High Pressure Atomiser Series
BACnet Communication Module User Guide
www.neptronic.com
Page | 11
ID
Name
Description
W?
Notes
AV.102
Cfg_NetworkTimeout
Configuration value of the network timeout.
Present Value
1 to 15 minutes, Resolution 1 minute
AV.103
Cfg_FanOnDelay
Configuration value of the delay in seconds before the fan is turned on.
Present Value
1 to 255 seconds, Resolution 1 second
AV.104
Cfg_FanOffDelay
Configuration value of the delay in seconds before the fan is turned off.
Present Value
1 to 255 seconds, Resolution 1 second
Advanced
AV.200
Stage1Runtime
Displays the value of the stage 1 runtime.
Read Only
0 to 42949672.95, Resolution 1
AV.201
Stage2Runtime
Displays the value of the stage 2 runtime.
Read Only
0 to 42949672.95, Resolution 1
AV.202
Stage3Runtime
Displays the value of the stage 3 runtime.
Read Only
0 to 42949672.95, Resolution 1
AV.203
Stage4Runtime
Displays the value of the stage 4 runtime.
Read Only
0 to 42949672.95, Resolution 1
Advanced
– Configuration
AV.300
Cfg_DuctRHSetpoint
Configuration value of the duct relative humidity setpoint.
Present Value
10% RH to 90% RH, Resolution 0.1% RH
AV.301
Cfg_DuctRHCutout
Configuration value of the duct relative humidity cutout.
Present Value
50% RH to 95% RH, Resolution 0.1% RH
AV.302
Cfg_DuctRHPropBand
Configuration value of the duct relative humidity proportional band.
Present Value
5% RH to 50% RH, Resolution 0.1% RH
AV.303
Cfg_DuctRHIntegralTime
Configuration value of the duct relative humidity integral time.
Present Value
0 to 600 seconds, Resolution 1 second
AV.304
Cfg_DuctRHDerivateTime
Configuration value of the duct relative humidity derivate time.
Present Value
0 to 60 seconds, Resolution 0.1 seconds
AV.305
Cfg_RHProportionalBand
Configuration value of the relative humidity proportional band.
Present Value
1% RH to 20% RH, Resolution 0.1%RH
AV.306
Cfg_TempProportionalBand
Configuration value of the temperature proportional band.
Present Value
0.5°C to 50°C, Resolution 0.01°C
AV.307
Cfg_IntegralTime
Configuration value of the integral time.
Present Value
0 to 600 seconds, Resolution 1 second.
AV.308
Cfg_DifferentialTime
Configuration value of the differential time.
Present Value
0 to 60 seconds, Resolution 0.1 second
AV.309
Cfg_TrlhRHSetpointMin
Configuration value of the minimum relative humidity setpoint measured
by the TRL.
Present Value
5% RH to AV.310, Resolution 0.1% RH
AV.310
Cfg_TrlhRHSetpointMax
Configuration value of the maximum relative humidity setpoint measured
by the TRL.
Present Value
AV.309 to 95% RH, Resolution 0.1% RH
AV.311
Cfg_TrlhTempSetpointMin
Configuration value of the minimum temperature setpoint measured by
the TRL.
Present Value
10°C to AV.312, Resolution 0.01°C
AV.312
Cfg_TrlhTempSetpointMax
Configuration value of the maximum temperature setpoint measured by
the TRL.
Present Value
AV.311 to 40°C, Resolution 0.01°C
AV.313
Cfg_RoomRHSetpointMin
Configuration value of the minimum relative humidity setpoint of the
room.
Present Value
0% RH to AV.314, Resolution 0.1% RH
AV.314
Cfg_RoomRHSetpointMax
Configuration value of the maximum relative humidity setpoint of the
room.
Present Value
AV.313 to 100% RH, Resolution 0.1% RH
AV.315
Cfg_RoomTempSetpointMin
Configuration value of the minimum temperature setpoint of the room.
Present Value
10°C to AV.316, Resolution 0.01°C
AV.316
Cfg_RoomTempSetpointMax
Configuration value of the maximum temperature setpoint of the room.
Present Value
AV.315 to 40°C, Resolution 0.01°C
AV.317
Cfg_RoomRHMin
Configuration value of the minimum relative humidity of the room.
Present Value
0%RH to AV.317, Resolution 0.1%RH
AV.318
Cfg_RoomRHMax
Configuration value of the maximum relative humidity of the room.
Present Value
AV.316 to 100%RH, Resolution 0.1%RH