Appendix D – Cooling Data for (-)GEDZR 8.5 Ton
P. APPENDICES
$SSHQGL['&RROLQJ'DWDIRU*('=57RQ
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
➀
wbE
71°F [21.7°C]
67°F [19.4°C]
63°F [17.2°C]
61°F [16.1°C]
59°F [15.0°C]
CFM [L/s]
4100 [1935]
3200 [1510]
2700 [1274]
4100 [1935]
3200 [1510]
2700 [1274]
4100 [1935]
3200 [1510]
2700 [1274]
4100 [1935]
3200 [1510]
2700 [1274]
4100 [1935]
3200 [1510]
2700 [1274]
DR
➀
0.21
0.17
0.14
0.21
0.17
0.14
0.21
0.17
0.14
0.21
0.17
0.14
0.21
0.17
0.14
O U T D O O R
D R Y
B U L B
T E M P E R A T U R E
°F [°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
129.7 [38.0]
75.5 [22.1]
6.2
123.4 [36.2]
66.7 [19.5]
6
119.9 [35.1]
61.8 [18.1]
5.9
122.5 [35.9]
90.5 [26.5]
6.1
116.6 [34.2]
80 [23.4]
6
113.3 [33.2]
74.2 [21.7]
5.9
118.1 [34.6]
104.2 [30.5]
6
112.4 [32.9]
92.1 [27.0]
5.9
109.2 [32.0]
85.4 [25.0]
5.8
117.3 [34.4]
110.3 [32.3]
6
111.6 [32.7]
97.5 [28.6]
5.9
108.4 [31.8]
90.4 [26.5]
5.8
117.8 [34.5]
115.6 [33.9]
6
112.1 [32.8]
102.2 [29.9]
5.8
108.9 [31.9]
94.7 [27.8]
5.8
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
125.5 [36.8]
73.3 [21.5]
6.5
119.4 [35.0]
64.8 [19.0]
6.4
116 [34.0]
60.1 [17.6]
6.3
118.3 [34.7]
88.4 [25.9]
6.5
112.5 [33.0]
78.2 [22.9]
6.3
109.3 [32.0]
72.5 [21.2]
6.2
113.9 [33.4]
102.1 [29.9]
6.4
108.3 [31.7]
90.3 [26.5]
6.2
105.3 [30.8]
83.7 [24.5]
6.2
113.1 [33.1]
108.2 [31.7]
6.4
107.6 [31.5]
95.6 [28.0]
6.2
104.5 [30.6]
88.7 [26.0]
6.1
113.6 [33.3]
113.5 [33.3]
6.3
108 [31.7]
100.3 [29.4]
6.2
105 [30.8]
93 [27.3]
6.1
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
121.2 [35.5]
71.2 [20.9]
6.9
115.3 [33.8]
62.9 [18.4]
6.7
112.1 [32.8]
58.4 [17.1]
6.7
114 [33.4]
86.3 [25.3]
6.8
108.5 [31.8]
76.3 [22.3]
6.7
105.4 [30.9]
70.7 [20.7]
6.6
109.6 [32.1]
100 [29.3]
6.8
104.3 [30.6]
88.4 [25.9]
6.6
101.3 [29.7]
81.9 [24.0]
6.5
108.8 [31.9]
106 [31.1]
6.7
103.6 [30.3]
93.7 [27.5]
6.6
100.6 [29.5]
86.9 [25.5]
6.5
109.3 [32.0]
109.3 [32.0]
6.7
104 [30.5]
98.4 [28.8]
6.6
101 [29.6]
91.3 [26.7]
6.5
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
117 [34.3]
69 [20.2]
7.3
111.3 [32.6]
61 [17.9]
7.2
108.1 [31.7]
56.6 [16.6]
7.1
109.8 [32.2]
84.1 [24.6]
7.3
104.4 [30.6]
74.3 [21.8]
7.1
101.5 [29.7]
68.9 [20.2]
7
105.4 [30.9]
97.8 [28.7]
7.2
100.2 [29.4]
86.5 [25.3]
7
97.4 [28.5]
80.2 [23.5]
6.9
104.6 [30.6]
103.9 [30.4]
7.2
99.5 [29.2]
91.8 [26.9]
7
96.7 [28.3]
85.1 [24.9]
6.9
105.1 [30.8]
105.1 [30.8]
7.1
99.9 [29.3]
96.5 [28.3]
7
97.1 [28.5]
89.5 [26.2]
6.9
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
112.7 [33.0]
66.8 [19.6]
7.8
107.2 [31.4]
59.1 [17.3]
7.6
104.2 [30.5]
54.8 [16.0]
7.5
105.5 [30.9]
81.9 [24.0]
7.7
100.4 [29.4]
72.4 [21.2]
7.5
97.5 [28.6]
67.1 [19.7]
7.4
101.1 [29.6]
95.6 [28.0]
7.6
96.2 [28.2]
84.5 [24.8]
7.5
93.4 [27.4]
78.3 [23.0]
7.4
100.3 [29.4]
100.3 [29.4]
7.6
95.4 [28.0]
89.8 [26.3]
7.4
92.7 [27.2]
83.3 [24.4]
7.3
100.8 [29.5]
100.8 [29.5]
7.6
95.9 [28.1]
94.5 [27.7]
7.4
93.2 [27.3]
87.7 [25.7]
7.3
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
108.4 [31.8]
64.6 [18.9]
8.3
103.1 [30.2]
57.1 [16.7]
8.1
100.2 [29.4]
52.9 [15.5]
7.9
101.2 [29.7]
79.6 [23.3]
8.2
96.3 [28.2]
70.4 [20.6]
8
93.6 [27.4]
65.2 [19.1]
7.9
96.8 [28.4]
93.3 [27.3]
8.1
92.1 [27.0]
82.5 [24.2]
7.9
89.5 [26.2]
76.5 [22.4]
7.8
96 [28.1]
96 [28.1]
8.1
91.3 [26.8]
87.9 [25.7]
7.9
88.8 [26.0]
81.4 [23.9]
7.8
96.5 [28.3]
96.5 [28.3]
8.1
91.8 [26.9]
91.8 [26.9]
7.9
89.2 [26.1]
85.8 [25.1]
7.8
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
104.1 [30.5]
62.3 [18.2]
8.8
99 [29.0]
55 [16.1]
8.6
96.2 [28.2]
51 [15.0]
8.4
96.9 [28.4]
77.3 [22.7]
8.7
92.2 [27.0]
68.3 [20.0]
8.5
89.6 [26.2]
63.4 [18.6]
8.4
92.5 [27.1]
91 [26.7]
8.6
88 [25.8]
80.5 [23.6]
8.4
85.5 [25.1]
74.6 [21.9]
8.3
91.7 [26.9]
91.7 [26.9]
8.6
87.2 [25.6]
85.8 [25.1]
8.4
84.8 [24.8]
79.6 [23.3]
8.3
92.2 [27.0]
92.2 [27.0]
8.6
87.7 [25.7]
87.7 [25.7]
8.4
85.2 [25.0]
83.9 [24.6]
8.2
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
99.8 [29.2]
59.9 [17.6]
9.3
94.9 [27.8]
53 [15.5]
9.1
92.2 [27.0]
49.1 [14.4]
9
92.6 [27.1]
75 [22.0]
9.2
88.1 [25.8]
66.3 [19.4]
9
85.6 [25.1]
61.5 [18.0]
8.9
88.2 [25.8]
88.2 [25.8]
9.2
83.9 [24.6]
78.4 [23.0]
9
81.5 [23.9]
72.7 [21.3]
8.8
87.4 [25.6]
87.4 [25.6]
9.1
83.1 [24.4]
83.1 [24.4]
8.9
80.8 [23.7]
77.6 [22.8]
8.8
87.9 [25.7]
87.9 [25.7]
9.1
83.6 [24.5]
83.6 [24.5]
8.9
81.2 [23.8]
81.2 [23.8]
8.8
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
95.4 [28.0]
57.5 [16.9]
9.9
90.8 [26.6]
50.9 [14.9]
9.6
88.2 [25.9]
47.2 [13.8]
9.5
88.3 [25.9]
72.6 [21.3]
9.8
84 [24.6]
64.2 [18.8]
9.6
81.6 [23.9]
59.5 [17.4]
9.4
83.8 [24.6]
83.8 [24.6]
9.8
79.7 [23.4]
76.3 [22.4]
9.5
77.5 [22.7]
70.7 [20.7]
9.4
83.1 [24.3]
83.1 [24.3]
9.7
79 [23.2]
79 [23.2]
9.5
76.8 [22.5]
75.7 [22.2]
9.4
83.5 [24.5]
83.5 [24.5]
9.7
79.5 [23.3]
79.5 [23.3]
9.5
77.2 [22.6]
77.2 [22.6]
9.3
120
[48.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
91.1 [26.7]
55.1 [16.2]
10.5
86.7 [25.4]
48.7 [14.3]
10.2
84.2 [24.7]
45.2 [13.2]
10.1
83.9 [24.6]
70.2 [20.6]
10.4
79.8 [23.4]
62.1 [18.2]
10.2
77.6 [22.7]
57.5 [16.9]
10
79.5 [23.3]
79.5 [23.3]
10.4
75.6 [22.2]
74.2 [21.7]
10.1
73.5 [21.5]
68.8 [20.1]
10
78.7 [23.1]
78.7 [23.1]
10.3
74.9 [21.9]
74.9 [21.9]
10.1
72.7 [21.3]
72.7 [21.3]
9.9
79.2 [23.2]
79.2 [23.2]
10.3
75.3 [22.1]
75.3 [22.1]
10
73.2 [21.4]
73.2 [21.4]
9.9
125
[51.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
86.7 [25.4]
52.7 [15.4]
11.1
82.5 [24.2]
46.6 [13.6]
10.9
80.2 [23.5]
43.2 [12.7]
10.7
79.5 [23.3]
67.7 [19.9]
11.1
75.7 [22.2]
59.9 [17.5]
10.8
73.5 [21.5]
55.5 [16.3]
10.6
75.1 [22.0]
75.1 [22.0]
11
71.5 [20.9]
71.5 [20.9]
10.7
69.4 [20.3]
66.8 [19.6]
10.6
74.3 [21.8]
74.3 [21.8]
11
70.7 [20.7]
70.7 [20.7]
10.7
68.7 [20.1]
68.7 [20.1]
10.5
74.8 [21.9]
74.8 [21.9]
10.9
71.2 [20.9]
71.2 [20.9]
10.7
69.1 [20.3]
69.1 [20.3]
10.5
DR
—Depression ra
tio
dbE
—Entering air dr
y bulb
wbE
—Entering air wet bulb
Total
—T
otal ca
pacity x 1000 BTUH
Sens
—Sensible ca
pacity x 1000 BTUH
Po
wer
—KW input
NO
TES:
➀
When the entering air dr
y bulb is other than 80°F [27°C],
adjust the sensible
ca
pacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
[
] Designates Metric Conversions
COOLING PERFORMANCE D
AT
A—
GEDZR102A
Summary of Contents for Climate Master RGED Series
Page 2: ...2 62 ...
Page 88: ...88 P APPENDICES Appendix C Air Flow Performance Data ...
Page 90: ...90 P APPENDICES Appendix C Air Flow Performance Data Cont ...
Page 92: ...92 P APPENDICES Appendix C Air Flow Performance Data Cont ...
Page 94: ...94 P APPENDICES Appendix C Air Flow Performance Data Cont ...
Page 159: ...159 ...