40 System Details
4.7.4 Fan Motor
Item
Description
Function
Supplies combustion air for the burner and purges exhaust flue gas.
To maintain gas input over long flue runs, the fan use APS to provide ideal combustion levels.
Fault
1. Fan speed failure: When fan speed is approximately 0 rpm.
2. A fan assembly screw is loose and/or the fan is disassembled.
3. Disconnected or defective fan connection terminal assembly.
Symptoms
1. Erratic combustion.
2. Vibration and noise coming from the boiler.
3. The boiler does not operate correctly.
Error codes
E109, E110
Diagnostics
1. Visual inspection: check the fan’s wiring connections and mounting.
2. Voltage test: Test the fan voltage for the specified voltage shown below.
Testing/inspection
information
Black - Yellow: DC 340 V
Summary of Contents for NCB300-28K
Page 3: ......
Page 4: ...Revisions 3 Version Description of changes Date 1 00 First issue September 7 2022 Revisions...
Page 106: ...Memo...
Page 107: ...Memo...
Page 108: ...Memo...