3.1.17 Temperature Sensor Display
The temperature Sensor Reading display is manually activated.
• Toggle with arrow key “UP” or “Down” until Date Window is visible.
• Toggle with arrow key “Left” or “Right” until Arrow Window is visible.
Press the “ESC” button simultaneously while pressing the arrow key “Left” to view Temperature sensor data.
ESC
OK
Temp Sens Input
Exhaust 40 C
Max 135 C
Aux Temp 28 C
Max 50 c
Min
0
c
ESC
If Sensor is not installed and sensor input is open, sensor reading is -50°C
Press the “OK” button to close the display.
Exhaust
40C
→
Fan Exhaust Air Temperature
Max
135C
→
Fan Exhaust Max Air Temperature Limit setting (Default 135 C)
Aux Temp
28 C
→
AUX Sensor Temperature
Maxd
50C
→
AUX Temperature Max Temperature Limit setting (Default 50 C)
Min
0 C
→
AUX Temperature Min Temperature Limit setting (Default 0 C)
See “AUX Setting” for more information
3.1.18 Vibration Sensor Display
The Vibration Sensor Reading display is manually activated.
• Toggle with arrow key “UP” or “Down” until Date Window is visible.
• Toggle with arrow key “Left” or “Right” until Arrow Window is visible.
Press the “ESC” button simultaneously while pressing the arrow key “Down” to view Vibration Sensor data (ac-
tually it is an Alarm display that is opened and viewed without Alarm is activated).
ESC
OK
V i b r a t i o n Limit
Exceeded
Level 3,8 mm/s
Delay Tmr 09:00 s
MaxS 10,0 mm/s
MaxR 10,0 mm/s
If Sensor is not installed and sensor input is open, sensor reading is approx-
imate -6.24mm/s
Press the “OK” button to close the display.
Level
3.8 mm/s
→
Actual Vibration value
Delay Tmr
09:00 s
→
Reaming time to unit stop, Stop delay timer
MaxS
10.0 mm/s
→
Max SET Vibration limit setting
MaxR
10.0 mm/s
→
Max RESET Vibration limit setting