background image

Net Safety Monitoring 
 

MAN-0101 Rev 01  UVIRS-H2-A/H2-AR & UVIRS-H2-A-X/H2-AR-X 

 

November 23, 2012 

 

Field of View 

 

The area in front of a flame detector, where a standardized flame can be 
detected and which is specified by distance and angle off the central axis, is 
the Field of View. The referenced flame is moved to 50% of the maximum 
on-axis detection distance and then moved off-axis horizontally and 
vertically to the limit of detection. These off-axis angle limits specify Field 
of View. 

 

Table 2: Field of View Testing 

Field of View Testing 

Fuel 

Size 

Horizontal 

Degrees 

Hydrogen(H2) 

24" Plume   128(+65, -63) 

NOTE: Data based on Maximum Sensitivity  
Setting. 

 

Installation Considerations 

The following should be considered when mounting flame detectors. 

 

Point detector toward where the flame is expected. 

 

Ensure an unobstructed view of the area to be monitored. 

 

Employ more than one detector to ensure the hazard is fully covered. 

 

The detector should be accessible for cleaning the window/lens

 

and 

reflector surfaces. 

 

Tilt detector downward a minimum of 10 to 20

°

 to reduce dirt and dust 

accumulation which could obscure the detector’s viewing window. 

 

Securely mount detector so as to reduce vibration as much as possible. 

 

When located outside, detector sensitivity can be reduced by heavy fog, 

rain and/or ice. 

 

Reduce sensitivity setting if false alarms, related to surrounding activities, 

occur (refer to "System Sensitivity" ) 

 

When installed near or on water (such as an off shore platform), be sure to 

take into account the low horizon level when tilting detector downward. 

 

UV radiation, other than that produced by an actual fire, is referred to as 

"background UV". An example of a high level of background UV could 
be a flare stack situated outside of a building. The UV radiation produced 
by this flare, in conjunction with a false alarm IR source, may be 
detected as fire when a door to the building is opened. Windows or other 
reflective surfaces may also cause unusually high levels of UV radiation 
to enter the building from the flare. In a situation like this, the fire 
detection system response must be carefully checked and the sensitivity 
level adjusted high enough so that this "background UV" will not cause 
false alarms. 

 

UV fire detectors respond to radiation other than ultraviolet. X-rays in 

conjunction with a false alarm IR source can activate the detector. Since 
X- rays are often used in industrial inspection it may be necessary to 
disable the system when inspections are conducted nearby. 

 

For protection against line surge and extraneous transients, it is required to 

install detector wires in a braided flexible conduit less than 5 feet. 

 

Note:

 CSA approved models (UVIRS-H2-A/AR) are not supplied with a 

locking collar. ATEX approved models (UVIRS-H2-A-X/H2-AR-X) are 
supplied with locking collar. 

 

 

 

Summary of Contents for UV/IRS-H2-A

Page 1: ...MAN 0101 Rev 01 UVIRS H2 A H2 AR UVIRS H2 A X H2 AR X November 23 2012 Ultraviolet Infrared Hydrogen Flame Detector User Manual Models UV IRS H2 A OR UV IRS H2 AR AND UV IRS H2 A X OR UV IRS H2 AR X...

Page 2: ......

Page 3: ...re carefully designed and manufactured from high quality components and can be expected to provide many years of trouble free service Each product is thoroughly tested inspected and calibrated prior t...

Page 4: ...the Housing 14 Relay Settings 14 Coil and Latch Status 14 Remote Reset 14 Final Setup 14 Detector Functionality 15 Detector Window Lens 15 Start Up Procedure 15 System Check 15 Monitor 15 Condition St...

Page 5: ...s not extend into the sensitivity range of the detector nor does radiation from normal artificial lighting such as fluorescent mercury vapour and incandescent lamps Locate Detector When positioning fi...

Page 6: ...s closer to the probable fire source and increasing the sensitivity can in some circumstances overcome this issue refer to Appendix A Immune The UV IRS H2 exhibits excellent immunity to many condition...

Page 7: ...ice Reduce sensitivity setting if false alarms related to surrounding activities occur refer to System Sensitivity When installed near or on water such as an off shore platform be sure to take into ac...

Page 8: ...ts from the packaging Check components against the enclosed packing list and inspect all components for obvious damage such as broken or loose parts If you find any components missing or damaged notif...

Page 9: ...e 2 Dimensional Drawing REFLECTOR POSITIONING Ensure the external VI reflector is placed directly over the VI Emitters refer to Figure 7 for VI source location Also ensure the detector is mounted with...

Page 10: ...ed to support wiring to any other electrical equipment Detectors can be located over 150 feet and up to 2000 feet if 16 AWG shielded conductor is used The maximum distance between the detector and the...

Page 11: ...pecific to A or AR configurations WARNING Prior to wiring ensure power is disconnected Improper wiring can cause damage to the detector Figure 4 Wire Colour Coding ANALOG FLAME DETECTOR WIRE CODING Wi...

Page 12: ...l block FIELD WIRING Terminal Function RRst Remote Reset MVI Manual VI SIG 4 20mA Signal Output PWR Com PWR Vdc FLAME DETECTOR WIRING Terminal Wire Function B Blue Manual VI Communication R Red 4 20mA...

Page 13: ...r is ATEX approved and has a locking collar that requires a 2mm Hex key to open WARNING Do not touch internal components other than the DIP Switches see Appendix B Electrostatic Sensitive Device ESD T...

Page 14: ...he default Fire Relay is normally De energized Non Latching The Fault Relay is factory set to normally Energized Non latching and cannot be modified Table 4 Relay Setting Junction Box Coil and Latch S...

Page 15: ...seconds Once the start up procedure has finished and no faults are present the detector will begin normal operation current output 4 mA and Green LED will remain on System Check Once powered up the s...

Page 16: ...Signal Output Table 5 Status LEDs and Current Output LED Status Current O P Green LED PWR Red LED Alarm Yellow LED Fault Internal power Fault or system power out of range 1mA OFF Solid Automatic or m...

Page 17: ...st The detector performs an automatic Visual Integrity VI test every 90 seconds during normal operation If the lens is dirty obstructed or the reflector is dirty obstructed or misaligned the unit will...

Page 18: ...this voltage for at least two seconds The Green and Red LED will be activated for the duration of the test 3 The detector will output a current that corresponds to the quality of the VI reading obtain...

Page 19: ...The housing should be opened periodically and the o ring inspected for breaks cracks or dryness To test the o ring remove it from the detector housing and stretch it slightly If cracks are visible th...

Page 20: ...nt can determine and correct the problem 3 A company name contact name and telephone number 4 A Purchase Order from your company authorizing repairs or request for quote 5 Ship all equipment prepaid t...

Page 21: ...ive PWR Com close current loop 6 mA Solid Background UV source Confirm external UV source by covering detector window so it is blind to all radiation If signal goes away background UV is present Field...

Page 22: ...tors may become blind as not enough ultra violet radiation can reach them to activate an alarm Moving detectors closer to the probable source of fire and increasing the sensitivity of the detector can...

Page 23: ...seemingly normal for an indefinite period of time followed by a sudden failure To eliminate potential ESD damage review the following guidelines Handle boards by metal shields taking care not to touc...

Page 24: ...Net Safety Monitoring MAN 0101 Rev 01 UVIRS H2 A H2 AR UVIRS H2 A X H2 AR X 24 November 23 2012 APPENDIX C RESISTANCE TABLE...

Page 25: ...Output 0 to 20 mA Into a max loop impedance of 800Ohms 32Vdc or 150Ohms 11 0Vdc Non Isolated loop supply Relay Output N A Form C contacts rated 1A 30Vdc 0 5A 125Vac Selectable energized de energized l...

Page 26: ...p No Effect at 5 Ft No Effect at 5 Ft No Effect at 5 Ft No Effect at 5 Ft 70W Hi Pressure Sodium Lamp No Effect at 5 Ft No Effect at 5 Ft No Effect at 5 Ft No Effect at 5 Ft 250W Metal Halide No Effec...

Page 27: ...ty Monitoring MAN 0101 Rev 01 UVIRS H2 A H2 AR UVIRS H2 A X H2 AR X 27 November 23 2012 APPENDIX F UVIRS H2 GRAPHICAL FIELD OF VIEW DATA UVIRS H2 Field of View with a 24 Plume at a distance of 55 feet...

Page 28: ...S 347 3427 ph 403 219 0688 fx 403 219 0694 http www net safety com Email nsmsales net safety com PRODUCT SERVICES CONTACT INFORMATION Telephone 8am 5pm MDT 403 769 6074 403 717 8219 Fax 403 219 0694 E...

Page 29: ...less than 10Vdc Detector internal power supply failure Replace power supply Confirm supply voltage 10 32Vdc to detector Contact factory 1 6mA Fault Flashing Yellow LED See Figure 7 on page 15 when loc...

Reviews: