background image

www.nextups.eu 

36 

E

n

g

lish
 

Fig 5-11 

Overload: 

When  the  UPS  is  overload,  the  alarm 
will  beep  twice  every  second.  Some 
unnecessary loads should be get rid of 
one  by  one  to  decrease  the  loads 
connected to the UPS. 

Fig 5-12 

Battery Test 

UPS is executing a battery test

 

Fig 5-13 

Battery fail: 

if the battery status detected is “bad 
battery detected” or “battery 
disconnected”, the symbol of battery 
failure would be shown and UPS would 
alarm. 

5.3 Turning on and Turning off UPS 

Attention: 

The UPS could only be turning on while connecting with the 

utility for the first time. 

Attention:

 Please switch off the connected loads at first before turning 

on the UPS, and switch on the loads one by one after the UPS is turned 
on. Switch off all of the connected loads before turning off the UPS. 

5.3.1 Turning on UPS with utility 

1)

Check all the connection is correct.

2)

Power on the UPS, the fan begins to rotate, LCD will show the
“WELCOME”  logo.  After  that,  the  LCD  will  show  the  default
UPS status summary screen.

3)

Pressing

button  continuously  for  more  than  1  second,  the 

buzzer will beep 1s, UPS starts to turn on. 

Summary of Contents for LOGIX II RT NETPACK 10000VA

Page 1: ...NEXT UPS Systems LOGIX II RT 6000 10000 NETPACK Installation and user manual English...

Page 2: ...ower cables connection Startup 21 4 1 Access to terminal block 22 4 2 Common input sources connection 22 4 3 Separate input sources connection 23 4 4 Frequency converter connection 24 4 5 UPS Initial...

Page 3: ...8 1 Typical Alarms and Conditions 52 9 Communication 57 9 1 RS 232 and USB Communication Ports 57 9 2 Network Management Card Included 59 9 3 UPS Management Software 60 9 4 REPO Function 61...

Page 4: ......

Page 5: ...oise Power outages can occur when you least expect them and power quality can be erratic These power problems have the potential to corrupt critical data destroy unsaved work sessions and damage hardw...

Page 6: ...www nextups eu 2 English Figure 1 2 LOGIX II 10000 UPS LOGIX II UPS as Tower installation Figure 1 3 LOGIX II 6000 UPS Figure 1 4 LOGIX II 10000 UPS...

Page 7: ...attery capability for powering up the UPS even if utility power is not available Standard communication options one RS 232 communication port one USB communication port Optional connectivity cards wit...

Page 8: ...trip over them UPS has provided earthed terminal in the final installed system configuration equipotent earth bonding to the external UPS battery cabinets An integral single emergency switching devic...

Page 9: ...l code and have a contact air gap of at least 3 mm Uninterruptible power supply output power 240V 6000 VA 40 amp 2 pole circuit breaker 10000 VA 63 amp 2 pole circuit breaker You can connect four exte...

Page 10: ...ect the batteries Verify that no current is present and no hazardous voltage exist in the capacitor or BUS capacitor terminals Batteries must be replaced only by qualified personnel Caution the risk o...

Page 11: ...PS except the qualified maintenance personnel 2 4 Transport Please transport the UPS only in the original packaging to protect against shock and impact 2 5 Storage The UPS must be stockpiled in the ro...

Page 12: ...ency Magnetic field IEC EN 61000 4 8 Level 3 Low Frequency Signals IEC EN 61000 2 2 Warning This is a product for commercial and industrial application in the second environment installation restricti...

Page 13: ...file a claim for concealed damage Note Check the battery recharge date on the shipping carton label If the date has passed and the batteries were never recharged do not use the UPS Contact your servi...

Page 14: ...1 Open the outer carton and remove the accessories out of the carton see Figure 3 1 3 2 LOGIX II 6000 UPS Figure 3 1 Unpacking the carton of LOGIX II 6000 UPS LOGIX II 10000 UPS Figure 3 2 Unpacking t...

Page 15: ...nd set it on a flat stable surface see Figure 3 3 3 4 Place the cabinet in a protected area that has adequate airflow and is free of humidity flammable gas and corrosion Lifting the Cabinet Figure 3 3...

Page 16: ...out of LOGIX II 10000 UPS carton Step 3 Discard or recycle the packaging in a responsible manner or store it for future use 3 3 UPS Rear Panel This section shows the rear panel of the Online R T model...

Page 17: ...10000 model Figure 3 6 LOGIX II 10000 Rear Panel 3 4 UPS Front Panel This section shows the front panel of the LOGIX II UPS The Online series have the same LCD panel and the same control button Figur...

Page 18: ...ed or supervised by personnel with knowledge of batteries Keep unauthorized personnel away from batteries CAUTION If installing an EXB Extended Battery install the EXB directly below the UPS 3 5 1 Ins...

Page 19: ...6 Install the PDU s ears to the UPS Figure 3 12 Install the PDU s ears to the UPS 7 Select the proper holes in the rail for positioning the cabinet in the desired location in the rack Locate the rail...

Page 20: ...LOGIX II 6000 Replace the battery tray and connect the internal battery connector then replace the protection plate and the front panel 11 If installing additional UPSs repeat from Step 1 to Step 8 f...

Page 21: ...OGIX II 6000 Model 1 Plug the EXB cable into the UPS battery connector Figure 3 15 Plug the EXB cable into the UPS battery connector 2 Replace UPS s front panel and EXB s front panel Figure 3 16 Repla...

Page 22: ...English LOGIX II 10000 Model Figure 3 17 Plug the EXB cable into the UPS battery connector 3 6 Tower Setup Tower setup as below CAUTION Please connect the EXB to protective ground with 8 AWG wire for...

Page 23: ...connecting wires of seperated AC inputs you should confirm that their earthing systems are identical Otherwise a transformer is necessary UPS with common Normal and Bypass AC inputs UPS with separate...

Page 24: ...www nextups eu 20 English 2 Transformer in the Bypass AC input 3 Both of them have transformer Frequency converter without Bypass AC input...

Page 25: ...cross section 4mm 2 10AWG 6mm 2 8AWG Input fuse 60A 80A Output L N Min conductor cross section 4mm2 10AWG 6mm2 8AWG External Battery Cabinet Positive Pole Negative pole Neutral Pole Min conductor cro...

Page 26: ...block Access to terminal block remove the 2 screws of the terminal block cover Figure 4 1 PDU of LOGIX II 6000 10000 4 2 Common input sources connection CAUTION This type of connection must be carrie...

Page 27: ...t the earthing wire first Figure 4 2 Common input sources connection 4 3 Separate input sources connection CAUTION This type of connection must be carried out by qualified electrical personnel CAUTION...

Page 28: ...ad alarm 1 Verify that the internal batterties are connected 2 If optional EXBs are installed verify that the EXBs are connected to the UPS 3 Set the upstream circuit breaker not included to the I pos...

Page 29: ...output voltage setting at the next AC startup the UPS sets output voltage according to input line voltage After the subsequent startup auto sensing is disabled until manually re enabled by output volt...

Page 30: ...UPS parallel cable The length of the parallel cable is appropriate to be less than 3 m 3 Strictly follow the chapter of 4 the wiring requirement of single UPS to perform the wiring of each UPS 4 Indep...

Page 31: ...www nextups eu 27 English Figure 4 5 a Parallel systerm wiring diagram of LOGIX II 6000 1000...

Page 32: ...www nextups eu 28 English Figure 4 5 b Parallel System Installation Diagram...

Page 33: ...as follows When the distance between the UPS in parallel and the breaker panel is less than 10 meters the length difference between input and output cable of the UPSs is required to be less than 20 W...

Page 34: ...main maintenance mechanical switch or static switch should be installed for the parallel system 2 Ensure the bypass is normal and the bypass setting is enable press the button to turn off the UPS syst...

Page 35: ...text to dark amber and the background to red See Figure below Figure 5 1 LOGIX II 6000 10000 Rack On line UPS Control Panel Table 5 1 Control Button Functions The Button Function Illustration Power o...

Page 36: ...to select the present menu option or enter next menu but do not change any setting Select one menu option Press this button for 100ms 1s to select the present menu option or enter next menu but do not...

Page 37: ...screen it provides the following information Status summary including mode and load Alarm status if any are present Notes alarm including fault and warning information Battery and charger status inclu...

Page 38: ...pplied from the utility power via internal filter The UPS will beep once every 2 minutes in bypass mode Fig 5 6 Bypass without output The UPS in bypass mode without output Fig 5 7 High Efficiency Mode...

Page 39: ...inuously 1 The function could be enabled through the LCD setting or the software Winpower etc 2 The load should be derating to 80 in converter mode Fig 5 9 Warning When the warning occurs it illustrat...

Page 40: ...and Turning off UPS Attention The UPS could only be turning on while connecting with the utility for the first time Attention Please switch off the connected loads at first before turning on the UPS...

Page 41: ...S turns into Battery mode If the utility power comes back the UPS will transfer to Line mode without output interruption of the UPS 5 3 3 Turning off UPS with utility 1 Pressing button continuously fo...

Page 42: ...the settings to fit the user own requirements optimize the function of UPS 5 4 1 The main menu In the default UPS status summary screen when pressing or 1s the detailed information about alarm the sys...

Page 43: ...www nextups eu 39 English...

Page 44: ...out UPS status please see Fig5 14 5 4 3 The event log menu By pressing on the menu of Event log the display would enter the next event menu tree All the previous events alarm and fault have been recor...

Page 45: ...u of Measurement the display would enter the next measurement menu tree A lot of detailed useful information could be checked here Ex the output voltage and frequency the output current the load capac...

Page 46: ...e command that control the UPS to do the battery test 2 Clear EPO status once EPO status is enabled the UPS output would be cut off To recover to normal status first EPO connector should be closed and...

Page 47: ...rror status then UPS would stop alarm and recover to Bypass mode And the reason of fault should be checked and deleted before UPS is turned on again by manual operation 4 Restore factory settings all...

Page 48: ...al number firmware serial number model type would be shown here By press 1s the display would return the last main menu tree Figure 5 18 Identification menu tree 5 4 7 The setting menu Please contact...

Page 49: ...www nextups eu 45 English potential failures or protecting function loss even directly damage the load battery or UPS Most of settings could only be done while UPS is in Bypass mode...

Page 50: ...www nextups eu 46 English Figure 5 19 Setting menu tree Example set rated output voltage value Figure 5 20 Set rated output voltage value...

Page 51: ...on the frequency of usage and ambient temperature Batteries used beyond expected service life will often have severely reduced runtimes Replace batteries at least every 6 years to keep units running a...

Page 52: ...ct your service representative When to Replace Batteries When the status summary screen displays the UPS fault icon with the Service Battery alarm and the audible alarm sounds continuously the batteri...

Page 53: ...tteries for 25 of the original expected runtime The status screen displays Battery test running and the percentage of the test completed The results display on the UPS status screen as completing 6 5...

Page 54: ...10KVA 9KW Voltage Range 208VAC 220VAC 230VAC 240VAC 208VAC 220VAC 230VAC 240VAC Frequency 50 60Hz 50 60Hz Voltage Distortion 5 Nonlinear load 2 Linear load 5 Nonlinear load 2 Linear load Over Load Li...

Page 55: ...ension and Weight Dimension W D H mm 438 698 129 438 704 215 5 Net Weight KG 46 82 5 Gross Weight KG 50 87 5 7 3 Operating Environment Item Specification Function Standards Comments Cooling Force Air...

Page 56: ...onditions Alarm or Condition Possible cause Action ON Maintenance Bypass Alarm Code 72 UPS was manually commanded to switch to bypass and will remain in bypass until commanded out of bypass Check the...

Page 57: ...connect Alarm Code 11 Battery voltage is lower than the batteries disconnected level defined for this UPS This may be due to a blown fuse intermittent battery connection or battery cable being disconn...

Page 58: ...Short Circuit Alarm Code 31 Indicates that the UPS has detected abnormally low impedance placed on its output and considers it a short circuit Remove all the loads Turn off the UPS Check if UPS outpu...

Page 59: ...er voltage fault The UPS transfers to Bypass mode if supporting the load Inv Under Volatge Alarm Code 33 Indicates that the UPS get inverter under voltage fault The UPS transfers to Bypass mode if sup...

Page 60: ...fferent not allow turn on UPS Check bypass input Power strategy different Alarm Code E9 Parallel system UPS OP mode normal converter HE different Check UPS OP mode Keep OP mode be the same Rate power...

Page 61: ...etween you computer and the UPS The software will obtain the detailed information of the UPS on the status of the power environment If power emergency occurs the software initiates the saving of all d...

Page 62: ...ttery signal Out 9 Vdc Power 12V This pin is connected via a jumper to pin 2 of SNMP connector Out Figure 9 2 RS 232 Communication Port Figure 9 3 Pin1 Pin8 typical application Notes The voltage of V...

Page 63: ...series has one available communication bay for the following connectivity cards Connect UPS MS Web SNMP Card has SNMP and HTTP capabilities as well as monitoring through a Web browser interface connec...

Page 64: ...itor and control any UPS on the same LAN no matter how far from the UPSs Installation procedure 1 Go to the website http www nextups eu software 2 Choose the operation system you need and follow the i...

Page 65: ...Power Off interface provides an emergence power off function When the REPO function is enabled once the EPO port is pulled out the UPS would shut off the output and enter into EPO mode and the UPS wo...

Page 66: ...lish NEXT UPS Systems BELGIUM Releghem Business Park Poverstraat 138 B 1731 Relegem 32 2 540 89 14 THE NETHERLANDS Winthontlaan 200 3526 KV Utrecht 31 492 54 18 17 janvandijk nextups eu www nextups eu...

Reviews: