Drain indoors
:DWHU VHDO
The condensation water is lead to an indoor drain
(subject to local rules and regulations).
Route the pipe downward from AMB 30.
The condensation water pipe must have a water seal
to prevent air circulation in the pipe.
Gutter drainage
LEK
Frostfritt
djup
)URVW SURRI
GHSWK
:DWHU VHDO
The outlet of the condensation water pipe must be at
frost free depth.
Route the pipe downward from AMB 30.
The condensation water pipe must have a water seal
to prevent air circulation in the pipe.
7
Chapter 2 |
Delivery and handling
AMB 30