INKA, IOR, REPO & LINK
3.7 Technical Alarms
3.7.1 Radio Test Alarm
To let the alarm receiver know that the unit is working, INKA, IOR and REPO can send test alarms to
the alarm receiver at regular intervals. By default this function is turned off. Selecting an interval
between 1 hour and 255 hours turns the function on. Interval time zero (0) hours means that the
function is turned off.
The
test alarm interval
parameter is found in the
miscellaneous
section under the
preferences
tab in
IOR Programmer.
INKA
IOR
REPO
Deactivate the test alarm function
Enter the value 0 in text box 305
INKA
IOR
REPO
Activate the test alarm function and set
the test alarm interval.
Enter the desired time (in hours) in text
box 305
Please note that no radio test alarms are sent in
power save mode
3.7.2 Battery Alarm: INKA, IOR and REPO
INKA, IOR and REPO can be configured to send a
battery alarm
when the battery voltage is too low.
The reason for the alarm can be
•
The batteries are getting old and must be replaced
•
The AC/DC adapter is not connected and the unit has been
battery-powered for a long time (IOR and REPO)
The battery voltage is continuously supervised. If the battery voltage is too low, a battery alarm is sent
every day until the batteries are replaced. The limit for low battery voltage is 2.6 V in INKA and 3.5 V
in IOR and REPO.
Please note that no battery alarms are sent in
power save mode
The
battery alarm
parameter is found in the
miscellaneous
section under the
preferences
tab in IOR
Programmer.
INKA
IOR
REPO
Activate the
battery alarm
function
Select “Yes/Function on” in list box 302
INKA
IOR
REPO
Deactivate the
battery alarm
function
Select “No/Function off” in list box 302
Technical Handbook for the IOR Family (firmware v20.x), document number NE41 06007-02 v1.0