Net Safety Monitoring
MAN-0101 Rev 01 UVIRS-H2-A/H2-AR & UVIRS-H2-A-X/H2-AR-X
16
November 23, 2012
Condition Status
—
Current Output
The Current Loop status can also be measured to determine detector
condition.
Test Jacks are available on the Analog board in the Net Safety Multi-Purpose
Junction Box. Refer to MAN-0081 for details. The area must be de-classified
prior to opening the Junction Box. The detector can also be monitored using
the 4-20 mA Signal Output.
Table 5: Status LEDs and Current Output
LED Status
Current
O/P
Green LED
(PWR)
Red LED
(Alarm)
Yellow LED
(Fault)
Internal power
Fault or
system power
out of range
1mA
OFF
Solid
Automatic or
manual VI
Test Failure
2mA
OFF
OFF
Flashing
Power up – 90
secs start delay
3mA
Solid
OFF
OFF
Normal
Operation
4mA
Solid
OFF
OFF
Background
UV Source
6mA
Solid
OFF
OFF
Background
IR Source
8mA
Solid
OFF
OFF
Manual VI
Testing
Adequate
10mA
Solid
Solid
OFF
Manual VI
Testing Good
11mA
Solid
Solid
OFF
Manual VI
Testing
Excellent
12mA
Solid
Solid
OFF
Early Warning
– Intermittent
UV/IR
detected
16mA
Solid
OFF
OFF
Fire
Confirmed
20mA
OFF
Flashing
OFF