8

INSTALLATION INSTRUCTIONS 

(continued)

• An AGA approved 150mm diameter Gas Cowl must be fitted.
• The flue or chimney of an open gas fire must be kept clear at all times. Devices which close or

temporally close the flue or chimney are not permitted. (e.g. a damper must be removed or

securely disabled in the fully open position.)

• If these conditions are met the chimney should usually provide satisfactory draw. In any event,

the chimney and final installation must be tested for spillage into the room. This can be done by

lighting a paper fire in the fireplace (before the appliance is installed) and holding a smoking

twist of paper or a smoking match by the front of the fireplace. Air conditioning vents near the

fireplace may also cause spillage.

• The fireplace must be at least 470mm wide (front), 325mm wide (rear) x 250mm Deep x

400mm high to suit the Type 1 burner.

• The room must have total fixed ventilation equal to the chimney / flue area.
• Refer also to “Wonderfire FFB Convector Box” instructions if fitting a Convector Box.

Fitting the unit

• The unit should be fixed to the base of the fireplace with a screw to each front corner of the

burner.

Gas

• Gas connection is to a ½” BSP male fitting connected to the RHS of the valve. It is located

100mm from front, 45mm up from floor and 170mm in from front RH corner of the appliance

• Thoroughly blow out the supply pipe to clear any dust and debris.
• Ensure all connections are gas tight.
• Note: Do not bring the gas supply down the active chimney.

Coals

The WONDERFIRE has ceramic coals and a burner designed to appear like a coal fire.
• The unit is supplied with the ceramics assembled ready for operation.
• When the unit is unpacked check that no damage has occurred in transport.
• Carefully place the ceramic coal assembly on top of the burner making sure that it sits in place

correctly.

• No other coals should be added as this will adversely affect the performance of the fire.
• Wash hands after handling the ceramic base or coal assembly.

Commissioning

• Once the fire is fitted and connected to the gas, test the unit’s operation.
• After 10 minutes operation from cold, test for fireplace spillage, i.e. all products of combustion

are entering the flue, by traversing the perimeter of the opening or canopy, using a smoke

generator (E.g. a smoking twist of paper or smoke match).

Summary of Contents for WONDERFIRE AF18

Page 1: ...tified as a Space Heater WONDERFIRE AF18 OF MANUAL VALVE INSTALLATION OPERATING MANUAL Nectre Wonderfire fire boxes are approved to be installed as a zero clearance firebox and are designed to operate...

Page 2: ...tructions or b it has been installed in an outdoor setting 4 Limit of Liability The warranty provided under this warranty is limited to replacement or repair of the Gas Burner only at our option To th...

Page 3: ...THE APPLIANCE OR DRAUGHT OF CHIMNEY OR FLUE DO NOT MODIFY THIS APPLIANCE THIS APPLIANCE IS DESIGNED TO OPERATE WITH LUMINOUS FLAMES THIS MAY EXHIBIT SLIGHT CARBON DEPOSITS Permanent ventilation of th...

Page 4: ...4 CONTENTS Contents 4 Data Plate 5 Dimensions 5 User Instructions 6 Installation Instructions 7 Servicing Details 9 Fault Finding Chart 10 Glen Dimplex contact information 12...

Page 5: ...the unit for reference to gas pressure consumption 5 AF18 OF Manual valve Eurosit 630 Gas Injector Size mm TPP N G C Mj Hr Natural Gas 1 x injector multiport 7 ports x 1 25 0 5kPa high 0 35kpa Low 35...

Page 6: ...not stay alight contact the supplier Once the pilot is alight you may turn the gas control knob to the high setting 7 The fire will ignite from the pilot If required you may now turn the gas control...

Page 7: ...erall dimensions of the fire is 465mm wide front 325mm wide rear x 240mm Deep x 320mm high See below for minimum fire place dimensions The appliance may be installed in an existing open fireplace as a...

Page 8: ...d be fixed to the base of the fireplace with a screw to each front corner of the burner Gas Gas connection is to a BSP male fitting connected to the RHS of the valve It is located 100mm from front 45m...

Page 9: ...he burner and place upside down on a flat surface covered with old newspaper BURNER To access the burner remove the coals The burner is glued in to the burner tray Examine it for any damage and check...

Page 10: ...et blocked Gas pressure too low Tighten at rear of valve Replace Oxypilot Blow clean out Pilot runs off mains pressure which must be at least 1 135 Kpa Gas will not ignite After turning off Time safet...

Page 11: ...11...

Page 12: ...GLEN DIMPLEX AUSTRALIA PTY LTD ABN 69 118 275 460 Head Office Factory Showroom 1340 Ferntree Gully Rd Scoresby Vic 3179 Ph 1300 554 155 Fax 03 8706 2001...

Reviews: