May be due to
Description
Alarm text on the dis-
play
Alarm
no.
- Open-circuit or short-circuit on sensor input
Sensor fault, outdoor temperature sensor in
AMS 10 (Tho-A).
Sensor fault Tho-A
E38
- Sensor does not work (see "Temperature
sensor" section)
- Defective control board in AMS 10
- Open-circuit or short-circuit on sensor input
Sensor fault, hot gas in AMS 10 (Tho-D).
Sensor fault Tho-D
E39
- Sensor does not work (see "Temperature
sensor" section)
- Defective control board in AMS 10
- Insufficient air circulation or blocked heat ex-
changer
The high pressure switch (63H1) deployed 5
times within 60 minutes or for 60 minutes con-
tinuously.
HP alarm
E40
- Open circuit or short circuit on input for high
pressure switch (63H1)
- Defective high pressure pressostat
- Expansion valve not correctly connected
- Service valve closed
- Defective control board in AMS 10
- Low or no flow during heating operation
- Defective circulation pump
- Defective fuse, F(4A)
Could occur when 15V power supply to the in-
verter PCB is unstable.
When IPM (Intelligent power module) displays
FO-signal (Fault Output) five times during a 60-
minute period.
Power transistor too hot
E41
- Incoming power supply interference
Voltage from the inverter outside the paramet-
ers four times within 30 minutes.
Inverter error
E42
- Service valve closed
- Insufficient amount of refrigerant
- Compressor fault
- Defective circuit board for inverter in AMS 10
- Open-circuit in connection between boards
Communication between circuit board for in-
verter and control board broken.
Inverter error
E45
- Defective circuit board for inverter in AMS 10
- Defective control board in AMS 10
- Sudden power failure
Overcurrent, Inverter A/F module
Inverter error
E47
- The fan cannot rotate freely
Deviations in the fan speed in AMS 10.
Fan alarm
E48
- Defective control board in AMS 10
- Defective fan motor
- Control board in AMS 10 dirty
- Fuse (F2) tripped
- Open circuit or short circuit on input for low
pressure transmitter
Too low value on the low pressure sensor 3
times within 60 minutes.
LP alarm
E49
- Defective low pressure transmitter
- Defective control board in AMS 10
- Open circuit or short circuit on input for suc-
tion gas sensor (Tho-S)
- Faulty suction gas sensor (Tho-S)
- Defective fan motor
Continuous deviation on power transistor for
15 minutes.
Inverter error
E51
- Defective circuit board for inverter in AMS 10
63
NIBE™ SPLIT ACVM 270
Miscellaneous
Alarm list
Summary of Contents for ACVM 270
Page 2: ...LEK LEK 1 2 LEK LEK 7 LEK 5 6 LEK 3 4 LEK LEK LEK LEK AMS 10 8 LEK LEK AMS 10 12 ...
Page 67: ...67 NIBE SPLIT ACVM 270 Miscellaneous Electrical circuit diagram ...
Page 68: ...NIBE SPLIT ACVM 270 68 Miscellaneous Electrical circuit diagram ...
Page 69: ...69 NIBE SPLIT ACVM 270 Miscellaneous Electrical circuit diagram ...
Page 70: ...NIBE SPLIT ACVM 270 70 Miscellaneous Electrical circuit diagram ...
Page 94: ......
Page 95: ......