INSTALLATION INSTRUCTIONS

Location

Installation must meet Australian gas codes AS/NZS 5601.
INSTALLATION CLEARANCES (where FFB is used)– Clearances from combustible materials
Floor

0mm

Sides

80mm

Top / gather

50mm

Flue outer

25mm

Back

25mm

PRELIMINARY

• This appliance must be installed by an Authorised person.
• This appliance must be installed in accordance with the Gas Installation Code AS5601 Clauses

5.12.13.2 to 5.12.13.5.

• Installation must be in accordance with municipal Building codes, any other relevant statutory

regulations as well as these instructions

• The Wonderfire Gas Fire is only to be used with Natural Gas.
• It is recommended that a secondary guard complying with AS 2286 be installed.
• Ensure that loose fabrics such as curtains and furniture cannot touch the appliance. It is

recommended that a fire guard be used with the appliance.

• The guard is fitted to this appliance to reduce the risk of fire or injury from burns and no part of

it should be permanently removed. For protection of young children or the infirm, a secondary

guard is required.

• The overall dimensions of the fire is 465mm wide (front), 325mm wide (rear) x 240mm Deep x

320mm high. (See below for minimum fire place dimensions).

• The appliance may be installed in an existing open fireplace (as a Type 1 appliance), in an

existing fireplace with the Wonderfire FFB fan assisted convector box (as a Type 1 appliance)

or in a purpose built enclosure with the Wonderfire FFB fan assisted convector (zero clearance)

box (as Type 2 appliance).

• If fitting the Wonderfire with the FFB firebox, please also refer to the Instructions for the

“Wonderfire FFB”

• There must be a minimum of 50mm gap between the gather and any combustible materials if

FFB firebox is used.

• Packaging and transit protection must be removed from the appliance prior to installation.  This

includes pallet, plastic wrap, temporary labels and foam protection

FITTING TO AN EXISTING OPEN FIREPLACE

Before installing in an existing open fireplace:

• The Wonderfire (type 1) must be installed in a fire resistive fire place with a proved draught.
• The chimney must be swept and inspected to see that it is in sound condition.
• The chimney must be a minimum size of 150x150mm if masonry or 150mm diameter if round

metal flue).

• NOTE – WHERE THE APPLIANCE IS INSTALLED INTO A MASONARY FIREPLACE A

FABRICATED FLUE MUST BE USED.

Summary of Contents for WONDERFIRE AF18

Page 1: ...tified as a Space Heater WONDERFIRE AF18 OF MANUAL VALVE INSTALLATION OPERATING MANUAL Nectre Wonderfire fire boxes are approved to be installed as a zero clearance firebox and are designed to operate...

Page 2: ...tructions or b it has been installed in an outdoor setting 4 Limit of Liability The warranty provided under this warranty is limited to replacement or repair of the Gas Burner only at our option To th...

Page 3: ...THE APPLIANCE OR DRAUGHT OF CHIMNEY OR FLUE DO NOT MODIFY THIS APPLIANCE THIS APPLIANCE IS DESIGNED TO OPERATE WITH LUMINOUS FLAMES THIS MAY EXHIBIT SLIGHT CARBON DEPOSITS Permanent ventilation of th...

Page 4: ...4 CONTENTS Contents 4 Data Plate 5 Dimensions 5 User Instructions 6 Installation Instructions 7 Servicing Details 9 Fault Finding Chart 10 Glen Dimplex contact information 12...

Page 5: ...the unit for reference to gas pressure consumption 5 AF18 OF Manual valve Eurosit 630 Gas Injector Size mm TPP N G C Mj Hr Natural Gas 1 x injector multiport 7 ports x 1 25 0 5kPa high 0 35kpa Low 35...

Page 6: ...not stay alight contact the supplier Once the pilot is alight you may turn the gas control knob to the high setting 7 The fire will ignite from the pilot If required you may now turn the gas control...

Page 7: ...erall dimensions of the fire is 465mm wide front 325mm wide rear x 240mm Deep x 320mm high See below for minimum fire place dimensions The appliance may be installed in an existing open fireplace as a...

Page 8: ...d be fixed to the base of the fireplace with a screw to each front corner of the burner Gas Gas connection is to a BSP male fitting connected to the RHS of the valve It is located 100mm from front 45m...

Page 9: ...he burner and place upside down on a flat surface covered with old newspaper BURNER To access the burner remove the coals The burner is glued in to the burner tray Examine it for any damage and check...

Page 10: ...et blocked Gas pressure too low Tighten at rear of valve Replace Oxypilot Blow clean out Pilot runs off mains pressure which must be at least 1 135 Kpa Gas will not ignite After turning off Time safet...

Page 11: ...11...

Page 12: ...GLEN DIMPLEX AUSTRALIA PTY LTD ABN 69 118 275 460 Head Office Factory Showroom 1340 Ferntree Gully Rd Scoresby Vic 3179 Ph 1300 554 155 Fax 03 8706 2001...

Reviews: