Figure 5. Loop-Powered Current Tranducer with REM-11102 Sensor Supply
24 VDC
AI+ (0:3)
AI– (0:3)
U
IS
(0:3)
GND
+ 24 V
Sensor
REM-11102
+
–
a1
a2
b1
b2
Figure 6. Loop-Powered Current Tranducer with External Supply
24 VDC
AI (0:3)+
AI (0:3)–
U
IS
(0:3)
GND
Sensor
REM-11102
+
–
+
–
a1
a2
b1
b2
Note
For information about fuse ratings for the REM-11102, refer to the device
Connection Guidelines
•
Always connect analog signals using shielded, twisted pair cables. Unshielded cables
may lead to values outside the specified tolerance limits in environments subject to heavy
noise.
•
Connect the cable shield to functional earth ground immediately after the cables enter the
control cabinet.
•
Connect the cable shield to a shield bus if you are not using a closed control cabinet.
•
NI recommends using the NI Remote I/O Shield Set for optimal shield connection.
•
Make sure that devices you connect to the REM-11102 are compatible with the module
specifications.
•
Push the wire into the terminal when using a solid wire or a stranded wire with a ferrule.
•
Open the terminal by pressing a screwdriver into the spring lever when using a stranded
wire without a ferrule.
10
|
ni.com
|