60)
Hz
This parameter should be set to the rated (nameplate) frequency of the motor
P-10
Motor Rated Speed
0
30000
0
RPM
This parameter can optionally be set to the rated (nameplate) RPM of the motor. When set to the default value of zero, all speed related
parameters are displayed in Hz, and the slip compensation (where motor speed is maintained at a constant value regardless of applied load) for the
motor is disabled. Entering the value from the motor nameplate enables the slip compensation function, and the Optidrive display will now show
motor speed in RPM. All speed related parameters, such as Minimum and Maximum Speed, Preset Speeds etc. will also be displayed in RPM.
NOTE If P-09 value is changed, P-10 value is reset to 0