W415-3101 / B / 01.09.23
26
IOM
IOM
10.6 MULTIPLE
VENTING
H15.6.3B
COMMON VENTING IS PROHIBITED!!
If two of these furnaces are to be installed in close proximity, the combustion air intake and exhaust terminations
may be installed as shown in Figures 12 and 13.
IMPORTANT
:
WHEN INSTALLING MULTIPLE FURNACES IN CLOSE PROXIMITY, EACH REQUIRES
DEDICATED COMBUSTION AIR AND EXHAUST VENTING.
If more than two furnaces are being installed in close proximity, each additional combustion air intake and
exhaust termination set shall not terminate less than 12 in (305mm) apart. Note: Canadian installations of
120000 Btu/hr require 3 ft (915mm).
FIGURE 13 - MULTIPLE VENTING (STANDARD
VERTICAL)
12" (305mm)
MIN. ABOVE
SNOW LEVEL
30" (762mm) MAX.
12" (305mm)
MIN.
3"
(76mm)
MIN.
TO BE REDUCED
FROM 3" PVC TO
2" PVC BELOW THE
COMBUSTION AIR
INTAKE 2" PVC
TWO FURNACES VENTING
THROUGH ROOF
3"
(76mm)
8"
(203mm)
MIN.
3"
(75mm)
MIN.
EXHAUST
GRADE
12"
(305mm)
MIN.
INTAKE
12" (305mm) MIN.
12" (305mm) MIN.
2"
(51mm)
MIN.
FIGURE 12 - MULTIPLE VENTING (STANDARD
HORIZONTAL)
H15.5A
Avoid locating the terminal in locations where dripping condensate may cause problems such as sidewalks,
patios, above planters, near windows where exhaust gases may cause fogging, icing, etc.
Avoid locating the termination too close to shrubs and other vegetation. The condensate may stunt or kill them.
Caulk all cracks, seams or joints within a 6 foot (1.8m) radius of the termination.
Do not terminate under a deck unless there is adequate clearance to prevent damage from the fl ue gases.
A termination may be located at the end of a patio deck. Piping running beneath the deck must be suitably
insulated and suspended in a manner to prevent condensate from collecting and freezing.
When locating vent terminations, consideration must be given to prevailing winds, location, and other
conditions. These conditions may cause recirculation of the combustion products of adjacent vents. Do not
locate the terminal on the side of the building facing the prevailing winter winds.
IMPROPER LOCATION OR INSTALLATION CAN RESULT IN STRUCTURAL DAMAGE TO
THE BUILDING, DAMAGE TO THE EXTERIOR FINISH OF THE BUILDING, OR MAY ALLOW
RECIRCULATION OR FREEZING OF THE FLUE GASES ONTO OR INTO THE COMBUSTION
AIR INTAKE.
MOISTURE IN THE FLUE GASES CONDENSES AS IT LEAVES THE TERMINALS. THIS
MOISTURE CAN FREEZE ON EXTERIOR WALLS, SOFFITS, AND OTHER NEARBY
OBJECTS. SOME DISCOLORATION IS TO BE EXPECTED.
CAUTION
!
!
The vent terminal should be located no fewer than 3 feet (.9m) from an inside corner formed by two exterior walls.
Recommended clearance for overhangs is a minimum of 1 foot (.3m) vertically for each foot horizontally up to
6 feet (1.8m).
Any adjacent painted surfaces should be in good condition; no cracks, peeling paint, etc. If wooden surfaces that
may be periodically exposed to fl ue gases are present, consider treating with a sealer
.
H3.15
RECIRCULATION OF FLUE GASES MAY OCCUR CAUSING THE INTAKE PIPE TO
FREEZE SHUT DURING COLD WEATHER OPERATION IF THE VENTING SYSTEM IS NOT
INSTALLED PER THESE GUIDELINES.
WARNING
!
!
Summary of Contents for WSX-N Series
Page 153: ...W415 3101 B 01 09 23 153 MU...
Page 154: ...W415 3101 B 01 09 23 154 MU...
Page 155: ...W415 3101 B 01 09 23 155 MU...