background image

GLT-299-7-17 Rev.1 

Jan  24, 2022 

 

 

 

ADDRESS SETTING PORT 

 

Instruction Manual

 

VDOT-Mini IP    Mini Input Module

                   

 

Before Installation 

Please read these instructions carefully and keep for future reference.   

The information in this document is subject to change without notice. 

For updates please refer to our website. 

 

 

 

 

 

 

 

Note

 

Follow the requirements for the installation of the product in 

accordance with the Specifications. Otherwise it may cause damage to 

equipment.

 

Note

 

Do not install the product in any location where oil, dust, iron 

powder, chemicals, or hydrogen sulphide may occur or affect the product. 

It may cause damage to equipment.

   

 

This package contains the following items: 

Main unit

……………………………………………………………………

Instruction Manual

  ………………………………………………………

EOL  Resistor  (VDOT-RE-10k)

………………………………………………

Sealing label

…………………………………………………………………

 

General Description 

VDOT-MiniIP Mini Input Module is intended for use in addressable two 

wire systems. The module monitors and transmits the status (normal, 

open, short, or active) of devices equipped with NC/NO dry contacts to a 

control panel. The initiating device circuit (IDC) can be wired on   

Class B.   

 

General Operation 

Normal standby condition: The module receives polling from the control 

panel at the regular interval. 

Active condition: When the external input is activated, the module 

communicates to the control panel the active status. 

Trouble condition: The module communicates to the control panel the 

open/short status of IDC, depending on the Subtype Setting described 

below.

 

 

 

 

 

 

 

 

 

 

Figure 1 

Compatibility Requirement 

To ensure proper operation, the module shall be connected to UL listed 

control panel series. Any conventional detector cannot be connected 

with the module. 

 

Before Installing 

Disconnect power to the control panel before installing the module. If 

the module  is  installed in an existing operational system, inform the 

operators and local authorities that the system will be temporarily out 

of service.   

 

Mounting 

Mount or place the module on the back or inside of monitored unit. Its 

small size and light weight allow it to be installed without rigid 

mounting.   

 

Setting 

Address Setting 

Use VDOT-AD2 Programmer for setting the address of the module prior 

to installation. VDOT-MiniIP  has an address given at random from 

factory.  Connect the Programmer with the address setting port to 

change the address to any of 1-254  (dec), with reference to the 

instruction manual of VDOT-AD2 Programmer. The address can be set 

regardless of whether power supply from the control panel is turned on 

or off. Refer to Figure 1. 

ZETA ALARMS LIMITED 

72-78 MORFA, ROAD, SWANSEA, SA1 2EN 

  http://www.velocitydetection.com 

Do not use the products outside the rated power supply voltage range 

specified in the Specifications. It may cause a fire or damage to 
equipment.

CAUTION

!

Do not disassemble, repair, or modify the products. It may cause a fire or 

electric shock.

CAUTION

!

Make sure to turn the power off before commencing any wiring work. 

Otherwise it may cause electric shock or damage to equipment.

CAUTION

!

mm(in) 

Summary of Contents for VDOT-Mini IP

Page 1: ...s of IDC depending on the Subtype Setting described below Figure 1 Compatibility Requirement To ensure proper operation the module shall be connected to UL listed control panel series Any conventional detector cannot be connected with the module Before Installing Disconnect power to the control panel before installing the module If the module is installed in an existing operational system inform t...

Page 2: ...tall module wiring in accordance with the appropriate wiring diagrams Do not connect cables in reverse polarity Failure to connect the polarity correctly could result in damage to the module and or other equipment CAUTION Refer to the figures below for wiring styles Note All wiring is power limited and supervised Note The SLC signaling line circuit of VDOT MiniIP supports Class A and Class B wirin...

Page 3: ... module goes back to the initial status after the external input is reset on the control panel 5 If subtype is set as 1 and 2 or 5 and 6 open between terminal A and A and confirm that the control panel detects the open circuit If subtype is set as 3 6 short between terminal A and A and confirm that the control panel detects the short circuit FOR WARRANTY SERVICE RETURN TO ZETA ALARMS LIMITED 72 78...

Page 4: ...this had been paid And the warranty period is three 3 years from the shipment from Zeta s factory 1 3 Notwithstanding anything to the contrary in this warranty terms Zeta shall not be liable to the customer by reason of any representation or implied warranty condition or other term or any duty at common law or under the express terms of this warranty terms for any consequential loss or damage whet...

Reviews: