35
MX4777 Rev. D ©2021
RELAY OUTPUTS - BASIC
10 11
9
USER RELAY
OUTPUTS
RELAY 1 – 3 LOGIC
0 DISABLED
1 CLOSE LIMIT
2 CLOSE PULSE
3 OPEN LIMIT
4 OPEN PULSE
5 WARN B4 OP
6 GATE LOCK
7 FORCE OPEN
8 OPEN 2LONG
9 SAFE MODE
10 ENTRAPMENT
11 TAILGATER
12 OUTSIDE LOOP
13 LOITERING
14 NEAR LIMIT
15 ALERT/FAULT
16 MOTOR RUNNING
17 AC POWER LOSS
18 LOW BATTERY
19 FLASHER
20 EXIT LOOP
21 INSIDE LOOP
22 CENTER LOOP
23 PRISON LOCK
24 PARTIAL OPEN
25 BATTERY OK
26 EXIT PULSE
27 NOT OP AC
28 FLASH AC
29 ARM ENTRY
30 ARM EXIT
31 RESET TKT
32 BACKOFF
33 TRANS IN
34 TRANS OUT
35 TENANT IN
36 TENANT OUT
37 SPEC IN
38 SPEC OUT
39 UNK IN
40 UNK OUT
41 TEST OPEN
42 ARM BREAK
43 WARN THRU
44 POL PULSE
45 OUTS CLOSE
46 TIMER OPEN
47 OXI ACCESSORY
48 OXI ACC/1-MIN
0 DISABLED –
48 OXI ACC/-MIN
RELAY 4 – 11 ARE VISIBLE AND CONFIGURABLE ONLY WITH OPTIONAL
I/O EXPANSION MODULE WHICH CONNECTS VIA COMMUNICATION CABLE
(MX4330 IN THE I/O EXPANSION MODULE KIT) FROM HS-2 ON THE
SMARTCNX CONTROLLER TO HS-A ON THE I/O EXPANSION MODULE
RELAY 4 – 11 LOGIC
The three relays on the SmartCNX Controller are
configurable to perform a wide range of options for
integration with external devices. For more information,
see Advanced Manual.
●
Accessory power limited to 2A at 24VDC across all
inputs and relays.
●
Relay capacity: (1) Mechanical 20A max at 240VAC
(Figure 48 Item 9). (2) Solid state relays 30VDC, 2A
1. Install the relay controlled device according to the
manufacturer's instructions.
2. Route the relay wires to the SmartCNX Controller
3. Install the relay wires in the appropriate relay port:
mechanical (Relay 1) or solid state (Relay 2 and 3)
4. Press MENU on the SmartCNX Controller.
5. Press the UP or DOWN arrow to navigate to USER
RELAY OUTPUTS, press SELECT,
6. Press the UP or DOWN arrow to navigate to RELAY
LOGIC, press SELECT.
7. Press the UP or DOWN arrow to highlight the
appropriate setting, press SELECT.
8. Press BACK until the SmartCNX controller resets and
operator status displays.
Figure 47. Route Relay Wires
Figure 48. Relay Ports