Electrical installation
General
ACVM 270 must be installed via a circuit breaker with a
minimum breaking gap of 3mm.
Other electrical equipment, except the outdoor sensors,
current sensors and outdoor module AMS 10 is already
connected at the factory.
■
Disconnect the indoor module ACVM 270 and outdoor
module AMS 10 before insulation testing the house
wiring.
■
For fuse ratings, see technical data, “Fuse protection”.
■
If the building is equipped with an earth-fault breaker,
ACVM 270 should be equipped with a separate one.
■
Connection must not be carried out without the permis-
sion of the electricity supplier and under the supervision
of a qualified electrician.
■
5x2.5 mm
2
cable must be used for the connection
between ACVM 270 and AMS 10.
■
Cables must be routed so that they are not damaged by
metal edges or trapped by panels.
■
AMS 10 is equipped with a single phase compressor.
This means that phase L3 is loaded with up to 15 A dur-
ing compressor operation.
NOTE
Electrical installation and service must be carried out
under the supervision of a qualified electrician. Elec-
trical installation and wiring must be carried out in
accordance with the stipulations in force.
NOTE
The switch (SF1) must not be moved to “1” or “
”
until the boiler has been filled with water. The circu-
lation pump and immersion heater may be damaged.
Principle diagram, electrical installation
L
PEN
1
L
2
L
3
Electrical distribution
unit
Isolator switch
Current sensor*
Incoming supply
Power and
communication cable
* Only in a 3-phase installation.
Electrical components
L
E
K
1 mm
5,5 mm
L
E
K
1 mm
5,5 mm
UB1
X1
SF1
FA2
FA1
BT30
FD1
X1
X2
UB2
X3
UB4
Explanation
Scale length of
conductor (mm)
Type
Designa-
tion
-
Cable gland
UB1,2,4
18
Terminal block, incoming
mains supply
X1
9
Terminal block, outgoing
supply and communication
X2
9
Terminal block, external addi-
tion
X3
-
Switch
SF1
-
Miniature circuit breaker,
control system
FA1
-
Miniature circuit breaker,
outdoor unit
FA2
-
Thermostat, standby mode
BT30
-
Temperature limiter
FD1
31
NIBE™ SPLIT ACVM 270
For the Installer
Electrical installation
Summary of Contents for ACVM 270
Page 2: ...LEK LEK 1 2 LEK LEK 7 LEK 5 6 LEK 3 4 LEK LEK LEK LEK AMS 10 8 LEK LEK AMS 10 12 ...
Page 67: ...67 NIBE SPLIT ACVM 270 Miscellaneous Electrical circuit diagram ...
Page 68: ...NIBE SPLIT ACVM 270 68 Miscellaneous Electrical circuit diagram ...
Page 69: ...69 NIBE SPLIT ACVM 270 Miscellaneous Electrical circuit diagram ...
Page 70: ...NIBE SPLIT ACVM 270 70 Miscellaneous Electrical circuit diagram ...
Page 94: ......
Page 95: ......