Standard test, EN14511
1. Check that the heat pump only produces heat to the
climate system by deselecting hot water production
in menu 9.3.14.
2. Select "Off" in menu 8.2.1 to prevent the electrical
additional heat.
3. Select heating curve 15 in menu 2.1.2.
4. Turn the "Offset, heating curve" knob clockwise to its
limit position.
5. Set the current degree minute value in menu 2.6 to
-200.
6. To set any compressor frequency, select "On" in menu
9.6.2.
7. Depending on the operating case, set the frequency
in menu 9.6.1 according to the table.
Frequency (Hz)
Test values
35
A7/W35
60
A2/W35
8. Set the circulation pump speed in menu 2.1.5 to obtain
10 kPa external available pressure.
Standard test, AMS 10-8
Output in (kW)
Heat capacity (kW)
COP
Flow temperature (°C)
Air temperature (°C)
0.83
3.85
4.66
35
7
1.36
5.11
3.77
35
2
Standard test, AMS 10-12
Output in (kW)
Heat capacity (kW)
COP
Flow temperature (°C)
Air temperature (°C)
1.09
5.21
4.79
35
7
1.79
6.91
3.87
35
2
85
NIBE™ SPLIT ACVM 270
Miscellaneous
Technical specifications