High Pressure Atomiser Series 

BACnet Communication Module User Guide

 

 

www.neptronic.com

 

Page | 11 

 

ID 

Name 

Description 

W? 

Notes 

AV.102 

Cfg_NetworkTimeout 

Configuration value of the network timeout. 

Present Value

 

1 to 15 minutes, Resolution 1 minute 

AV.103 

Cfg_FanOnDelay 

Configuration value of the delay in seconds before the fan is turned on.  

Present Value 

1 to 255 seconds, Resolution 1 second 

AV.104 

Cfg_FanOffDelay 

Configuration value of the delay in seconds before the fan is turned off.  

Present Value 

1 to 255 seconds, Resolution 1 second 

Advanced 

 

AV.200 

Stage1Runtime 

Displays the value of the stage 1 runtime. 

Read Only 

0 to 42949672.95, Resolution 1 

AV.201 

Stage2Runtime 

Displays the value of the stage 2 runtime. 

Read Only 

0 to 42949672.95, Resolution 1 

AV.202 

Stage3Runtime 

Displays the value of the stage 3 runtime. 

Read Only 

0 to 42949672.95, Resolution 1 

AV.203 

Stage4Runtime 

Displays the value of the stage 4 runtime. 

Read Only 

0 to 42949672.95, Resolution 1 

Advanced 

– Configuration

 

AV.300 

Cfg_DuctRHSetpoint 

Configuration value of the duct relative humidity setpoint. 

Present Value 

10% RH to 90% RH, Resolution 0.1% RH 

AV.301 

Cfg_DuctRHCutout 

Configuration value of the duct relative humidity cutout. 

Present Value 

50% RH to 95% RH, Resolution 0.1% RH 

AV.302 

Cfg_DuctRHPropBand 

Configuration value of the duct relative humidity proportional band. 

Present Value 

5% RH to 50% RH, Resolution 0.1% RH 

AV.303 

Cfg_DuctRHIntegralTime 

Configuration value of the duct relative humidity integral time. 

Present Value 

0 to 600 seconds, Resolution 1 second 

AV.304 

Cfg_DuctRHDerivateTime 

Configuration value of the duct relative humidity derivate time. 

Present Value 

0 to 60 seconds, Resolution 0.1 seconds 

AV.305 

Cfg_RHProportionalBand 

Configuration value of the relative humidity proportional band.  

Present Value 

1% RH to 20% RH, Resolution 0.1%RH 

AV.306 

Cfg_TempProportionalBand 

Configuration value of the temperature proportional band.  

Present Value 

0.5°C to 50°C, Resolution 0.01°C 

AV.307 

Cfg_IntegralTime 

Configuration value of the integral time.  

Present Value 

0 to 600 seconds, Resolution 1 second.  

AV.308 

Cfg_DifferentialTime 

Configuration value of the differential time.  

Present Value 

0 to 60 seconds, Resolution 0.1 second 

AV.309 

Cfg_TrlhRHSetpointMin 

Configuration value of the minimum relative humidity setpoint measured 
by the TRL.  

Present Value 

 5% RH to AV.310, Resolution 0.1% RH 

AV.310 

Cfg_TrlhRHSetpointMax 

Configuration value of the maximum relative humidity setpoint measured 
by the TRL. 

Present Value 

AV.309 to 95% RH, Resolution 0.1% RH 

AV.311 

Cfg_TrlhTempSetpointMin 

Configuration value of the minimum temperature setpoint measured by 
the TRL.   

Present Value 

10°C to AV.312, Resolution 0.01°C 

AV.312 

Cfg_TrlhTempSetpointMax 

Configuration value of the maximum temperature setpoint measured by 
the TRL.  

Present Value 

AV.311 to 40°C, Resolution 0.01°C 

AV.313 

Cfg_RoomRHSetpointMin 

Configuration value of the minimum relative humidity setpoint of the 
room.  

Present Value 

0% RH to AV.314, Resolution 0.1% RH 

AV.314 

Cfg_RoomRHSetpointMax 

Configuration value of the maximum relative humidity setpoint of the 
room.  

Present Value 

AV.313 to 100% RH, Resolution 0.1% RH 

AV.315 

Cfg_RoomTempSetpointMin 

Configuration value of the minimum temperature setpoint of the room.  

Present Value 

10°C to AV.316, Resolution 0.01°C 

AV.316 

Cfg_RoomTempSetpointMax 

Configuration value of the maximum temperature setpoint of the room.  

Present Value 

AV.315 to 40°C, Resolution 0.01°C 

AV.317 

Cfg_RoomRHMin 

Configuration value of the minimum relative humidity of the room.  

Present Value 

0%RH to AV.317, Resolution 0.1%RH 

AV.318 

Cfg_RoomRHMax 

Configuration value of the maximum relative humidity of the room.  

Present Value 

AV.316 to 100%RH, Resolution 0.1%RH 

Summary of Contents for SKH Series

Page 1: ...SKH BACnet Guide 200114 High Pressure Atomiser SKH Series BACnet User Guide...

Page 2: ...guration Options 3 Quick Setup 3 Manual Setup 3 MAC Address and Max_Master 3 Network Reset 4 Device Object Properties 5 Object Types Supported 6 Out of Service Property 7 Object Table Information 8 An...

Page 3: ...is performed within Tusage_delay of 15 minutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The humidifier supports a Full Master Node state machine for MS TP Max_Master and the in...

Page 4: ...ntifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decimal or hexadecimal representation tends to be incomprehensible F...

Page 5: ...nally poll for other masters based on the MAC address and Max_Master A poor combination of MAC addresses and Max_Master can lead to a slower network due to lost time polling for masters that are not p...

Page 6: ...address in the system If consecutive numbering is not possible then the next most efficient setup is one in which all units have Max_Master the maximum MAC address in the system Network Reset Reset t...

Page 7: ...taBase_Revision 2 Read Only Max_APDU_Length_Accepted Always 480 Read Only Segmentation_Supported 3 No Segmentation Read Only APDU_Timeout 6000 W Number_of_APDU_Retries Always 3 Read Only Local_Time 00...

Page 8: ...ter a programmable period of time Refer to Proprietary property 1002 of Device Object in Table 2 Device Object Properties Analog Value Reliability Description COV Increment Priority_Array Relinquish_D...

Page 9: ...1000 1001 1002 Configuration_Files Last_Restore_Time Backup_And_Restore_State Backup_Preparation_Time Restore_Completion_time Restore_Preparation_Time Refer to Table 2 Device Object Properties on pag...

Page 10: ...isplays the setpoint for the room relative humidity sensor OR Displays the setpoint for the room temperature sensor Out of Service 0 0 to 100 0 RH or 10 C to 40 C Resolution 0 1 RH or 0 01 C AI 4 Room...

Page 11: ...SimulationZoneDemand Configuration value of the demand of the simulation zones Present Value 0 to 4 Resolution 1 AV 6 SimulationPumpSelection Configuration value for the selection of the simulation p...

Page 12: ...humidity setpoint in the unoccupied mode Present Value 5 RH to 95 RH Resolution 0 1 RH AV 6 UnoccupiedTempSetpoint Configuration value of the temperature setpoint in the unoccupied mode Present Value...

Page 13: ...humidity proportional band Present Value 1 RH to 20 RH Resolution 0 1 RH AV 306 Cfg_TempProportionalBand Configuration value of the temperature proportional band Present Value 0 5 C to 50 C Resolution...

Page 14: ..._RoomTempOffset Configuration value of the temperature offset value of the room Present Value 10 C to 10 C Resolution 0 01 C AV 328 Cfg_DuctRHOffset Configuration value of the relative humidity offset...

Page 15: ...egrator BO 1 FanControl Displays the status of Fan control Read Only 0 Off 1 On Advanced BO 200 ZoneDrain Displays the status of zone drain Read Only 0 Off 1 On BO 201 ZoneInlet Displays the status of...

Page 16: ...1 On BV 218 AL_PumpOutputPressureSensorFailure Displays the status of the pump output pressure sensor failure Read Only 0 Off 1 On BV 222 AL_PumpVFDFailure Displays the status of the pump VFD failure...

Page 17: ...o long Read Only 0 Off 1 On BV 280 AL_Zone7ComTimeout Displays the status of communication timeout for the zone 7 It indicates that the communication delay is too long Read Only 0 Off 1 On BV 281 AL_Z...

Page 18: ...08 Cfg_TRLHDisplayTime Select whether to display the time on the TRL Present Value 0 Off 1 On BV 109 Cfg_TRLHTimeFormat Select the time format on the TRL Present Value 0 24H 1 12H Advanced BV 200 Simu...

Page 19: ...100 Cfg_PressureUnits Configuration value to select the pressure units Present Value 1 kPa 2 PSI 3 Bar MSV 101 Cfg_Language Select the language of the BACnet server Present Value 1 English MSV 102 Cf...

Page 20: ...tSource Configuration value to select the control setpoint source Present Value 1 AI3 2 Internal 3 Network MSV 104 Cfg_HighLimitSource Configuration value to select high limit source for analog input...

Page 21: ...le and atomicReadFile FIL 4 PumpBootloaderUpdateFile File object for pump bootloader upgrade File_Size Archive Stream access method via atomicWriteFile and atomicReadFile PGM 1 FirmwareUpdateTask Firm...

Page 22: ...Notes...

Page 23: ......

Page 24: ...u blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm East...

Reviews: