FlexPAK
4.2.47 AUX Setting
In the menu “AUX Setting”, set parameter values related to AUX temperature input.
ESC
OK
AUX Se!ng 1/2
MaxS
=50
MaxR
=50
MinR
=0
MinS
=0
Larm
=Off
MaxS = Default 50°C
MaxR = Default 50°C
MinR = 0°C
MinS = 0°C
ESC
OK
AUX Se!ng 2/2
Stat
=Off
Tdly
=10:00s
Larm = Default Off
Stat = Default Off
Tdly = Default 10:00 s
MaxS = Set Temperature Threshold
Maximum accepted Temperature. If the temperature passes above MaxS, the Max temperature alarm activates.
When the Temperature Alarm Delay Timer is elapsed = TDly, the unit stops.
MaxR = Reset Temperature Threshold
If the temperature alarm is activated and Temperature Alarm Delay Timer not elapsed = TDly > 0 and the tem-
perature is lower than MaxR, the alarm is reset and FlexPAK is not stopped. Always set MaxR = MaxS!
MinS = Set Temperature Threshold
Minimum accepted Temperature. If temperature passes below MinS, the FlexPAK unit Min temperature alarm
activates. When the Temperature Alarm Delay Timer is elapsed = TDly, the unit stops.
MinR = Reset Temperature Threshold
If the temperature alarm is activated and Temperature Alarm Delay Timer is not elapsed = TDly > 0 and the tem-
perature is higher than MinR, the alarm is reset and FlexPAK is not stopped. Always set MinR = MinS!
Larm = Larm Activation
If Stat = off, AUX Sensor Activation. The Warning and Alarm functions are disabled.
If parameter Larm =off, only Warning messages are displayed when the Aux temperature passes any of the
Temperature Thresholds. Alarm/Stop functionality is disabled. If parameter Larm =on, Warnings and Alarm mes-
sages are displayed. Fan off function is enabled when the Aux temperature passes any of the Temperature
Thresholds. Attention! The Alarm message and Fan stop function are time delayed. Alarm time delay is set in
parameter TDly.
Stat = AUX Sensor Activation
Set parameter Stat = On, Temperature sensor installed
Set parameter Stat = Off, Temperature sensor not installed
TDly = Alarm Time Delay
This parameter sets Alarm Time Delay in seconds
The default is 10:00 seconds.