15
Distances between stove and a conventional brick Class 1 Chimney
(see figure 2A)
Refer to current National Laws, Building Regulations & any other Rules in Force, including BS
8303 and BS EN 15287-1:2007.
When installing this stove into a conventional class 1 non-combustible brick chimney built to building
regulations and any other rules in force including BS 8303 and BS EN 15287-1:2007 the clearances to
the sides and rear of stove required is 150mm, however providing all surrounding non-combustible
brick walls have a minimum thickness of 200mm the clearance between the rear & sides of stove can
be reduced to 50mm, refer to building regulations & any rules in force. However it is recommended
that the measurement between the sides & rear of stove to be as large as possible above this
dimension, as the efficiency of this stove is dependent on the clearances as shown in figure 2A.
Distance from the top of the stove to a
non-
combustible wall or fireplace above is recommended to
be a minimum of 200mm. Refer to building regulations & any other rules in force, including BS
8303 and BS EN 15287-1:2007 and refer to fireplace manufacturer’s instructions.
For all other clearances to a non-combustible brick wall and chimney
refer to Current National Laws,
Building Regulations & any other Rules in Force, including BS 8303 and BS EN 15287-1:2007.
Contact your local building authority regarding restrictions and installation requirements.