High Pressure Atomiser Series
BACnet Communication Module User Guide
www.neptronic.com
Page | 7
Object
Type
Enabled
Optional Properties
Supported
Writable Properties
Notes
•
Priority_Array
•
Relinquish_Default
know the writable property for each BV object.
•
Out_of_Service property is writable for every Binary
Value object.
•
Some objects are commandable. In such case, the
priority-array and relinquish-default properties are
available.
•
Object automatically returns to Normal after a
programmable time. Refer to Proprietary property
#1002 of Device Object in Table 2 - Device Object
Properties.
Binary
Output
•
description
•
reliability
•
inactive-text
•
active-text
Present_Value
•
Present_Value property is writable.
Device
•
Max_Master
•
Max_Info_Frame
•
Description
•
active-cov-subscriptions
•
#1000 (MSTP addr)
•
#1001 (Baud rate)
•
#1002 (Time out)
•
Local_Time
•
Local_Date
•
Uts_Offset
•
Daylight_Savings_Status
•
Apdu_Timeout
•
Backup_Failure_Timeout
•
Object_Identifier
•
Object_Name
•
Max_Master
•
Description
•
Local_Time
•
Local_Date
•
Uts_Offset
•
Daylight_Savings_Status
•
Apdu_Timeout
•
Backup_Failure_Timeout
•
#1000
•
#1001
•
#1002
•
Configuration_Files
•
Last_Restore_Time
•
Backup_And_Restore_State
•
Backup_Preparation_Time
•
Restore_Completion_time
•
Restore_Preparation_Tim
e
•
Refer to Table 2 - Device Object Properties on page
Multi-
State
Value
•
Description
•
Reliability
•
States_Text
Present_Value
•
Present_Value property is writable for every Multi
State Value object except MSV.12, MSV.13, MSV.15
•
Writable properties are different for some objects.
Refer to the respective Object Table information to
know the writable property for each MSV object.
•
Out_of_Service property is not writable for MSV.
Out of Service Property
Neptronic humidifiers offer the use of the Out of Service writable property. When the value of this property is set to True,
it disconnects the object from the physical input, enabling you to input other values. This is useful for special applications
or while troubleshooting. For example, you can ignore the temperature read from a sensor and input the desired
temperature value in order to perform specific tests.
For security reasons, a timeout will set the Out of Service property back to False after 15 minutes. This value can be
modified to between 0 and 120 minutes (For more information, see proprietary property #1002 in