background image

Net Safety Monitoring 

 

MAN-0101 Rev 01 UVIRS-H2-A/H2-AR & UVIRS-H2-A-X/H2-AR-X 

17 

 

November 23, 2012 

 

 

 

 

 

 

 

D

ETECTOR 

M

AINTENANCE

 

Although an automatic testing of the optics is done every 90 seconds, the 
system should be periodically checked. To maintain maximum sensitivity, 
the viewing window and reflector should be cleaned on a routine basis 
depending on the type and amount of contaminants in the area. 

T

ESTING

 

WARNING:

 

   When testing the system, ensure all external equipment is 

disabled to prevent unwanted activation.  

Manual Check Procedure  

The whole system should be checked periodically with a Net Safety UV/IR 
test lamp to make sure that the detectors are not obstructed, that the area 
covered by the detector has not changed and that there is no fault in the VI 
circuit. 

1.  

Activate and direct the UV/IR test lamp at the detector viewing window. 
The current output will change with the amount of radiation being 
detected and the Red LED will flash (refer to “ Table 5 - Status LEDs 
and Current Output”). 

2.  

Turn off the UV/IR test lamp after successful check. 

3.  

Repeat steps 1 & 2 for all detectors in the system. 

4.  

After all detectors have been checked, return the system to the normal 
operating mode and enable any external equipment. 

Automatic Visual Integrity (VI) Test 

The detector performs an automatic Visual Integrity (VI) test every 90 
seconds during normal operation. If the lens is dirty, obstructed, or the 
reflector is dirty, obstructed or misaligned, the unit will perform a number of 
VI tests to confirm the presence of the obstruction. 

If the obstruction is temporary, the unit will return to normal after the 
obstruction is removed. If the obstruction remains, the unit will drop the 
current output to 2 mA and the yellow LED will flash continuously 
indicating a misaligned reflector, failed sensor or contaminants on the 
window or reflector. The detector will remain in this condition until the 
problem is corrected. The detector window should be promptly cleaned (refer 
to "Cleaning window/Lens & reflector" ) or the obstruction removed. Also 
refer to the troubleshooting section – Possible Problems & Solutions. 

 

Manual VI Test 

 

This test procedure can assist with maintenance planning and is often 
performed during commissioning. The detector has a manual VI input and 
the manual VI test is performed by: 
 

 

connecting Manual VI to system power by a direct connection OR 

 

connecting a momentary contact push button between system power and 

the manual VI input. 

 

The Net Safety Junction Box is optional and is available with or without a 

Manual VI Test Switch (for Analog models). Activate the Manual VI 
Test Switch with the magnet if the switch is available, otherwise use 
other available options mentioned above for manual VI Test. 

Summary of Contents for UV/IRS-H2-A

Page 1: ...MAN 0101 Rev 01 UVIRS H2 A H2 AR UVIRS H2 A X H2 AR X November 23 2012 Ultraviolet Infrared Hydrogen Flame Detector User Manual Models UV IRS H2 A OR UV IRS H2 AR AND UV IRS H2 A X OR UV IRS H2 AR X...

Page 2: ......

Page 3: ...re carefully designed and manufactured from high quality components and can be expected to provide many years of trouble free service Each product is thoroughly tested inspected and calibrated prior t...

Page 4: ...the Housing 14 Relay Settings 14 Coil and Latch Status 14 Remote Reset 14 Final Setup 14 Detector Functionality 15 Detector Window Lens 15 Start Up Procedure 15 System Check 15 Monitor 15 Condition St...

Page 5: ...s not extend into the sensitivity range of the detector nor does radiation from normal artificial lighting such as fluorescent mercury vapour and incandescent lamps Locate Detector When positioning fi...

Page 6: ...s closer to the probable fire source and increasing the sensitivity can in some circumstances overcome this issue refer to Appendix A Immune The UV IRS H2 exhibits excellent immunity to many condition...

Page 7: ...ice Reduce sensitivity setting if false alarms related to surrounding activities occur refer to System Sensitivity When installed near or on water such as an off shore platform be sure to take into ac...

Page 8: ...ts from the packaging Check components against the enclosed packing list and inspect all components for obvious damage such as broken or loose parts If you find any components missing or damaged notif...

Page 9: ...e 2 Dimensional Drawing REFLECTOR POSITIONING Ensure the external VI reflector is placed directly over the VI Emitters refer to Figure 7 for VI source location Also ensure the detector is mounted with...

Page 10: ...ed to support wiring to any other electrical equipment Detectors can be located over 150 feet and up to 2000 feet if 16 AWG shielded conductor is used The maximum distance between the detector and the...

Page 11: ...pecific to A or AR configurations WARNING Prior to wiring ensure power is disconnected Improper wiring can cause damage to the detector Figure 4 Wire Colour Coding ANALOG FLAME DETECTOR WIRE CODING Wi...

Page 12: ...l block FIELD WIRING Terminal Function RRst Remote Reset MVI Manual VI SIG 4 20mA Signal Output PWR Com PWR Vdc FLAME DETECTOR WIRING Terminal Wire Function B Blue Manual VI Communication R Red 4 20mA...

Page 13: ...r is ATEX approved and has a locking collar that requires a 2mm Hex key to open WARNING Do not touch internal components other than the DIP Switches see Appendix B Electrostatic Sensitive Device ESD T...

Page 14: ...he default Fire Relay is normally De energized Non Latching The Fault Relay is factory set to normally Energized Non latching and cannot be modified Table 4 Relay Setting Junction Box Coil and Latch S...

Page 15: ...seconds Once the start up procedure has finished and no faults are present the detector will begin normal operation current output 4 mA and Green LED will remain on System Check Once powered up the s...

Page 16: ...Signal Output Table 5 Status LEDs and Current Output LED Status Current O P Green LED PWR Red LED Alarm Yellow LED Fault Internal power Fault or system power out of range 1mA OFF Solid Automatic or m...

Page 17: ...st The detector performs an automatic Visual Integrity VI test every 90 seconds during normal operation If the lens is dirty obstructed or the reflector is dirty obstructed or misaligned the unit will...

Page 18: ...this voltage for at least two seconds The Green and Red LED will be activated for the duration of the test 3 The detector will output a current that corresponds to the quality of the VI reading obtain...

Page 19: ...The housing should be opened periodically and the o ring inspected for breaks cracks or dryness To test the o ring remove it from the detector housing and stretch it slightly If cracks are visible th...

Page 20: ...nt can determine and correct the problem 3 A company name contact name and telephone number 4 A Purchase Order from your company authorizing repairs or request for quote 5 Ship all equipment prepaid t...

Page 21: ...ive PWR Com close current loop 6 mA Solid Background UV source Confirm external UV source by covering detector window so it is blind to all radiation If signal goes away background UV is present Field...

Page 22: ...tors may become blind as not enough ultra violet radiation can reach them to activate an alarm Moving detectors closer to the probable source of fire and increasing the sensitivity of the detector can...

Page 23: ...seemingly normal for an indefinite period of time followed by a sudden failure To eliminate potential ESD damage review the following guidelines Handle boards by metal shields taking care not to touc...

Page 24: ...Net Safety Monitoring MAN 0101 Rev 01 UVIRS H2 A H2 AR UVIRS H2 A X H2 AR X 24 November 23 2012 APPENDIX C RESISTANCE TABLE...

Page 25: ...Output 0 to 20 mA Into a max loop impedance of 800Ohms 32Vdc or 150Ohms 11 0Vdc Non Isolated loop supply Relay Output N A Form C contacts rated 1A 30Vdc 0 5A 125Vac Selectable energized de energized l...

Page 26: ...p No Effect at 5 Ft No Effect at 5 Ft No Effect at 5 Ft No Effect at 5 Ft 70W Hi Pressure Sodium Lamp No Effect at 5 Ft No Effect at 5 Ft No Effect at 5 Ft No Effect at 5 Ft 250W Metal Halide No Effec...

Page 27: ...ty Monitoring MAN 0101 Rev 01 UVIRS H2 A H2 AR UVIRS H2 A X H2 AR X 27 November 23 2012 APPENDIX F UVIRS H2 GRAPHICAL FIELD OF VIEW DATA UVIRS H2 Field of View with a 24 Plume at a distance of 55 feet...

Page 28: ...S 347 3427 ph 403 219 0688 fx 403 219 0694 http www net safety com Email nsmsales net safety com PRODUCT SERVICES CONTACT INFORMATION Telephone 8am 5pm MDT 403 769 6074 403 717 8219 Fax 403 219 0694 E...

Page 29: ...less than 10Vdc Detector internal power supply failure Replace power supply Confirm supply voltage 10 32Vdc to detector Contact factory 1 6mA Fault Flashing Yellow LED See Figure 7 on page 15 when loc...

Reviews: