[ENG] NetPing IO v2, User guide -[ENG] [IOv2] Plugging Sensors
[ENG] [IOv2] Plugging Sensors
–
A sensor is a «dry contact», therefore an order of connecting wires does not matter.
Contact Name
One of IO Lines – 1 - 4
GND
A sensor will be displayed in a device interface as a status of an IO line to which it is connected.
A sensor is packaged with an inseparable cable, with connectors on the ends. A cable length can be increased with
the help of
sensor, which are sequentially plugged one into another. Or it can be done
independently with the help of any wire with a minimum cross section of 0,4 mm
2
. Maximum allowable length of a
flat cable is 100 m.
sockets is limited only by a number of available IO lines.
socket is connected, needs to be switched to a status
«output». When a status is a «logic 0», and 220V is
present on an IO line in a socket, the load will be switched on
. When a status is
«logic 1», and there is no voltage on
an
IO line in a socket, the load will be switched off.
Cable
Contact Name
Red
+U
Black
GND
Blue (green)
One of IO lines – 1 - 4
Plugging a Buzzer
Plugging to an IO line with the use of +12V:
Colored Loop
NetPing IO v2 Terminal
White
One of IO lines – 1 - 4
Important! A corresponding IO line must be set to an “input” mode in settings of a device.
Important! A brown (white) wire is not used and must stay unplugged!