GV5/GV3.5 OPERATIONS & MAINTENANCE MANUAL
OPERATING THE TRANSMITTER
PAGE 3.2.162
VERSION 0.2 2014-07-23
Selecting the
Low Audio
tab displays a screen that allows for setting of the low trip level and
timeout delay for the main audio and SCA audio low thresholds.
If the applicable audio source (main or SCA) level falls below the
Trip Leve
l setting (default is
-22.5 dB) for longer than the
Timeout
setting (default is 20 s), an alarm will activate in the
Status
and
Logs
pages. When the audio source level increases above the
Trip Level
, the
alarm will clear. To disable the low audio alarm, set the associated
Trip Level
to -100 dB. Press
Apply
to save the change or
Cancel
to discard changes.
Selecting the
Low Forward Power
tab displays a screen that allows for setting of the threshold for
the low forward power and very low forward power alarms.
If the forward power falls below the low threshold setting (default is 50% of the setpoint) or
below the very low threshold setting (default is 12.5% of the setpoint), the associated alarm
will activate in the
Status
and
Logs
pages. When the forward power level increases above a
threshold, the alarm will clear. To disable the low forward power alarms, set the associated
percentage to 0%. Press
Apply
to save the change or
Cancel
to discard changes.
Summary of Contents for GV3.5
Page 2: ......
Page 4: ......
Page 8: ...GV5 GV3 5 OPERATIONS MAINTENANCE MANUAL PAGE 3 VIII VERSION 0 2 2014 07 23...
Page 16: ...GV5 GV3 5 OPERATIONS MAINTENANCE MANUAL DESCRIPTION PAGE 3 1 8 VERSION 0 2 2014 07 23...
Page 18: ...VERSION 0 2 2014 07 23 PAGE 3 1 10 LJXUH 9 9 XGLR 3DWK ORFN LDJUDP...
Page 239: ...GV5 GV3 5 OPERATIONS MAINTENANCE MANUAL ROUTINE MAINTENANCE PAGE 3 3 10 VERSION 0 2 2014 07 23...
Page 249: ...GV5 GV3 5 OPERATIONS MAINTENANCE MANUAL LIST OF TERMS PAGE 3 5 2 VERSION 0 2 2014 07 23...
Page 250: ......