High Pressure Atomiser Series
BACnet Communication Module User Guide
www.neptronic.com
Page | 17
Multi State Value (MSV)
Table 10 - Object Table Information: Multi State Value (MSV)
ID
Name
Description
W?
Notes
Integrator
MSV.1
PumpState
Displays the status of pump.
Read Only
1 = Stand-by
2 = Start Pump
3 = Pressurizing
4 = Ready
5 = Cooling
6 = Manual Prime
7 = System Drain
8 = Inactivity Drain
9 = Alarm
10 = Closing
Integrator
– Configuration
MSV.100
Cfg_PressureUnits
Configuration value to select the pressure units.
Present Value
1 = kPa
2 = PSI
3 = Bar
MSV.101
Cfg_Language
Select the language of the BACnet server.
Present Value
1 = English
MSV.102
Cfg_ObjectListMode
Configuration value to select the category of BACnet objects to
display.
Present Value
1 = Integrator
2 = Advanced
3 = Factory
SKH EZC
ID
Name
Description
W?
Notes
Integrator
MSV.1
ZoneState
Displays the status of zone.
Read Only
1 = POR
2 = Alarm
3 = Stand-By
4 = Drain Stages
5 = Drain Lines
6 = Ready
MSV.2
Occupancy
Configuration value of the current occupancy state.
Present Value
1 = Occupied
2 = Unoccupied
3 = Vacant
4 = Off