Figure 1. Minimal safety clearances for the SAANA heater. 

The installation of 

a heater in a wall 

recess 

B min

A min 

A min

max 300 mm

A min

D min 

C min 

Figure 2.

3. INSTALLATION:

 

3.1 Installation instructions for the heater, the temperature sensor and the control unit

-   Connection of the sauna heater to the power supply may only be carried out by an  

  authorised electrician in accordance with the valid regulations.

-  A rubber-sheathed cable of type H07RN-F or similar must be used as the connection cable.

-  If you want to make use of the temperature control feature, we recommend using a rubber cable 

  with at least seven wires. The cross-section of the cable and the fuse size are presented in Table 1.

3.11 Connection the power supply cable  

  -  Lay the sauna heater on the floor, with its front facing the floor

  -  Remove the bottom plate

  -  Connect the power cable. Do not connect voltage to the heater before adding 

    the temperature sensor and the controller.

3.12 Installing the temperature sensor

-  Install temperature sensor to the wall, above the sauna heater so it is located 100mm below 

  the ceiling. (see Fig. 2)

-  The supply air valve must not be located closer than 1000mm from the temperature sensor. 

  If the valve is located 500-1000mm from the sauna heater, an adjustable valve is needed and 

  set to channel the air away from the sauna heater. If the supply air valve is too close to the 

  temperature sensor, the heater will receive false data and it might result in overheating 

  the sauna heater.

-  If the heater is installed more than 200mm away from the wall, the temperature sensor must be

  placed into the ceiling 100mm away from the heaters outer surface.

-  Install the sensor in the area lined in Figure 2.

-  Install the temperature sensor on the wall with the screws included in the delivery (2 pcs. Ø 2,9 x 16).

-  The wiring for the temperature sensor can be embedded.

-  Connect the sensor to the circuit plate, as shown in Fig. 2.1.

-  Connect the end of the conductor, the one with no connector in place, to the temperature sensor. 

  You can cut the conductor to a suitable length.

Fastening of the control unit 

to the wall. ATTENTION! 

The control unit must 

not be installed in a wall 

recess.

Figure 3.

 

HUOM! Ohjausyksikköä ei saa 

asentaa seinäsyvennykseen.

M

ax. 900 mm

min. 600 mm

100 mm

M

ax. 900 mm

min. 600 mm

100 mm

Figure

 2.1 

Connection of circuit board 

Socket for the 

control unit 

The locking lever 

on the outer edge 

side!
Socket for the 

temperature 

sensor

Fuse

Summary of Contents for SAANA

Page 1: ...NARVI SAANA 6 8kW 9kW FI SE GB DE RU ASENNUS JA K YTT OHJE INSTALLATIONS OCH BRUKSANVISNING INSTALLATION AND INSTRUCTION MANUAL INSTALLATIONS UND BETRIEBSANLEITUNG VERSIO 9 2019...

Page 2: ......

Page 3: ...A kiukaan asennustiedot Saunan minimikorkeus on m ritelty taulukossa 1 samoin kuin minimisuojaet isyydet Varmista ett kiinnityslevyn ruuveille on riitt v n tukeva kiinnitysalusta Pelkk ohut paneeli ei...

Page 4: ...tuloilmaventtiili jolla ilmavirta saadaan suunnattua poisp in anturista L hell anturia sijaitsevan tuloilmaventtiilin ilmavirta voi v rist anturin mittaustulosta ja kiuas voi ylikuumentua Jos kiuas as...

Page 5: ...a l mp tilan asetukset s ilyv t muistissa my s lyhyen s hk katkon j lkeen Pidemm n s hk katkon j lkeen ajat ovat oletusarvoja Esiajastusaika menee nollaksi aina k yt n j lkeen On Off LED palaa punaise...

Page 6: ...T m n j lkeen kiuas siirtyy normaaliin toimintatilaan ja sen j lkeen teht v t p ll oloajan asetukset vaikuttavat vain kyseiseen saunomiskertaan Painamalla SET nappia keltainen LED vilkkuu ja n ytt n t...

Page 7: ...ema 100 C 7 Painetaan SET nappia kiuas menee p lle ja asetetut arvot j v t muistiin my s seuraava kertaa varten Halutaan asettaa kiuas p lle vasta 3 tunnin kuluttua 1 Kytket n virta I O napista 2 Pain...

Page 8: ...suunnatulla suulakkeella Painovoimaisella ilmanvaihdolla tuloilmaventtiili suositellaan asennettavaksi kiukaan viereen tai alapuolelle joko sein n tai lattiaan Raitisilman tuonnissa on t rke ilman se...

Page 9: ...VIO Kiukaan eristysresistanssimittauksessa saattaa esiinty vuotoa johtuen varastoinnin tai kuljetuksen aikana l mmitysvastuksien eriste aineeseen imeytyneest ilmassa olevasta kosteudesta Kosteus saada...

Page 10: ...ilt Takuu ei korvaa ulkopuolisten h iri iden aiheuttamaa sulakkeen hajoamista Ohjaimen johto on vaurioitunut tai kontakti on huono ohjaimen liitoksissa Ohjaimen kotelo on v ntynyt esim kiinnityksen ta...

Page 11: ...ll 1 f r varken verskridas eller underskridas Tabell 1 Installationsdata f r SAANA aggregat Bastuns minimih jd samt minimis kerhetsavst nden anges i tabell 1 F rs kra dig om att f stunderlaget f r f s...

Page 12: ...ntil anv ndas och kalluften b r styras bort t fr n aggregatet Om friskluftventilen ligger f r n ra termostaten kan termostaten tolka fel temperatur vilket kan leda till att aggregatet verhettas Om bas...

Page 13: ...svarande v rdet Inst llningarna f r den p kopplade tiden och temperaturen blir kvar i minnet ven under ett kort elavbrott Efter ett l ngre elavbrott terst lls tiderna till sina utg ngsv rden F rvalsti...

Page 14: ...tl ge och eventuell justering av den p kopplade tiden inverkar endast p den aktuella uppv rmningen D du trycker ned knappen SET b rjar den gula diodlampan blinka och det visas nollor i rutan Efter det...

Page 15: ...sl s p och de inst llda v rdena sparas i minnet f r n sta g ng Om du nskar att bastuaggregatet kopplas p f rst efter 3 timmar 1 Koppla p str mmen via knappen I O 2 Tryck ner knappen SET den gula diod...

Page 16: ...tt inloppsluftventilen installeras bredvid eller under bastuaggregatet antingen i v ggen eller i golvet Vid intagningen av friskluft r det v sentligt att den blandas med basturummets luft och bad ngan...

Page 17: ...ller klor f r anv ndas Saltvatten och fuktig inneluft p skyndar bastuugnens korrosion 10 KOPPLINGSSCHEMA M tning av bastuaggregatets isoleringsmotst nd kan utvisa l ckage vilket beror p att isolermat...

Page 18: ...or som orsakats av externa orsaker Controllerns kabel kan vara skadad eller felaktigt kopplad Controllers plastfodral har g tt s nder t ex vid installeringen Knapparna fungerar inte eller r nedtryckta...

Page 19: ...e 1 Table 1 Installation information for SAANA heaters The minimum height of the steam room and minimal safety clearances are shown in table 1 Make sure that the surface onto which the fastening plate...

Page 20: ...air valve must not be located closer than 1000mm from the temperature sensor If the valve is located 500 1000mm from the sauna heater an adjustable valve is needed and set to channel the air away fro...

Page 21: ...he exterior coating of the heater using safety gloves When piling the stones make sure that the resistors do not get bent and that the circulation of air is sufficient Stones 5 10 cm in diameter are s...

Page 22: ...ing mode and any subsequent settings of the power on time will only affect the current heating session When the SET button is depressed the yellow LED will flash and an array of zeros will be displaye...

Page 23: ...epress the SET button the heater is switched on and the set values will be saved for the next time You wish to switch on the heater in about three hours 1 Switch on the power using the I O button 2 De...

Page 24: ...on is natural we recommend placing the inlet air valve on the side of the heater or under it either in the wall or in the floor It is important to introduce fresh air so that the air mixes with the ai...

Page 25: ...humid climate fastens the corrosion of the heater 10 CONNECTION SCHEME When measuring the insulation barrier of the heater some leakage may occur which is caused by the humidity that has seeped into...

Page 26: ...ire may be damaged or it has a bad connection The control units casing has been damaged for example if it is installed incorrectly Buttons does not work or are pressed down constantly Open the lid and...

Page 27: ...zum Aufbau von SAANA fen Die Mindesth he des Saunaraums sowie die Mindestsicherheitsabst nde werden in Tabelle 1 dargestellt Stellen Sie sicher dass die Oberfl che auf der die Befestigungsplatten ver...

Page 28: ...rs Montieren Sie den F hler an der Wand oberhalb Ihres Elektro Saunaofens 100 mm unterhalb der Decke s Abb 2 Das Lufteinlassventil darf sich nicht n her als 1000 mm vom Temperaturf hler befinden Falls...

Page 29: ...Nach einer l ngeren Unterbrechung der Stromversorgung kehren die Zeiten zu den Defaultwerten zur ck Die Vorlaufdauer jedoch wird nach jeder Benutzung auf null zur ckgesetzt Die On Off LED leuchtet rot...

Page 30: ...erden Danach geht der Saunaofen in den normalen Betriebszustand ber und die sp ter vorgenommenen Einstellungen an der Einschaltdauer wirken sich nur auf die jeweilige Saunarunde aus Nach dem Dr cken d...

Page 31: ...hert Man m chte dass der Saunaofen erst nach 3 Stunden eingeschaltet wird 1 Schalten Sie mit dem I O Taster ein 2 Bet tigen Sie die SET Taste die gelbe LED blinkt 3 Bet tigen Sie die Tasten oder so of...

Page 32: ...il neben oder unter dem Saunaofen in der Wand oder im Boden eingebaut werden Es ist wichtig Frischluft hereinstr men zu lassen damit sich diese mit der Luft und dem Dampf in der Sauna vermischt Die hi...

Page 33: ...t werden Auch Wasser mit Chlorgehalt darf nicht verwendet werden Feuchte Luft und Seeklima beschleunigen die Korrosion Ihres Saunaofens 10 ANSCHLUSSSCHEMA Wenn Sie die Isolationsbarriere des Ofens ber...

Page 34: ...den Saunaofen vor St rungen im Stromnetz Die Garantie gilt nicht f r Besch digung der Sicherung aus u eren Ursachen Das Steuerkabel ist besch digt oder der Kontakt in den Anschl ssen ist schlecht Das...

Page 35: ...9 903005 903015 RU 1 1 2 3 4 5 2 3 1 1 5 3 1 1 1 SAANA 1 400 V 3N A B C D 3 3 2 A SAANA 903003 SAANA 903013 6 8 5 8 1900 120 120 970 30 80 5x1 5 3x10 SAANA 903005 SAANA 903015 9 8 14 1900 120 120 970...

Page 36: ...1 3 11 3 12 100 2 1000 500 1000 200 100 2 2 9 x 16 2 1 3 HUOM Ohjausyksikk ei saa asentaa sein syvennykseen Max 900 mm min 600 mm Fastening of the control console to the wall ATTENTION The control con...

Page 37: ...4 5 4 1 I O SET ON OFF ON OFF 6 ON OFF SET 3 2 SAANA 4 5 10 5 4 3 13 90 60 3 2 3 5 15 2 1 3 0 10...

Page 38: ...4 3 ON OFF 30 4 4 15 4 5 ON OFF ON OFF 3 3 3 4 6 1 SET 30 SET SET SET 60 C 115 C SET ON OFF ON OFF 4 2 60 C 115 C...

Page 39: ...4 7 3 d 1 d 1 d 2 d 3 d 1 d 2 d 3 SET SET 1 d 4 8 100 C 2 5 1 I O 2 SET 3 SET 4 2 30 5 SET 6 100 C 7 SET 3 1 I O 2 SET 3 3 00 4 SET 5 SET 6 SET SET 15 1 SET 2 3 SET 4 SET 5 1 I O SET 1...

Page 40: ...5 5 1 60 C 115 C 24 4 5 2 IPX4 5 3 230 3 50 16 A 10 5 IPX4 144 C 250 6 3 6 100 1000 500 100 150 7 8...

Page 41: ...t L mp tila anturi Temperaturgivare Temperature sensor Temperatursensor Piirilevy Kretskortet Circuit board Leiterplatte PE L1 L2 L3 N 162957 08_2018 N2014 L1 L2 L3 N N PE L1 L2 L3 L1 L2 L3 N N PE L1...

Page 42: ...11 o opy a o ocy ec c a po a c pco o Er1 Er2 Er3 10k 25 C 1...

Page 43: ......

Page 44: ...Narvi Oy Yritt j ntie 1 27230 Lappi Finland Tel 358 207 416 740 www narvi fi Narvi Oy pid tt oikeudet tuotteisiin tuleviin muutoksiin 9 2019...

Reviews: