79
P. APPENDICES
Appendix B – Electrical Data (Cont.)
ELECTRICAL DATA - (-)GEDZR SERIES
120ACA15
120ACA22
120ACB15
120ACB22
120ACC15
120ACC22
120ADA15
120ADA22
120ADB15
120ADB22
120ADC15
120ADC22
120AYA15 120AYA22 120AYB15 120AYB22 120AYC15 120AYC22
Unit Information
Unit Operating Voltage Range
187-253
187-253
187-253
414-506
414-506
414-506
517-633
517-633
517-633
517-633
517-633
517-633
Volts
208/230
208/230
208/230
460
460
460
575
575
575
575
575
575
Phase
3
3
3
3
3
3
3
3
3
3
3
3
Hz
60
60
60
60
60
60
60
60
60
60
60
60
Minimum Circuit Ampacity
48
51
53
26
27
28
19
19
20
20
20
20
Minimum Overcurrent
Protection Device Size
60
60
60
30
30
35
25
25
25
25
25
25
Maximum Overcurrent
Protection Device Size
70
70
80
35
40
40
25
25
30
30
30
30
Compressor Motor
No.
1
1
1
1
1
1
1
1
1
1
1
1
Volts
208/230
208/230
208/230
460
460
460
575
575
575
575
575
575
Phase
3
3
3
3
3
3
3
3
3
3
3
3
RPM
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
3450
HP, Compressor 1
10
10
10
10
10
10
10
10
10
10
10
10
Amps (RLA), Comp. 1
28.2
28.2
28.2
14.7
14.7
14.7
11.3
11.3
11.3
11.3
11.3
11.3
Amps (LRA), Comp. 1
239
239
239
130
130
130
93.7
93.7
93.7
93.7
93.7
93.7
Condenser Motor
No.
2
2
2
2
2
2
2
2
2
2
2
2
Volts
208/230
208/230
208/230
460
460
460
575
575
575
575
575
575
Phase
1
1
1
1
1
1
1
1
1
1
1
1
HP
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
1/3
Amps (FLA, each)
2.4
2.4
2.4
1.4
1.4
1.4
1
1
1
1
1
1
Amps (LRA, each)
4.7
4.7
4.7
2.4
2.4
2.4
1.6
1.6
1.6
1.6
1.6
1.6
Evaporator Fan
No.
1
1
1
1
1
1
1
1
1
1
1
1
Volts
208/230
208/230
208/230
460
460
460
575
575
575
575
575
575
Phase
3
3
3
3
3
3
3
3
3
3
3
3
HP
2
2
2
2
3
3
2
2
3
3
3
3
Amps (FLA, each)
7.9
10.1
12
3.9
5
6
2.5
2.5
3.5
3.5
3.5
3.5
Amps (LRA, each)
45
74.5
74.5
22.5
38.1
38.1
19
19
20
20
20
20
Summary of Contents for Climate Master RGED Series
Page 2: ...2 62 ...
Page 88: ...88 P APPENDICES Appendix C Air Flow Performance Data ...
Page 90: ...90 P APPENDICES Appendix C Air Flow Performance Data Cont ...
Page 92: ...92 P APPENDICES Appendix C Air Flow Performance Data Cont ...
Page 94: ...94 P APPENDICES Appendix C Air Flow Performance Data Cont ...
Page 159: ...159 ...