Configuration Options 

The following options enable you to configure and run the BACnet features of the humidifiers quickly. 

Quick Setup 

Configure the humidifier's baud rate and device instance without programming.    

1. 

Connect the humidifier to the network and power it up.  

2. 

The humidifier automatically configures the baud rate and device instance.  

3. 

Repeat the steps for each humidifier.  

Manual Setup 

1. 

To use a 

Device_Instance

 other than 153,000, and/or if your site has more than one humidifier network, 

go to the menu.  

2. 

Disconnect the power to the humidifier, connect the humidifier to the network, and connect the power 
again.  

3. 

Configure the 

Max_Master

 value through 

WriteProperty

 service to the 

Device Object.Max_Master

 to 

increase network efficiency or if there are less than 127 devices on the network.  

MAC Address and Max_Master    

The MAC address must be unique on the entire MS/TP network. However, having a unique MAC address and a high 
baud rate does not guarantee efficient operation of the humidifier and other MS/TP units on the MS/TP network. Some 
MAC  address and Max_Master combinations are more efficient than  others. BACnet requires token-passing units to 
occasionally “poll” for other masters based on the MAC address and Max_Master. 
A poor combination of MAC addresses and Max_Master can lead to a slower network due to lost time polling for masters 
that are not present. Unless there are 126 other units on the MS/TP network, the default Max_Master value of 127 is 
not the most efficient choice for the humidifier. The Max_Master default value of 127 was selected to ensure that any 
master, specifically a BACnet client can be found when the humidifier is initially started. 

Examples of Mac Address and Max_Master Configurations 

The  following  are  some  of  the  examples  to  indicate  the  optimum  combination  of  Mac  address  and  Max_Master 
configurations to ensure a quick and efficient output.  

Example 1 

 

MAC=0. Max_Master=127 

 

MAC=1, Max_Master=127 

This configuration is slow and inefficient because every time either unit is required to find another master unit, it has to 
poll 126 units until it finds the right one to pass the token. 

Example 2 

 

MAC=0. Max_Master=5 

 

MAC=1 to MAC=4 are not used 

 

MAC=5, Max_Master=5 

This configuration is better than Example 1 but it is still slower. The Max_Master is set to the most efficient value but 
the gap between the two MAC addresses is high. Therefore, each unit must poll four units until it finds the right one to 
pass the token. 

Example 3 

 

MAC=0. Max_Master=1 

 

MAC=2, Max_Master=2 

This  is  an  incorrect  configuration.  The  MAC=0  will  never  find  MAC=2  because  it  will  never  poll  for  the  master  MAC 
address=2. 

Summary of Contents for SKH Series

Page 1: ...SKH BACnet Guide 200114 High Pressure Atomiser SKH Series BACnet User Guide...

Page 2: ...guration Options 3 Quick Setup 3 Manual Setup 3 MAC Address and Max_Master 3 Network Reset 4 Device Object Properties 5 Object Types Supported 6 Out of Service Property 7 Object Table Information 8 An...

Page 3: ...is performed within Tusage_delay of 15 minutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The humidifier supports a Full Master Node state machine for MS TP Max_Master and the in...

Page 4: ...ntifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its decimal or hexadecimal representation tends to be incomprehensible F...

Page 5: ...nally poll for other masters based on the MAC address and Max_Master A poor combination of MAC addresses and Max_Master can lead to a slower network due to lost time polling for masters that are not p...

Page 6: ...address in the system If consecutive numbering is not possible then the next most efficient setup is one in which all units have Max_Master the maximum MAC address in the system Network Reset Reset t...

Page 7: ...taBase_Revision 2 Read Only Max_APDU_Length_Accepted Always 480 Read Only Segmentation_Supported 3 No Segmentation Read Only APDU_Timeout 6000 W Number_of_APDU_Retries Always 3 Read Only Local_Time 00...

Page 8: ...ter a programmable period of time Refer to Proprietary property 1002 of Device Object in Table 2 Device Object Properties Analog Value Reliability Description COV Increment Priority_Array Relinquish_D...

Page 9: ...1000 1001 1002 Configuration_Files Last_Restore_Time Backup_And_Restore_State Backup_Preparation_Time Restore_Completion_time Restore_Preparation_Time Refer to Table 2 Device Object Properties on pag...

Page 10: ...isplays the setpoint for the room relative humidity sensor OR Displays the setpoint for the room temperature sensor Out of Service 0 0 to 100 0 RH or 10 C to 40 C Resolution 0 1 RH or 0 01 C AI 4 Room...

Page 11: ...SimulationZoneDemand Configuration value of the demand of the simulation zones Present Value 0 to 4 Resolution 1 AV 6 SimulationPumpSelection Configuration value for the selection of the simulation p...

Page 12: ...humidity setpoint in the unoccupied mode Present Value 5 RH to 95 RH Resolution 0 1 RH AV 6 UnoccupiedTempSetpoint Configuration value of the temperature setpoint in the unoccupied mode Present Value...

Page 13: ...humidity proportional band Present Value 1 RH to 20 RH Resolution 0 1 RH AV 306 Cfg_TempProportionalBand Configuration value of the temperature proportional band Present Value 0 5 C to 50 C Resolution...

Page 14: ..._RoomTempOffset Configuration value of the temperature offset value of the room Present Value 10 C to 10 C Resolution 0 01 C AV 328 Cfg_DuctRHOffset Configuration value of the relative humidity offset...

Page 15: ...egrator BO 1 FanControl Displays the status of Fan control Read Only 0 Off 1 On Advanced BO 200 ZoneDrain Displays the status of zone drain Read Only 0 Off 1 On BO 201 ZoneInlet Displays the status of...

Page 16: ...1 On BV 218 AL_PumpOutputPressureSensorFailure Displays the status of the pump output pressure sensor failure Read Only 0 Off 1 On BV 222 AL_PumpVFDFailure Displays the status of the pump VFD failure...

Page 17: ...o long Read Only 0 Off 1 On BV 280 AL_Zone7ComTimeout Displays the status of communication timeout for the zone 7 It indicates that the communication delay is too long Read Only 0 Off 1 On BV 281 AL_Z...

Page 18: ...08 Cfg_TRLHDisplayTime Select whether to display the time on the TRL Present Value 0 Off 1 On BV 109 Cfg_TRLHTimeFormat Select the time format on the TRL Present Value 0 24H 1 12H Advanced BV 200 Simu...

Page 19: ...100 Cfg_PressureUnits Configuration value to select the pressure units Present Value 1 kPa 2 PSI 3 Bar MSV 101 Cfg_Language Select the language of the BACnet server Present Value 1 English MSV 102 Cf...

Page 20: ...tSource Configuration value to select the control setpoint source Present Value 1 AI3 2 Internal 3 Network MSV 104 Cfg_HighLimitSource Configuration value to select high limit source for analog input...

Page 21: ...le and atomicReadFile FIL 4 PumpBootloaderUpdateFile File object for pump bootloader upgrade File_Size Archive Stream access method via atomicWriteFile and atomicReadFile PGM 1 FirmwareUpdateTask Firm...

Page 22: ...Notes...

Page 23: ......

Page 24: ...u blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm East...

Reviews: