When  the  window  is  closed,  check that  the chain  terminal  protrudes  completely from the 
actuator body by at least a couple millimetres; this ensures that the window is closed well 
and the seal is compressed properly, otherwise the window may not be completely closed 
arising the risk of possible leakages.  
Check also that the attachments and support brackets are solidly joined to the window and 
the screws are tightened properly. 
The  use  of  self-threading  or  self-drilling  screws  on  aluminium  windows  is  not 
recommended  at  all,  since  they  can  tear  the  profile  after  a  few  manoeuvres;  use  metric 
screws with threaded inserts instead 

(see instructions in paragraph 9.3)

10.4. 

LED Light signals 

If  there  are  any  problems  during  installation  or  operation  of  the  machines,  please  take  a 
look to the possible causes listed below: 

WITH RED LED 

No. of 

Flashes 

Type of Error 

Possible Solution 

Current error: 

The actuator has detected an 

overcurrent in the motor. 

Check that there are no obstacles preventing 
the actuator from completing its stroke. Check 
that the actuator is installed correctly. 

Communication error: 

Communication between the 

devices is interrupted, or the 

devices being used have 

undergone the RESET procedure 

separately. 

Check the condition of the connection cables, 
and repeat the RESET procedure if necessary. 

Electro-lock error 

Check the electro-lock. 

Contrasting Dip-switch settings: 

The devices connected to one 

another have conflicting Dip-switch 

settings. 

Check the settings of the various Dip-switches. 

RESET Procedure error: 

The RESET procedure was not 

completed successfully or was 

interrupted. 

Repeat the RESET procedure. 

Wiring error: 

The power supply cables of the 

devices configured in Syncro³ 

modus are inverted. 

Check and correct the wiring. 

Encoder error: 

The internal encoder had a 

counting error. 

Repeat the RESET procedure. 

Electric power supply error: 

The power supply voltage is 

outside the permitted range or is 

unstable. 

Check the electrical contacts at the ends of the 
actuator cable and ensure that the power 
supply is correct. 

Chain alignment error: 

The misalignment of the chain 

Repeat the RESET procedure. 

14 

terminal positions on devices 

connected in a Syncro 

configuration exceeds the 

maximum amount allowed. 

10 

Memory error: 

The internal memory write process 

failed. 

Repeat the RESET procedure. 

11 

Connection error: 

A RESET procedure is being 

started with actuators different than 

Syncro³, K-LOCK or AUX 

Check the type of actuators chosen for the 
system. Repeat the RESET procedure. 

 

WITH GREEN LED 

LED Status 

Meaning 

STEADY-ON 

Device powered correctly. 
The device has correctly performed a chain re- entry stroke, completing 
the operation by writing the memory; or it is still in motion. 

FLASHING 

Device  powered  correctly.  The  device  executed  an  outgoing  stroke  of 
the  chain  correctly.  The  number  of  flashes  indicates  the  number 
previously assigned to the device during the RESET procedure. 

 

WITH ORANGE LED 

LED Status 

Meaning 

STEADY-ON 

Duration < 0.5 sec. 

Internal memory write process in progress. 

STEADY-ON 

RESET Procedure in progress. 

STEADY-ON for 3 

sec. 

Overlap acquisition procedure finished correctly. 

FLASHING 

RESET Procedure finished correctly. The number of flashes indicates 
the  number  assigned  to  the  device  in  a  configuration  with  several 
devices. 

11.  Checking for correct assembly 

  Check  if  the  window  is  perfectly  closed  at  corners  and  that  there  are  no  obstacles 

caused by incorrect positioning during assembly. 

  Check  when  the  window  frame  is  closed  if  the  chain  terminal  is  at  least  a  few 

millimetres away from the actuator body. This will ensure the window is properly closed 
and seals are correctly compressed. In the event that this should not be the case there 
is no guarantee that the window is closed correctly. 

  Check  if  hinges  and  support  brackets  are  aligned  to  each  other,  tightened  to  the 

window frame and screws correctly fixed. 

  Check if the window reaches the desired position according to the stroke-end selected. 

  In the presence of an electro-lock, check if at the end of the actuator closing stroke, the 

K-LOCK activates and it’s closing time is about 4 seconds. 

Summary of Contents for KIMO 202

Page 1: ...uthorised by the manufacturer Do not use if repair or adjustment is required CAUTION if the power cable is damaged it must be replaced by qualified personnel from a service centre authorised by the manufacturer CAUTION Disconnect the power supply during cleaning or maintenance operations Do not use solvents or jets of water to wash the appliance the appliance should not be submerged in water In th...

Page 2: ...arranty for the appliance In the event of any problems or queries consult your agent or contact the manufacturer directly 4 AREFULLY OBSERVE ALL THE FOLLOWING INSTALLATION INSTRUCTIONS MPROPER INSTALLATION CAN SERIOUSLY ENDANG MANDATORY RISK ANALYSIS AND PROTECTION MEASURES The Nekos electrical actuators comply with the Machinery Directive 2006 42 EC Standard 103 Particular requirements for drives...

Page 3: ... of the window mobile sash only H cm Height of the mobile sash For vertical windows OUTWARD OPENING A BOTTOM HUNG WINDOWS B F 0 54 x P x C H Possible load exerted by snow or wind on the dormer should be calculated separately 3 2 Maximum opening based The selection of the actuator stroke should be made based on the height of the sash and its application As a general rule never select a stroke great...

Page 4: ... the second conductor BLACK that should be connected to the positive OPENS the window the third conductor GREEN is the conductor used for Syncro communication K LOCK control communication signal and AUX The 24V low voltage actuators can be powered using a unit with emergency batteries or a security power supply unit at least in Class 2 with an output voltage of 24V min 20 4V max 28 8V that is to s...

Page 5: ...ctuator should not be installed Check that once the actuator has been installed chain completely in the window If this is not the case the actuator will not function correctly as 9 1 Preparation for mounting the actuator In case of doubts uncertainties or different applications always contact manufacturer For a proper Before beginning to mount the actuator depending on the type of application the ...

Page 6: ...cedure should be carried out with the chain terminal or terminals for configurations with several devices uncoupled from the window sash bracket IMPORTANT The dip switch settings should be changed to non powered actuators after each change it is necessary to wait a few seconds 5 sec before restoring the power to the actuators in order for the change to become effective Set the dip switches in the ...

Page 7: ...eck the electrical contacts at the ends of the actuator cable and ensure that the power supply is correct 9 Chain alignment error The misalignment of the chain Repeat the RESET procedure 14 terminal positions on devices connected in a Syncro configuration exceeds the maximum amount allowed 10 Memory error The internal memory write process failed Repeat the RESET procedure 11 Connection error A RES...

Page 8: ...rtake to replace defective parts due to poor quality materials or manufacturing defects in accordance with article 1490 of the Civil Code The guarantee covers products and from the date of purchase The latter is valid as long as the purchaser possesses proof of purchase and completion of all agreed conditions of Guarantee of good function of appliances agreed by the manufacturer implies that the l...

Reviews: