SERVICING DETAILS

• The following notes are to assist a serviceman in the event of a malfunction.
• Servicing must only be carried out by authorised personnel.
• Spare parts and advice are available from Glen Dimplex on 1300 554 155.
• See also the Fault Finding chart.

To Check Burner Pressure

• Gas consumption is 35 MJ/hr - Natural Gas ONLY.
• Appliance Test point pressures: High:Natural Gas 0.50 kPa
• The burner pressure test point is on the valve to the left. The rear test point is the supply or inlet

pressure and the front point is the appliance test point.

• Remove test point plug and connect manometer. Switch the gas and appliance on. Take

pressure reading once the unit is running and it should be within tolerance. Turn the unit and

gas off, disconnect the manometer and replace the test point plug.

• The pilot runs off the inlet pressure and needs a minimum of 1.135 Kpa to stay alight.

To Make Pressure Adjustments

• The regulator adjusts the burner pressure. The adjusting screw is on the right hand side of the

valve under the plastic front cover.

GAS CONTROL

• The SIT gas control and valve is situated under the burner tray. To access; remove the coals

and disconnect the gas supply. Remove the burner and place upside down on a flat surface

covered with old newspaper.

BURNER

• To access the burner remove the coals. The burner is glued in to the burner tray. Examine it for

any damage and check the venturi at the rear for lint and dust. Carefully clean as required.

• Ensure that the main injector is located centrally with respect to the venturi.
• Minor cracking of the ceramics is normal and will not affect the operation of the appliance.

FAN (if the appliance is fitted in a FFB convector box)

• To remove the fan, ensure that the fan has been unplugged from the power supply, unscrew the

4 screws holding the fan to the front of the fire box. Carefully lift the fan assembly forward.

• The fan’s wiring diagram is located next to the terminal block. The fuse is a 1 amp fuse.

WARNING

Improper use of this gas fire could be hazardous to health. This fire is to be used either in a

WONDERFIRE FFB convector box properly installed and flued in accordance with its

instructions, or a non-combustible fireplace with the chimney or flue free of any obstruction

or damper.
The fireplace, hearth, chimney, flue, canopy or any other part associated with the fireplace

must conform with the relevant building regulations for domestic type solid fuel burning

appliances.

We strongly recommend the use of an approved fireguard whenever young children

or the infirm are in the presence of a working fire.

Summary of Contents for WONDERFIRE AF18

Page 1: ...tified as a Space Heater WONDERFIRE AF18 OF MANUAL VALVE INSTALLATION OPERATING MANUAL Nectre Wonderfire fire boxes are approved to be installed as a zero clearance firebox and are designed to operate...

Page 2: ...tructions or b it has been installed in an outdoor setting 4 Limit of Liability The warranty provided under this warranty is limited to replacement or repair of the Gas Burner only at our option To th...

Page 3: ...THE APPLIANCE OR DRAUGHT OF CHIMNEY OR FLUE DO NOT MODIFY THIS APPLIANCE THIS APPLIANCE IS DESIGNED TO OPERATE WITH LUMINOUS FLAMES THIS MAY EXHIBIT SLIGHT CARBON DEPOSITS Permanent ventilation of th...

Page 4: ...4 CONTENTS Contents 4 Data Plate 5 Dimensions 5 User Instructions 6 Installation Instructions 7 Servicing Details 9 Fault Finding Chart 10 Glen Dimplex contact information 12...

Page 5: ...the unit for reference to gas pressure consumption 5 AF18 OF Manual valve Eurosit 630 Gas Injector Size mm TPP N G C Mj Hr Natural Gas 1 x injector multiport 7 ports x 1 25 0 5kPa high 0 35kpa Low 35...

Page 6: ...not stay alight contact the supplier Once the pilot is alight you may turn the gas control knob to the high setting 7 The fire will ignite from the pilot If required you may now turn the gas control...

Page 7: ...erall dimensions of the fire is 465mm wide front 325mm wide rear x 240mm Deep x 320mm high See below for minimum fire place dimensions The appliance may be installed in an existing open fireplace as a...

Page 8: ...d be fixed to the base of the fireplace with a screw to each front corner of the burner Gas Gas connection is to a BSP male fitting connected to the RHS of the valve It is located 100mm from front 45m...

Page 9: ...he burner and place upside down on a flat surface covered with old newspaper BURNER To access the burner remove the coals The burner is glued in to the burner tray Examine it for any damage and check...

Page 10: ...et blocked Gas pressure too low Tighten at rear of valve Replace Oxypilot Blow clean out Pilot runs off mains pressure which must be at least 1 135 Kpa Gas will not ignite After turning off Time safet...

Page 11: ...11...

Page 12: ...GLEN DIMPLEX AUSTRALIA PTY LTD ABN 69 118 275 460 Head Office Factory Showroom 1340 Ferntree Gully Rd Scoresby Vic 3179 Ph 1300 554 155 Fax 03 8706 2001...

Reviews: