Table 4. Error Status of E1 and E2 LEDs

Error

E1 LED

E2 LED

 

 

 

No error

Off

Off

Underrange

Off

On

Overrange

Off

On

Supply voltage faulty

On

On

Parameter table invalid

Off

On

Device error

Off

On

Flash format error

Off

On

Note

 

The reported error depends on the measuring range. For information about

input scaling, refer to the device datasheet on 

ni.com/manuals

.

Connecting the REM-11102

Figure 4. REM-11102 Current Measurement Connection

24 VDC

AI+ (0:3)

AI– (0:3)

U

IS

 (0:3) 

GND

24 VDC

Sensor

GND

x4

REM-11102

+

a1

a2

b1

b2

U

IS

 and GND are optional, sensor-dependent connections.

REM-11102 Getting Started Guide

  | 

© National Instruments

  | 

9

Summary of Contents for REM-11102

Page 1: ...ght not meet the same safety ratings Refer to the documentation for each component in the system to determine the safety and EMC ratings for the entire system Caution Do not operate the REM 11102 in a...

Page 2: ...romagnetic environment This product is intended for use in industrial locations However harmful interference may occur in some installations when the product is connected to a peripheral device or tes...

Page 3: ...g the device ground yourself using a grounding strap or by holding a grounded object such as your computer chassis 1 Touch the antistatic package to a metal part of the computer chassis 2 Remove the d...

Page 4: ...ED indicators Table 1 Module Function Labels Label Color Module Function Blue Digital input Red Digital output Green Analog input thermocouple Yellow Analog output White Bus coupler power module Insta...

Page 5: ...bus connector Note A bus connector will not attach to a preceding bus connector with a mounted module Remove the preceding module before installing additional bus connectors 3 Repeat Steps 2 and 3 for...

Page 6: ...the underside of the module 2 Press the REM 11102 directly onto the bus connector and DIN rail until it clicks into place Caution Tilting the module when mounting it on the DIN rail will damage the c...

Page 7: ...ly for analog modules internally jumpered b1 b2 Blue GND Reference potential of the supply voltage internally jumpered 00 to 03 Orange AI0 to AI3 Positive voltage connection for channel 0 to 3 10 to 1...

Page 8: ...detect a valid cycle after power on Flashing The REM 11102 is not part of the configuration Red Solid The REM 11102 has lost connection to the Bus Coupler Flashing The REM 11102 has lost connection t...

Page 9: ...r Off On Note The reported error depends on the measuring range For information about input scaling refer to the device datasheet on ni com manuals Connecting the REM 11102 Figure 4 REM 11102 Current...

Page 10: ...utside the specified tolerance limits in environments subject to heavy noise Connect the cable shield to functional earth ground immediately after the cables enter the control cabinet Connect the cabl...

Page 11: ...r from the module Removing the REM 11102 Remove all connections before removing the REM 11102 either by disconnecting the cables or removing the spring terminal block What to Use Flathead Screwdriver...

Page 12: ...us connector 1 3 2 1 Slide the bus connector away from the preceding bus connector at least 5 0 mm 0 20 in 2 Insert the screwdriver and loosen both latches on one side of the DIN rail 3 Rotate the bus...

Page 13: ...t ni com services for NI Factory Installation Services repairs extended warranty and other services Visit ni com register to register your NI product Product registration facilitates technical support...

Page 14: ...Instruments Patent Notice at ni com patents You can find information about end user license agreements EULAs and third party legal notices in the readme file for your NI product Refer to the Export C...

Reviews: