background image

COMMAND CONFIGURATION

This item covers the command categories associable with inputs 1 - 2 - 3 (refer to the section “input configuration - Table 1” to check the commands avail-
able). Each command category features various operating modes as described in a table (1-A, 1-B, etc.):

Step-by-step

In this command category the user can select one of the operating modes specified in Table 1-A.

TABLE 1-A: COMMAND CONFIGURATION

MODE

DESCRIPTION

Industrial mode

This runs the sequence “open in semiautomatic- close in hold-to-run”.

Open - stop - close - stop

This executes the above sequence.

Open - Stop - Close - Open

Operating mode set in factory (Input 1 - “step-by-step” command). This executes the above sequence.

Open - Close - Open - Close

This executes the above sequence.

Apartment block 1 step-by-step

Runs the sequence “close - stop - open - open”, until it reaches the fully open position. Note – If another command 
is sent after this one, the application executes the Closing manoeuvre with the same sequence.

Apartment block 2 step-by-step

Runs the sequence “close - stop - open - open” until the fully open position is reached. Note – If another command 
is sent after this one, the application executes the Closing manoeuvre with the same sequence. Important – When 
sending a command, if the transmitter key is held down for more than 2 seconds, the control unit activates a Stop.

Step-by-step 2

This executes the sequence “open - stop - close - open”. Important – When sending a command, if the transmitter 
key is held down for more than 2 seconds, the control unit activates a “partial open 1” command (input configura-
tion > Table 1).

Hold-to-run

The Opening or Closing manoeuvre is executed exclusively if the transmitter key is held down (hold-to-run).

partial open

In this command category the user can select one of the operating modes specified in Table 1-B.

TABLE 1-B: COMMAND CONFIGURATION

MODE

DESCRIPTION

Open - stop - close - stop

Operating mode set in factory. This executes the above sequence.

Open - Stop - Close - Open

This executes the above sequence.

Open - Close - Open - Close

This executes the above sequence.

Apartment block 1 step-by-step

This executes the sequence “close - stop - partial open 1- partial open 1” until the position is reached as pro-
grammed in the function “Partial Open 1”. Note – If another command is sent after this one, the application executes 
the Closing manoeuvre with the same sequence.

Apartment block 2 step-by-step

This executes the sequence “close - stop - partial open 1 - partial open 1” until the position is reached as pro-
grammed in the function “Partial Open 1”. Note – If another command is sent after this one, the application executes 
the Closing manoeuvre with the same sequence. Important – When sending a command, if the transmitter key is 
held down for more than 2 seconds, the control unit activates a Stop.

Hold-to-run

The Partial open 1 or Closing manoeuvre is executed exclusively if the transmitter key is held down (hold-to-run).

Industrial mode

This runs the sequence “open in semiautomatic- close in hold-to-run”.

Open

In this command category the user can select one of the operating modes specified in Table 1-C.

TABLE 1-C: COMMAND CONFIGURATION

MODE

DESCRIPTION

Open - Stop - Open

Operating mode set in factory (Input 2 - “open” command). This executes the above sequence.

Apartment block 1

An Opening manoeuvre is executed.

Apartment block 2

This executes the sequence “open - open”. Important – When sending a command, if the transmitter key is held 
down for more than 2 seconds, the control unit activates a Stop.

Open 2

Important – When sending a command, if the transmitter key is held down for more than 2 seconds, the control unit 
activates a “partial open 1” command (input configuration > Table 1).

Hold-to-run Open

The Opening manoeuvre is executed exclusively if the transmitter key is held down (hold-to-run).

Close

In this command category the user can select one of the operating modes specified in Table 1-D.

TABLE 1-D: COMMAND CONFIGURATION

MODE

DESCRIPTION

Close - stop - close

Operating mode set in factory (Input 3 - “close” command). This executes the sequence as described.

Apartment block 1 close

This executes the sequence “close - close”.

Apartment block 2 close

This executes the sequence “close - close”. Important – When sending a command, if the transmitter key is held 
down for more than 2 seconds, the control unit activates a Stop.

Hold-to-run close

The Closing manoeuvre is executed exclusively if the hold-to-run command is used.

Stop 

In this category, you can choose one of the operating modes listed in table 1-E.

TABLE 1-E: COMMAND CONFIGURATION

MODE

DESCRIPTION

Stop

Operating mode set in factory. When the control unit receives the command, it stops the manoeuvre in progress 
gradually and in a short time (not instantly).

Summary of Contents for LBar

Page 1: ...Programmable functions using the Oview programmer MBar LBar STF XBA3 Rev00 Firmware XB02a XU01 XF01 ...

Page 2: ... a programming session followed by the log out procedure on completion of the programming procedure Note the log out procedure enables the user to prevent access by unauthorised personnel by re activating the existing password Caution In programming the password on multiple devices for example on the Oview control unit receiver etc it is advisable to use the same password for all devices including...

Page 3: ... at the end of the wait time programmed in the function pause time If the function is not active OFF the Control unit operation mode is semiautomatic Pause time 0x81 This parameter is expressed in seconds and can be set with a value from 0 to 250 sec the factory setting is 20 sec This function enables programming on the Control unit of the required wait time which must pass between the end of an O...

Page 4: ...n of barrier The function enables control of the force absorbed by the motor during a Closing manoeuvre Important Setting this value too high can damage the gearmotor and overheat the control unit closing deceleration force 0x4d This parameter can be set with a value from 10 to 100 the factory setting depends on the version of barrier The function enables control of the maximum force absorbed by t...

Page 5: ...n be set with a value from 0 to 10 sec the factory setting is 3 sec This function programs the flashing time which indicates the imminent start of a Closing manoeuvre it is associated with the pre flashing function Stand by 0x8b active 0x8c This parameter is ON OFF the factory setting is OFF When this function is set to ON automation power consumption can be reduced mode 0x8e The function has 3 op...

Page 6: ...ration opening mode This command is factory assigned to Input 2 in mode open When this command is sent the control unit activates the ap plication to complete the Opening manoeuvre until the position is reached as set in the function opening Control unit func tions installation positions opening Input configured as normally open Close Closure Program the desired mode from those listed in table 1 B...

Page 7: ...de apartment block 1 open When this command is sent the control unit activates the ap plication to perform the opening manoeuvre only until the limit switch is reached Note This command is useful when using control photocells or a magnetic detector loop Input configured as normally open Photo Safety function Photo Program the desired mode from those listed in Table 1 F command configuration photo ...

Page 8: ...iation of the metal body required to start a manoeuvre Note set a high sensitivity to detect small metal bodies set a low sensitivity to detect large metal bodies Loop activation 0xe7 This parameter type is ON OFF the factory setting is ON Activating the loop means that the barrier will react as programmed when it is tripped If the function is DEACTIVATED the status of the loop is available if one...

Page 9: ...er command is sent after this one the application executes the Closing manoeuvre with the same sequence Apartment block 2 step by step This executes the sequence close stop partial open 1 partial open 1 until the position is reached as pro grammed in the function Partial Open 1 Note If another command is sent after this one the application executes the Closing manoeuvre with the same sequence Impo...

Page 10: ...lication to perform a brief inversion in the opposite direction Closing Caution During execution of the Opening manoeuvre this command is ignored Stop When the control unit receives the command it stops the Opening manoeuvre in progress Caution During execu tion of the Opening manoeuvre this command is ignored temporary stop When the control unit receives the command it stops the Closing manoeuvre...

Page 11: ...er TABLE 2 OUTPUT CONFIGURATION FUNCTION DESCRIPTION sca 0x01 The programmed light indicates the operating status of the control unit light off application in maximum Closing position slow flashing application Opening manoeuvre execution phase quick flashing application Closing manoeuvre execution phase light permanently on application in maximum Opening position SCA1 0x14 The programmed light ind...

Page 12: ...nnel is not free on the control unit s receiver due to having been previously memorised with a command when the chan nel is activated by the transmitter the control unit only activates the programmed output and ignores the motor command Radio channel 4 0x12 When a transmitter sends a command this output is activated This mode is useful if installing external devices for example an auxiliary light ...

Page 13: ...tem to be controlled with a single transmitter CAUTION If this channel is not free on the control unit s receiver due to having been previously memorised with a command when the channel is activated by the transmitter the control unit only activates the programmed output and ignores the motor command Output active 24 V DC max 10 W radio channel no 2 If this radio channel is set for the configurati...

Page 14: ... to occupation by a metal body Loop2 Indicates when the loop is activated due to occupation by a metal body BOARD KEYS no 1 Indicates when key 1 is pressed OPEN on the control unit no 2 Indicates when key 2 is pressed STOP on the control unit no 3 Indicates when key 3 is pressed CLOSE on the control unit DIRECTION SELECTION Indicates the status of the direction selector for a manoeuvre INPUT STATU...

Page 15: ...ata is useful to understand whether the encoder is in an overtravel position i e outside the operating zone of the absolute encoder bluebus device diagnostics This function displays the type operating status and configuration of devices connected ot the Bluebus output These parameters are described in Table 6 TABLE 6 DIAGNOSTICS of bluebus devices PARAMETER DESCRIPTION Bluebus PHOTOCELLS PHOTO Ind...

Page 16: ...s required after performing mainte nance on the automation ADVANCED FUNCTIONS event log This function enables the display of the events generated or received by the control unit An event is a condition which changes the operating status of the control unit such as activation of an input end of a manoeuvre photocell or stop input tripped etc This section displays the date and type of an event firmw...

Reviews: