May be due to
Description
Alarm text on the dis-
play
Alarm
no.
- Open-circuit or short-circuit on sensor input
Sensor fault, suction gas in AMS 10 (Tho-S).
Sensor fault Tho-S
E53
- Sensor does not work (see "Temperature
sensor" section)
- Defective control board in AMS 10
- Open-circuit or short-circuit on sensor input
Sensor fault, low pressure transmitter in
AMS 10.
Sensor fault LPT
E54
- Sensor does not work (see "Temperature
sensor" section)
- Defective control board in AMS 10
- Fault in the refrigerant circuit
- Service valve closed
Insufficient refrigerant is detected upon start-
up in cooling mode.
Insufficient refrigerant
E57
- Loose connection sensor (BT15, BT3)
- Defective sensor (BT15, BT3)
- Too little refrigerant
- Defective circuit board for inverter in AMS 10
Failed start for compressor
Inverter error
E59
- Defective control board in AMS 10
- Compressor fault
Hot water alarm
The following alarms block hot water production via AMS 10. The addition is blocked completely.
May be due to
Description
Alarm text on the dis-
play
Alarm
no.
- Contactor to internal electricity defective
Too high a temperature (>90 °C) on hot water
sensor (BT6).
High HW temp.
8
- Incorrect external addition setting
- Contactor to internal electricity defective
Too high a temperature (>90 °C) on immersion
heater sensor (BT19).
High AH temp.
9
- Incorrect external addition setting
- Open-circuit or short-circuit on sensor input
Sensor fault, hot water (BT6).
S. fault HW
34
- Sensor does not work (see "Temperature
sensor" section)
- Open-circuit or short-circuit on sensor input
Sensor fault, immersion heater (BT19).
S. fault AH
35
- Sensor does not work (see "Temperature
sensor" section)
Supply alarm
The following alarms switch off heating/cooling. Only hot water production is permitted.
May be due to
Description
Alarm text on the dis-
play
Alarm
no.
- Sensor does not work (see "Temperature
sensor" section)
Too high a temperature (>90 °C) on supply line
sensor, system 1 (BT2).
High VBF1
10
- Sensor does not work (see "Temperature
sensor" section)
Too high a temperature (>90 °C) on supply line
sensor, system 2.
High VBF2
11
- Open-circuit or short-circuit on sensor input
Sensor fault, supply, system 1 (BT2).
Sensor fault VBF1
36
- Sensor does not work (see "Temperature
sensor" section)
- Open-circuit or short-circuit on sensor input
Sensor fault, supply, system 2.
Sensor fault VBF2
37
- Sensor does not work (see "Temperature
sensor" section)
NIBE™ SPLIT ACVM 270
64
Miscellaneous
Alarm list
Summary of Contents for ACVM 270
Page 2: ...LEK LEK 1 2 LEK LEK 7 LEK 5 6 LEK 3 4 LEK LEK LEK LEK AMS 10 8 LEK LEK AMS 10 12 ...
Page 67: ...67 NIBE SPLIT ACVM 270 Miscellaneous Electrical circuit diagram ...
Page 68: ...NIBE SPLIT ACVM 270 68 Miscellaneous Electrical circuit diagram ...
Page 69: ...69 NIBE SPLIT ACVM 270 Miscellaneous Electrical circuit diagram ...
Page 70: ...NIBE SPLIT ACVM 270 70 Miscellaneous Electrical circuit diagram ...
Page 94: ......
Page 95: ......