High Pressure Atomiser Series 

BACnet Communication Module User Guide

 

 

www.neptronic.com

 

Page | 5 

 

 

Device Object Properties 

The following table lists all the BACnet properties supported for the device object. The W indicates that the property is 
writable using the BACnet 

WriteProperty

 service. 

Table 2 - Device Object Properties 

Property 

Value 

Writable 

Object_Identifier 

  Programmable where the instance part of the Object_Identifier is in the range of 0-

4194302 

  The device instance must be unique system-wide 

  The default value for the device instance=153000 (Vendor_Identifier*1000) 

Object_Name 

SKH 

Description 

Programmable up to 32 characters (default: SKH). 

Object_Type 

Device 

 

System_Status 

Operational 

 

Vendor_Identifier 

Always 153 

 

Vendor_Name 

Always Neptronic 

 

Model_Name 

Example, SKH 

Read Only 

Firmware_Revision 

currently, 2.05 

Read Only 

Application_Software_Version 

currently, 2.03 

Read Only 

Protocol_Version 

Always 1 

Read Only 

Protocol_Revision 

14 

Read Only 

DataBase_Revision 

Read Only 

Max_APDU_Length_Accepted 

Always 480 

Read Only 

Segmentation_Supported 

(3) = No Segmentation 

Read Only 

APDU_Timeout 

6000 

Number_of_APDU_Retries 

Always 3 

Read Only 

Local_Time 

00:00:00 

Local_Date 

01-Jan-2015 (Thu) 

Uts_Offset 

-3:00 

W

 

Daylight_Savings_Status 

False 

W

 

Backup_Failure_Timeout 

300 

W

 

Configuration_Files 

File-1 

 

Last_Restore_Time 

2015-01-01 (Thu), 00:01:50:00 

 

Backup_And_Restore_State 

IDLE 

 

Backup_Preparation_Time 

 

Restore_Completion_Time 

 

Restore_Preparation_Time 

 

Protocol_Services_Supported 

  07470BC83AE200 

  confirmedCOVNotification 

  subscribeCOV 

  atomicReadFile 

  atomicWriteFile 

  readProperty 

  readPropertyMultiple 

  WriteProperty 

  writePropertyMultiple 

  deviceCommunicationControl 

  reinitializeDevice 

  i-Am 

  i-Have 

  unconfirmedCOVNotification 

  unconfirmedPrivateTransfer 

  timeSynchronization 

  who-Has 

  who-Is 

  subscribeCOVProperty 

 

 

Protocol_Object_Types_Supported 

  analog-input 

  analog-output 

  analog-value 

  binary-input 

  binary-output 

  binary-value 

  device 

  file 

  program 

  schedule 

  multi-state-value 

 

Object_List 

196 

Read Only 

Device_Address_Binding 

Always empty 

 

Max_Master 

Programmable in the range of 0-127 (default: 127) 

Max_Info_Frames 

Always 1 

 

Summary of Contents for SKH Series

Page 1: ...SKH BACnet Guide 200114 High Pressure Atomiser SKH Series BACnet User Guide...

Page 2: ...guration Options 3 Quick Setup 3 Manual Setup 3 MAC Address and Max_Master 3 Network Reset 4 Device Object Properties 5 Object Types Supported 6 Out of Service Property 7 Object Table Information 8 An...

Page 3: ...is performed within Tusage_delay of 15 minutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The humidifier supports a Full Master Node state machine for MS TP Max_Master and the in...

Page 4: ...ntifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decimal or hexadecimal representation tends to be incomprehensible F...

Page 5: ...nally poll for other masters based on the MAC address and Max_Master A poor combination of MAC addresses and Max_Master can lead to a slower network due to lost time polling for masters that are not p...

Page 6: ...address in the system If consecutive numbering is not possible then the next most efficient setup is one in which all units have Max_Master the maximum MAC address in the system Network Reset Reset t...

Page 7: ...taBase_Revision 2 Read Only Max_APDU_Length_Accepted Always 480 Read Only Segmentation_Supported 3 No Segmentation Read Only APDU_Timeout 6000 W Number_of_APDU_Retries Always 3 Read Only Local_Time 00...

Page 8: ...ter a programmable period of time Refer to Proprietary property 1002 of Device Object in Table 2 Device Object Properties Analog Value Reliability Description COV Increment Priority_Array Relinquish_D...

Page 9: ...1000 1001 1002 Configuration_Files Last_Restore_Time Backup_And_Restore_State Backup_Preparation_Time Restore_Completion_time Restore_Preparation_Time Refer to Table 2 Device Object Properties on pag...

Page 10: ...isplays the setpoint for the room relative humidity sensor OR Displays the setpoint for the room temperature sensor Out of Service 0 0 to 100 0 RH or 10 C to 40 C Resolution 0 1 RH or 0 01 C AI 4 Room...

Page 11: ...SimulationZoneDemand Configuration value of the demand of the simulation zones Present Value 0 to 4 Resolution 1 AV 6 SimulationPumpSelection Configuration value for the selection of the simulation p...

Page 12: ...humidity setpoint in the unoccupied mode Present Value 5 RH to 95 RH Resolution 0 1 RH AV 6 UnoccupiedTempSetpoint Configuration value of the temperature setpoint in the unoccupied mode Present Value...

Page 13: ...humidity proportional band Present Value 1 RH to 20 RH Resolution 0 1 RH AV 306 Cfg_TempProportionalBand Configuration value of the temperature proportional band Present Value 0 5 C to 50 C Resolution...

Page 14: ..._RoomTempOffset Configuration value of the temperature offset value of the room Present Value 10 C to 10 C Resolution 0 01 C AV 328 Cfg_DuctRHOffset Configuration value of the relative humidity offset...

Page 15: ...egrator BO 1 FanControl Displays the status of Fan control Read Only 0 Off 1 On Advanced BO 200 ZoneDrain Displays the status of zone drain Read Only 0 Off 1 On BO 201 ZoneInlet Displays the status of...

Page 16: ...1 On BV 218 AL_PumpOutputPressureSensorFailure Displays the status of the pump output pressure sensor failure Read Only 0 Off 1 On BV 222 AL_PumpVFDFailure Displays the status of the pump VFD failure...

Page 17: ...o long Read Only 0 Off 1 On BV 280 AL_Zone7ComTimeout Displays the status of communication timeout for the zone 7 It indicates that the communication delay is too long Read Only 0 Off 1 On BV 281 AL_Z...

Page 18: ...08 Cfg_TRLHDisplayTime Select whether to display the time on the TRL Present Value 0 Off 1 On BV 109 Cfg_TRLHTimeFormat Select the time format on the TRL Present Value 0 24H 1 12H Advanced BV 200 Simu...

Page 19: ...100 Cfg_PressureUnits Configuration value to select the pressure units Present Value 1 kPa 2 PSI 3 Bar MSV 101 Cfg_Language Select the language of the BACnet server Present Value 1 English MSV 102 Cf...

Page 20: ...tSource Configuration value to select the control setpoint source Present Value 1 AI3 2 Internal 3 Network MSV 104 Cfg_HighLimitSource Configuration value to select high limit source for analog input...

Page 21: ...le and atomicReadFile FIL 4 PumpBootloaderUpdateFile File object for pump bootloader upgrade File_Size Archive Stream access method via atomicWriteFile and atomicReadFile PGM 1 FirmwareUpdateTask Firm...

Page 22: ...Notes...

Page 23: ......

Page 24: ...u blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm East...