High Pressure Atomiser Series
BACnet Communication Module User Guide
www.neptronic.com
Page | 13
Binary Output (BO)
Table 8 - Object Table Information: Binary Output (BO)
ID
Name
Description
W?
Notes
BO.1
AlarmRelay
Select whether to open or close the alarm relay. Closed when any
alarm is on but AirFlowCutout and ServiceWarning.
Present Value
Relinquish
Default
0 = Open, 1 = Close
BO.2
MaintenanceRelay
Select whether to open or close the maintenance relay. Closed
when ServiceAlarm or ServiceWarning is on.
Present Value
Relinquish
Default
0 = Open, 1 = Close
BO.3
Buzzer
Select whether to activate or not the buzzer. ON when a key push
event is acknowledged and KeyBeep is on or when AlarmRelay is
closed and AlarmBeep is on.
Present Value
0 = Inactive, 1 = Active
SKH EZC
ID
Name
Description
W?
Notes
Integrator
BO.1
FanControl
Displays the status of Fan control.
Read Only
0 =Off, 1 = On
Advanced
BO.200
ZoneDrain
Displays the status of zone drain.
Read Only
0 = Off, 1 = On
BO.201
ZoneInlet
Displays the status of zone inlet.
Read Only
0 =Off, 1 = On
Binary Value (BV)
Table 9 - Object Table Information: Binary Value (BV)
ID
Name
Description
W?
Notes
Integrator
BV.1
SystemMode
Select to whether to enable or disable the system mode.
Present Value
0 = Off, 1 = On
BV.2
SimulationState
Displays the status of the simulation state.
Read Only
0 = Off, 1 = On
BV.3
SimulationPumpOverride
Displays the status of the simulation pump override.
Read Only
0 = Off, 1 = On
BV.4
SystemDrainPending
Displays the status of the system drain pending.
Read Only
0 = Off, 1 = On
BV.5
SystemDrain
Displays the status of the system drain.
Read Only
0 = Off, 1 = On
BV.6
SystemZoneDemand
Displays the status of system zone demand.
Read Only
0 = Off, 1 = On
BV.7
WaterPressureState
Displays the status of the water pressure state.
Read Only
0 = Not Ready, 1 = Ready