Net Safety Monitoring
MAN-0101 Rev 01 UVIRS-H2-A/H2-AR & UVIRS-H2-A-X/H2-AR-X
26
November 23, 2012
A
PPENDIX
E:
UVIRS-H2
DATA
In Door Interference and false alarm Test
Un-Modulated
without fire
Modulated with out
fire
Un-Modulated with
fire
Modulated with fire
Electrical
Heater(1000W)
No Effect at 5 Ft
8mA output at 3Hz, 5
Ft, no effect other
frequency or at 15 Ft
No Effect at 5 Ft
No Effect at 5 Ft
300W Halogen
Lamp
No Effect at 5 Ft
8mA output at 3Hz, 5
Ft, no effect other
frequency or at 15 Ft
No Effect at 5 Ft
No Effect at 5 Ft
40W
Fluorescent
Lamp
No Effect at 5 Ft
No Effect at 5 Ft
No Effect at 5 Ft
No Effect at 5 Ft
70W
Hi
Pressure
Sodium Lamp
No Effect at 5 Ft
No Effect at 5 Ft
No Effect at 5 Ft
No Effect at 5 Ft
250W
Metal
Halide
No Effect at 5 Ft
No Effect at 5 Ft
No Effect at 5 Ft
No Effect at 5 Ft
Out Door Interference and false alarm Test
Un-Modulated
without fire
Modulated with out
fire
Un-Modulated with
fire
Modulated with fire
Direct Sunlight
No Effect
8mA output at 3Hz,
no effect at other
frequency
No Effect
No Effect
Indirect
Sunlight
No Effect
8mA output at 3Hz,
no effect at other
frequency
No Effect
No Effect
Arc Welding
No Effect further than
20 Ft. False alarm at
15Ft
6mA output at 20 Ft
False alarm at 15Ft
No Effect farther than
20 Ft
No Effect farther than
20 Ft
Summary of Contents for UV/IRS-H2-A
Page 2: ......