
Page 11
-↑ +↓
P401
Exit 4
Work time (10 - 240) s F[60]
-↑ +↓
P402
Exit 4
Reset time (0 - 60)min F[0]
If F[0] the function is not on.
-↑ +↓
P403
Exit 4
Wind sensor function (0 - 2) F[0]. Set the action when active as
follows:
0=none
1=open
2=close
-↑ +↓
P404
Exit 4
Rain sensor function (1 - 2) F[2]. Set the action when the input is
active, as follows:
0=none
1=open
2=close
-↑ +↓
P405
Exit 4
Timer function F[0]. Set the action when active as follows:
0=none
1=open
2=close
-↑ +↓
P406
Exit 4
Aeration time (1-60)min F[10].
-↑ +↓
P407
Exit 4
Single manual command functioning mode:
0=half-automatic mode
1=dead-man mode, sensors and remote controls enabled
2= dead-man mode, sensors and remote controls disabled
-↑ +↓
P501
Exit 5
Work time (10 - 240) s F[60]
-↑ +↓
P502
Exit 5
Reset time (0 - 60)min F[0]
If F[0] the function is not on.
-↑ +↓
P503
Exit 5
Wind sensor function (0 - 2) F[0]. Set the action when active as
follows:
0=none
1=open
2=close
Page 12
-↑ +↓
P504
Exit 5
Rain sensor function (1 - 2) F[2]. Set the action when the input is
active, as follows:
0=none
1=open
2=close
-↑ +↓
P505
Exit 5
Timer function F[0]. Set the action when active as follows:
0=none
1=open
2=close
-↑ +↓
P506
Exit 5
Aeration time (1-60)min F[10].
-↑ +↓
P507
Exit 5
Single manual command functioning mode:
0=half-automatic mode
1=dead-man mode, sensors and remote controls enabled
2= dead-man mode, sensors and remote controls disabled
-↑ +↓
P601
Exit 6
Work time (10 - 240) s F[60]
-↑ +↓
P602
Exit 6
Reset time (0 - 60)min F[0]
If F[0] the function is not on.
-↑ +↓
P603
Exit 6
Wind sensor function (0 - 2) F[0]. Set the action when active as
follows:
0=none
1=open
2=close
-↑ +↓
P604
Exit 6
Rain sensor function (1 - 2) F[2]. Set the action when the input is
active, as follows:
0=none
1=open
2=close
-↑ +↓
P605
Exit 6
Timer function F[0]. Set the action when active as follows:
0=none
1=open
2=close
-↑ +↓
P606
Exit 6
Aeration time (1-60)min F[10].