INKA, IOR, REPO & LINK
1.8 Inputs: INKA and IOR
Connect wired sensors to the connector marked IN on the bottom side of the unit, see section 1.2.1-
1.2.2.
Up to 5 alarm sensors can be connected to the same INKA or IOR unit. The first sensor is connected
between pin 3 and 8 in the input connector, the second sensor is connected between pin 4 and 8, the
third between pin 5 and 8, the fourth between pin 6 and 8 and the fifth sensor is connected between
pin 7 and 8 in the input connector. See image below.
Note that inputs 4 and 5 are not available when running INKA or IOR on batteries in
power save
mode
The connected alarm sensors may be powered from INKA and IOR. The unregulated voltage from the
AC/DC-adapter is supplied between pin 1 and pin 8 in the input connector. With the standard AC/DC-
adapter from NEAT, this voltage is 5-9V
DC
. A total of 250 mA may be drawn from pin 1 and 8. A
regulated voltage of 3 V
DC
is supplied between pin 2 and pin 8 in the input connector. A total of 50 mA
may be drawn from pin 2 and 8.
Technical Handbook for the IOR Family (firmware v20.x), document number NE41 06007-02 v1.0
11