background image

 

11 

10.  Programming the actuator 

10.1. 

KIMO 202 programming 

Closing stroke-end 

The  closing  stroke-end  is  automatic  and  non-settable.  The  position  at  which  the  actuator 
stops  is  determined  by  the  power  absorbed  by  the  actuator  when  the  window  reaches 
complete closure and the seals are completely compressed, i.e., the actuator stops when 
the power absorbed exceeds a preset threshold.  
After  each  closure  or  intervention  of  the  electronic  protection,  the  chain  moves  in  the 
opposite direction for about 1 mm, in order to produce the right compression on the seals 
and  relax  the  internal  mechanical  parts.  During  operation,  the  KIMO202  actuators 
automatically recognize and memorize the distance between window sash and frame when 
the window is completely closed. The difference in the position of the protruding part of the 
window sash with respect to the frame is defined as the “overlap” and allows the actuator 
to acquire its own operating parameters, storing the position and type of window frame. 
This procedure, known as “

OVERLAP ACQUISITION

” (paragraph 10.3), occurs the first time the 

actuator closes the window completely following a RESET operation and remains stored as 
an operating parameter. 

Opening stroke-end 

The  KIMO202  actuator  is  supplied  with  the  RESET  procedure  already  executed  and  a 
preset  maximum stroke. The  overlap still needs to  be "acquired"  (paragraph  10.3),  and  a 
smaller stroke selected if necessary.  

IMPORTANT. If connecting an electro-lock K-LOCK a new RESET procedure must be 
carried out. 
When  using  the  KIMO202  Syncro³  model,  the  RESET  procedure  and  acquisition  of 
the  overlap  must  be  performed  during  installation  (see  paragraphs  10.2  and  10.3) 
before the desired opening stroke-end can be selected.  

We recommend checking the electrical wiring before starting the RESET procedure. If the 
settings  are  lost,  a  new  RESET  procedure  must  be  performed  followed  by  acquisition  of 
the overlap (see paragraphs 10.2 and 10.3). 

Three

  positions  can  be  selected  for  the  stroke-end  positions  of  the  outgoing  chain  by 

setting dip switches no. 

1

 and 

(see table below). Programming is quick and simple and 

can be done at any time. 

STROKE  

(mm) 

DIP-SWITCH 

 

100 

ON 

OFF 

170 

OFF 

ON 

250 

ON 

ON 

The actuator is factory-set with the longest stroke (250 mm). 
 
 

12 

10.2. 

RESET Procedure 

This  procedure  concerns  the  configuration  of  a  single  actuator,  Syncro³  setting  of  or  in 
presence of a K-LOCK electromechanical lock. 
This  procedure  should  be  carried  out  with  the  chain  terminal  (or  terminals,  for 
configurations with several devices) uncoupled from the window sash bracket. 

IMPORTANT:  The  dip-switch  settings  should  be  changed  to  non-powered 
actuators; after each change it is necessary to wait a few seconds (~ 5 sec) before 
restoring the power to the actuators in order for the change to become effective. 

­

  Set  the  dip-switches  in  the  following  manner: 

DIP  1  OFF

  – 

DIP  2  OFF

.  For 

configurations with several devices (or with the K-LOCK electro-lock), the setting of 
the dip-switches as described above should only be changed for one actuator, and 
the other devices will link to it automatically. 

­

  Supply  power  to  the actuators  (either  by  opening  or closing). The  initializing  phase 

will then start. 

­

  The  actuator  will  start  at  once  (or  after  about  8 seconds  if  there  is  an  electro-lock) 

and  perform  a  full  closing  manoeuvre  (chain  completely  retracted)  and  then  an 
opening  manoeuvre  of  about  5  cm.  During  this  phase,  ensure  that  there  are  no 
obstacles  to  the  movement  of  the  chain  and  wait  until  the  closing  manoeuvre  is 
completed on all actuators. 

­

  When  the  operation  is  finished,  each  connected  device  gives  a  flashing  orange 

signal  to  indicate  completion  of  the  RESET  procedure.  Each  device  will  give  a 
different number of flashes to indicate that the access code is received (actuator 1 → 
1 flash → pause → 1 flash → pause; actuator 2 → 2 flashes → pause → 2 flashes 
→ pause, etc.). 

­

  The power supply to the devices can now be switched off and the dip-switches used 

to set the desired stroke on all the actuators. 

­

  Couple the chain terminal to the movable sash bracket. 

Once  the  RESET  procedure  is  executed,  at  the  next  complete  closure  the  actuator  will 
repeat the overlap acquisition operation. If the K-LOCK electro-lock is present, refer to the 
respective user and installation manual. 

10.3. 

Overlap acquisition 

The operation that must be carried out to acquire the overlap (after the RESET procedure 
has already been executed) is described below: 

  Assembly of the actuator(s) on the window (as per chapter 9). 

  Electrical connection of the actuator (as per chapter 8). 

  Coupling of the chain terminal(s) to the sash bracket. 

  Activating the window closing command. 

  Wait until the window is completely closed. An orange light will flash on the actuator 

for 3 seconds to indicate that the overlap has been successfully acquired. 

IMPORTANT:  If,  for  any  reason,  the  actuator  fails  to  complete  the  closure  of  the 
window  correctly,  stopping  before  finishing  the  stroke,  the  RESET  and  overlap 
acquisition operation will have to be repeated in that order, until the procedure is 
completed correctly. 

Summary of Contents for KIMO 202

Page 1: ...uthorised by the manufacturer Do not use if repair or adjustment is required CAUTION if the power cable is damaged it must be replaced by qualified personnel from a service centre authorised by the manufacturer CAUTION Disconnect the power supply during cleaning or maintenance operations Do not use solvents or jets of water to wash the appliance the appliance should not be submerged in water In th...

Page 2: ...arranty for the appliance In the event of any problems or queries consult your agent or contact the manufacturer directly 4 AREFULLY OBSERVE ALL THE FOLLOWING INSTALLATION INSTRUCTIONS MPROPER INSTALLATION CAN SERIOUSLY ENDANG MANDATORY RISK ANALYSIS AND PROTECTION MEASURES The Nekos electrical actuators comply with the Machinery Directive 2006 42 EC Standard 103 Particular requirements for drives...

Page 3: ... of the window mobile sash only H cm Height of the mobile sash For vertical windows OUTWARD OPENING A BOTTOM HUNG WINDOWS B F 0 54 x P x C H Possible load exerted by snow or wind on the dormer should be calculated separately 3 2 Maximum opening based The selection of the actuator stroke should be made based on the height of the sash and its application As a general rule never select a stroke great...

Page 4: ... the second conductor BLACK that should be connected to the positive OPENS the window the third conductor GREEN is the conductor used for Syncro communication K LOCK control communication signal and AUX The 24V low voltage actuators can be powered using a unit with emergency batteries or a security power supply unit at least in Class 2 with an output voltage of 24V min 20 4V max 28 8V that is to s...

Page 5: ...ctuator should not be installed Check that once the actuator has been installed chain completely in the window If this is not the case the actuator will not function correctly as 9 1 Preparation for mounting the actuator In case of doubts uncertainties or different applications always contact manufacturer For a proper Before beginning to mount the actuator depending on the type of application the ...

Page 6: ...cedure should be carried out with the chain terminal or terminals for configurations with several devices uncoupled from the window sash bracket IMPORTANT The dip switch settings should be changed to non powered actuators after each change it is necessary to wait a few seconds 5 sec before restoring the power to the actuators in order for the change to become effective Set the dip switches in the ...

Page 7: ...eck the electrical contacts at the ends of the actuator cable and ensure that the power supply is correct 9 Chain alignment error The misalignment of the chain Repeat the RESET procedure 14 terminal positions on devices connected in a Syncro configuration exceeds the maximum amount allowed 10 Memory error The internal memory write process failed Repeat the RESET procedure 11 Connection error A RES...

Page 8: ...rtake to replace defective parts due to poor quality materials or manufacturing defects in accordance with article 1490 of the Civil Code The guarantee covers products and from the date of purchase The latter is valid as long as the purchaser possesses proof of purchase and completion of all agreed conditions of Guarantee of good function of appliances agreed by the manufacturer implies that the l...

Reviews: