background image

3.2 

SHUTTING DOWN THE FURNACE

3.3 OPERATING 

TIPS

H26.2

IMPORTANT:

  

If you intend to be away from home for lengthy periods of time during the non-heating season, 
it is advisable to follow the furnace shut down procedure.

1.  Set the thermostat to its lowest setting.
2. Shut 

o

  electric power to the furnace.

3.  Turn the furnace manual shut-o

  valve to the “OFF” position.

4.  Remove the burner access door, turn the manual gas valve switch to the “OFF” position, then re-install the 

burner access door.

H26.3

1. Clean 

air 

fi

 lters maximize e

  ciency, and reduce heating costs.

2.  During the heating season, keep windows and doors closed to reduce the heating load on the system.
3.  Avoid excessive use of kitchen exhaust hoods and other exhaust fans to reduce the heating load on the 

system.

4.  Arrange the furniture and drapes so that the supply air registers and return air grills are unobstructed.
5.  If you have a perimeter duct system, ideally, the warm air should bathe the interior walls. Avoid the use of 

plastic de

fl

 ectors on the supply air registers which tend to short circuit the warm air straight into the return 

air grills.

6.  Avoid placing heat producing appliances such as televisions, radios, lamps, etc. in a location to in

fl

 uence 

the thermostat.

7.  Keep combustible articles at least 3 feet (0.91m) away from the furnace. Do not block access for servicing 

the furnace Do not use the combustion air or exhaust piping as a hanger for clothes or anything else.

IMPORTANT:

  

NEVER ATTEMPT TO OPERATE THE FURNACE WITHOUT THE BLOWER DOOR AND 
COMBUSTION COMPARTMENT DOOR IN PLACE OR WHEN THE BLOWER HAS FAILED.

W415-3101 / B / 01.09.23

71

  

UM

Summary of Contents for WSX-N Series

Page 1: ...or property damage As a professional installer you have an obligation to know the product better than the customer This includes all safety precautions and related items Prior to actual installation...

Page 2: ...R COMBUSTION AIR TWO PIPE SYSTEM 24 9 4 3 COMBUSTION AIR 24 10 0 TERMINATIONS 25 10 1 COMBUSTION AIR 25 10 2 EXHAUST 25 10 3 CONCENTRIC VENTING KIT 25 10 4 CONCENTRIC VENT TERMINATION INSTALLATION INS...

Page 3: ...S LED 56 19 6 FAULT CODE HISTORY 56 20 0 WIRING DIAGRAM FOR TWO STAGE FURNACE 57 21 0 WARRANTY 59 22 0 REPLACEMENT PARTS LIST 60 23 0 SERVICE HISTORY 62 NOTE Changes other than editorial are denoted b...

Page 4: ...TICES CAUTION H6 0 IMPORTANT READ THE FOLLOWING INSTRUCTIONS COMPLETELY BEFORE INSTALLING 1 0 INTRODUCTION H4 0 8A This high e cient gas fired two stage condensing furnace is an upflow horizontal righ...

Page 5: ...PROPERTY DAMAGE OR LOSS OF LIFE REFER TO THIS MANUAL INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER SERVICE AGENCY OR THE GAS SUPPLIER H3 4 THESE INSTRUCTIONS ARE INTENDED AS AN A...

Page 6: ...he floor The furnace must be located or protected to avoid physical dam age by vehicles See safety warning 9 Wolf Steel furnaces may be used as a construction heater provided that the furnace installa...

Page 7: ...OT INSTALL THIS FURNACE IN A MOBILE HOME THIS FURNACE IS NOT APPROVED FOR INSTALLATION IN A MOBILE HOME DOING SO COULD CAUSE FIRE PROPERTY DAMAGE PERSONAL INJURY OR LOSS OF LIFE THE FURNACE CONTAINS F...

Page 8: ...CAL DAMAGE BY VEHICLES FAILURE TO HEED THESE WARNINGS CAN CAUSE A FIRE OR EXPLOSION RESULTING IN PROPERTY DAMAGE PERSONAL INJURY OR LOSS OF LIFE TABLE A FURNACE DIMENSIONS INPUT Width Depth Height Sup...

Page 9: ...furnaces operated with a system temperature rise of 70 100 F 39 56 C This furnace is designed to be operated with a system temperature rise T as illustrated in model input and temperature section If t...

Page 10: ...tibles guidelines as marked on the appliance rating plate 5 The furnace must be installed on a level surface It is recommended that the rear of the furnace be elevated 1 4 6mm higher than the front to...

Page 11: ...ordance with instructions in the appropriate sections of this manual NON SUSPENDED INSTALLATION Maintain clearances to combustibles as outlined in Table B The furnace must be supported in such a way a...

Page 12: ...bles information Also see the appliance rating plate a xed to the furnace for specific model number serial number and clearance to combustibles information IMPORTANT THIS FURNACE REQUIRES A MINIMUM OF...

Page 13: ...c pressure drop of the air distribution system including filters should not exceed 1 0 w c or that specified on product rating plate H3 8 DO NOT ALLOW GAS PIPING TO BE ROUTED THROUGH JOIST SPACES THAT...

Page 14: ...that there is adequate space and accessibility for air filter removal 5 If an air conditioning evaporator coil is required position it on the supply air side of the furnace Ensure that no air can byp...

Page 15: ...nged with other vent systems or unlisted pipe and or fittings Follow the venting manufacturers instructions on installation cutting de burring cementing curing and supporting of the venting system Fur...

Page 16: ...vertical riser closest to the furnace 2 Place a reducer bushing of proper diameter in the stem portion of the tee The recommended size for the reducer is 5 8 15 9mm 3 Place a piece of 5 8 15 9mm diame...

Page 17: ...Glue and similar adhesives and cements Ammonia as commonly found in permanent wave solutions used in hair dressing salons Anti static fabric softeners used in clothes dryers Carbon tetrachloride Chlor...

Page 18: ...in 12 305mm of the ceiling and the other within 12 305mm of the floor The air openings must be sized considering the method outside air is introduced whether the combustion and ventilation air is bein...

Page 19: ...and ventilation air requirements must be added to those of the furnace IMPORTANT IF THE ATTIC HAS AN EXHAUST FAN POWER VENT IT MAY CREATE A NEGATIVE PRESSURE SUFFICIENTLY LARGE ENOUGH TO PREVENT THE A...

Page 20: ...USED TO REDUCE TO THE SMALLER DUCT SIZE IF NECESSARY IMPORTANT THE OUTDOOR GRILLS MUSTBE INSTALLED INALOCATION WHERETHEYWILLNOTBE OBSTRUCTED IN ANY MANNER Combustion Air Duct Terminates 12 305mm above...

Page 21: ...unt all termination fittings in addition to counting the concentric vent as a straight pipe FAILURE TO FOLLOW ALL VENTING GUIDELINES MAY RESULT IN ERRATIC FURNACE OPERATION FREEZE UP OF THE EXHAUST AI...

Page 22: ...80 2 2 50 45 40 35 30 25 20 3 100 95 90 85 80 75 70 H12 4 7 H12 4 7 NOTE When 1 2 or 3 pipe is used exit the cabinet with 2 pipe Reduce or increase immediately after exiting the cabinet on both intak...

Page 23: ...ngle family dwellings and serves both dwellings Less than 7 feet 2 1m above a paved sidewalk or paved driveway located on public property Within 6 feet 1 8m of a mechanical air supply inlet to any bui...

Page 24: ...llations Dedicated combustion air and vent piping eliminates the need to use already heated air for combustion purposes The probability of corrosive contaminants being present in the combustion air is...

Page 25: ...age of the natural buoyancy of the flue gases to help prevent re circulation of the exhaust Figure 9 VERTICAL No termination fitting is required if venting vertically through a roof The end of the exh...

Page 26: ...terminate under a deck unless there is adequate clearance to prevent damage from the flue gases A termination may be located at the end of a patio deck Piping running beneath the deck must be suitably...

Page 27: ...m H Clearance to each side of center line ex tended above meter regulator assembly 3ft 91cm within a height 15ft 4 5m above the meter regulator assembly I Clearance to service regulator vent outlet 3f...

Page 28: ...15cm H Clearance to each side of center line ex tended above meter regulator assembly 3ft 91cm within a height 15ft 4 5m above the meter regulator assembly I Clearance to service regulator vent outlet...

Page 29: ...e 5 8 barbed fitting on the condensate trap assembly The small one is used to secure the drain hose to the exhauster drain collar and the 1 2 barbed fitting on the condensate trap assembly The drain c...

Page 30: ...erials This ensures proper drainage and prevents spilling the products of combustion into the building The blower compartment should be completely isolated from the burner compartment and in tight roo...

Page 31: ...ING FIGURE 15 UPFLOW VENT AND DRAINING OPTION TOP VENT LEFT DRAIN INSTALLATION TOP VENT RIGHT DRAIN INSTALLATION IMPORTANT PRIME CONDENSATE TRAP WITH WATER AND CUT DRAIN HOSES TO PROPER LENGTH CUT PRE...

Page 32: ...available to a condensate pump If using a condensate pump be sure that it is approved for furnace condensate DO NOT DRAIN THE CONDENSATE OUTDOORS DO NOT RUN THE CONDENSATE LINE THROUGHAREASWHEREFREEZI...

Page 33: ...e use of accessory drain trap heaters electric heat tape and or RV antifreeze is recommended for these installations Locate the furnace so condensate ows downwards to the drain Do not locate the furna...

Page 34: ...ientations 3 A 1 2 PVC coupling or bushing will fit snug over the 1 2 rubber hose A 3 4 CPVC coupling or bushing will fit snug over the 5 8 rubber hose This method ensures a water tight seal and also...

Page 35: ...RCIAL STANDARDS In Canada the gas piping should be installed in accordance with CAN CSA B149 1 and 2 and in accordance with any local codes In the United States the gas piping should be installed in a...

Page 36: ...ply pressure should be 11 to 13 w c 12 w c recommended These pressures must be maintained while all other gas fired appliances are operating at maximum conditions IMPORTANT DO NOT EXCEED 13 W C INLET...

Page 37: ...IFICE SIZES DMS NATURAL LP 40 60 80 0 2000 0 610 m 45 55 2000 3000 610 914 m 56 3000 4000 914 1219 m 4000 5000 1219 1524 m 5000 6000 1524 1829 m 6000 7000 1829 2134 m 7000 7800 2134 2377 m 7800 8000 2...

Page 38: ...rical supply to furnace remove the manometer hose from the inlet pressure tap boss and tighten the inlet pressure tap screw using the 3 32 Allen wrench Clockwise 7 in lb minimum 6 Turn on the gas supp...

Page 39: ...astic regulator adjustment screw clockwise to increase manifold pressure or counterclockwise to reduce manifold pressure Always adjust regulator according to original equipment manufacturer s specifi...

Page 40: ...w c The input rating of the furnace is based on 1000 Btu ft gas with a specific gravity of 0 6 Since heating values for the gas vary geographically the actual furnace input and output will vary accor...

Page 41: ...adian Electrical Code Part 1 and any applicable local code In the United States all electrical work must be in accordance with the latest edition of the National Electrical Code ANSI NFPA 70 Although...

Page 42: ...connected with L2 Neutral and a GREEN wire to be connected to the ground If the junction box must be moved from it s original location to the other side of the unit 1 Remove the appropriate knockouts...

Page 43: ...10 minutes of continuous low heat operation Once high heat is started from automatic staging the demand for high heat remains until the heat call is satisfied Factory Setting FIGURE 30 THERMOSTAT CON...

Page 44: ...m temperatures Avoid locations where the thermostat will be exposed to cold drafts heat from nearby lamps or appliances exposure to sunlight heat from inside wall stacks etc H24 17 THERMOSTAT IFC Y C...

Page 45: ...is operating in the heating or cooling fan modes H20 2 NOTE All HUM and EAC terminals are 120V Do not directly connect 24V equipment to these terminals The integrated furnace control has provisions to...

Page 46: ...ain trap assembly be primed before the initial startup Refer to the instructions on how to prime the condensate trap on the drain piping section in this manual A dry trap will allow flue gases to flow...

Page 47: ...ower on delay time begins when the gas valve is energized The control provides the motor low heat speed signal when flame is proven and starts a 30 second blower delay before full capacity blower leve...

Page 48: ...er bypass ducts etc Choose a location well within the main air stream 3 Operate the furnace long enough to obtain steady state conditions at both input rates High Fire and Low Fire 4 When the two ther...

Page 49: ...e provided for reference only and above the certification design parameters of this ap pliance Always refer to and follow the rating plate for allowable installation parameters WSX060T3AA ESP in WC Lo...

Page 50: ...zed as long as the call for fan remains without a call for heat or cooling This feature allows continuous circulation of air between calls for heating or cooling If a call for heat W occurs during con...

Page 51: ...e drop across the filter The contractor should assess the capabilities of the duct system to deliver su cient air flow if this type of filter is considered RECOMMENDED Electronic air cleaners using el...

Page 52: ...rs of the screws attaching the heat exchanger to the division panel and blower assembly LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OP...

Page 53: ...sembly to the division panel and the heat exchanger assembly screws fastened from lower vestibule through to the upper vestibule and place thread covers 11 Feed the wire connectors through to the lowe...

Page 54: ...afety controls now prevent the formation of carbon monoxide The third general area is the recovery of the latent heat contained in the flue gas which is comprised of water vapor and carbon dioxide By...

Page 55: ...Low Heat Circulating Air Fan On After Programmed Delay Flame Sense Lost Thermostat Call For Heat Ends Low Main Valve Closes Combustion Air Blower Off After Pos t Purge 5 Seconds Circulating Air Fan Of...

Page 56: ...within one call for heat 7 Flashes Pressure switch cycle lockout 8 Flashes Lockout due to too many flame dropouts 9 Flashes Not used 10 Flashes Flame present with gas valve o A green LED AN2 is provid...

Page 57: ...OLOUR LEAD NUMBER BLACK WHITE RED BLACK WHITE EMPTY 1 2 3 4 5 6 1 2 3 4 5 C1 H24 6 3 7 1 6 5 C2 HOUSING VIEW FROM OPPOSITE OF WIRE INSERTION END PLASTIC 9 PIN HOUSING AMP 1 480707 0 METAL CONTACT TERM...

Page 58: ...IRED POSITION COLOUR LEAD NUMBER BLACK BLACK RED 1 2 3 4 1 3 3 2 1 C6 WHITE WHITE 4 5 2 5 5 4 H24 11 1 9 3 4 5 C7 HOUSING VIEW FROM OPPOSITE OF WIRE INSERTION END PLASTIC 9 PIN HOUSING AMP 1 480706 0...

Page 59: ...sed by installation that is not performed in compliance with all applicable federal provincial state laws or regulations and Installation Operating Manual 4 Damage as a result of vandalism freight dam...

Page 60: ...F THE ORIGINAL INVOICE WILL BE REQUIRED TO HONOUR THE CLAIM When ordering replacement parts always give the following information Model Serial Number of appliance Installation date of appliance Part n...

Page 61: ...KIT CONVERSION NG TO LP YES 15 W370 0031 KIT CONVERSION LP TO NG 16 W100 0276 SER BURNER BOX 40K 2STG GF Items may not appear exactly as illustrated Ref No Part Number Part Description Stocked 16 W100...

Page 62: ...01 B 01 09 23 62 IOM IOM Appliance Service History This appliance must be serviced annually depending on usage Date Dealer Name Service Technician Name Service Performed Special Concerns 23 0 SERVICE...

Page 63: ...ller service agency or the gas supplier Before servicing disconnect all electrical power to furnace When servicing controls label all wires prior to disconnecting Reconnect wires correctly Verify prop...

Page 64: ...OMEOWNER 72 4 1 AIR FILTER 72 4 2 ROUTINE EXAMINATION 72 4 3 ANNUAL INSPECTION SERVICE 73 4 4 FURNACE APPEARANCE 73 4 5 SEQUENCE OF OPERATION 74 4 6 VARIATIONS 74 4 7 TERMINATIONS 74 5 0 HOMEOWNER S R...

Page 65: ...ICH IF NOT AVOIDED COULD RESULT IN DEATH OR SERIOUS INJURY WARNING INDICATES A POTENTIAL HAZARDOUS SITUATION WHICH IF NOT AVOIDED MAY RESULT IN MINOR OR MODERATE INJURY IT MAY ALSO BE USED TO ALERT AG...

Page 66: ...e or explosion A qualified service agency should be contacted to inspect the furnace and to replace all gas controls control system parts electrical parts that have been wet or the furnace if deemed n...

Page 67: ...N ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE CAN CAUSE INJURY PROPERTY DAMAGE OR LOSS OF LIFE REFER TO THIS MANUAL INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER SERVICE AGENCY...

Page 68: ...portant for these vents to remain clear Do not allow moisture which could freeze to build up in the vent If you see moisture building up in the regulator vent contact your gas supplier H3 29 OBSTRUCTI...

Page 69: ...insulating materials are combustible Do not allow building insulating materials to come into contact with the furnace 5 Any additions alterations or conversions required in order for the furnace to p...

Page 70: ...o valve to the OFF position If burning LP gas smell for gas near the floor since propane and butane are both heavier than air If after this time you do not smell gas continue to the next step 9 Turn...

Page 71: ...ds and other exhaust fans to reduce the heating load on the system 4 Arrange the furniture and drapes so that the supply air registers and return air grills are unobstructed 5 If you have a perimeter...

Page 72: ...d not sag and should have a 1 4 6mm per foot 305mm slope upwards to the outside wall or termination There should be no water marks on the floor under the venting Water marks may indicate a leaking pip...

Page 73: ...d be observed for signs of dirt carbon debris etc CIRCULATING FAN The condition of the circulating fan should be checked to ensure that it is free of excessive dust buildup debris etc The mechanical f...

Page 74: ...s open because it is directly in series with the high pressure switch 5 When the thermostat W2 call ends and W1 remains two stage thermostat the control de energizes the high gas output and immediatel...

Page 75: ...ocated on bottom of inside door Date Installed Contractor Contact Address Postal Code Zip Code Telephone No After Hours No If di erent from Installation Contractor Service Tech Telephone No After Hour...

Page 76: ...COMFORT PRODUCTS 7200 Route Transcanadienne Montr al Qu bec H4T 1A3 24 Napoleon Road Barrie Ontario Canada L4M 0G8 214 Bayview Drive Barrie Ontario Canada L4N 4Y8 103 Miller Drive Crittenden Kentucky...

Page 77: ...n tant qu installateur professionnel vous vous devez de conna tre le produit mieux que le client Ceci comprend toutes les consignes de s curit et les informations connexes Avant de commencer l install...

Page 78: ...EXT RIEUR SYST ME DEUX CONDUITS 100 9 4 3 AIR COMBURANT 100 10 0 TERMINAISONS 101 10 1 AIR COMBURANT 101 10 2 VACUATION 101 10 3 ENSEMBLE DE TERMINAISON D VACUATION CONCENTRIQUE 101 10 4 INSTRUCTIONS...

Page 79: ...E POUR UNE FOURNAISE DEUX TAPES 133 21 0 GARANTIE 135 22 0 LISTE DES PI CES DE RECHANGE 136 23 0 HISTORIQUE D ENTRETIEN 138 NOTE Les changements autres que les ditoriaux sont d not s par une ligne ver...

Page 80: ...0 IMPORTANT AVANT DE PROC DER L INSTALLATION LISEZ TOUTES LES DIRECTIVES SUIVANTES 1 0 INTRODUCTION H4 0 8A Cette fournaise condensation deux tape aliment e au gaz et rendement lev est un g n rateur d...

Page 81: ...F REZ VOUS CE MANUEL L INSTALLATIONETL ENTRETIENDOIVENT TREEFFECTU SPARUNINSTALLATEUR QUALIFI UNE AGENCE DE SERVICE OU UN FOURNISSEUR DE GAZ H3 4 CES INSTRUCTIONS SONT DESTIN ES AIDER LES TECHNICIENS...

Page 82: ...ournaise doivent se trouver au moins 18 457 mm au dessus du plancher Pour viter que les v hi cules endommagent la fournaise elle doit tre install e dans un endroit appropri ou tre prot g e Con sultez...

Page 83: ...ET POURRAIT CAUSER UN INCENDIE DES DOMMAGES MAT RIELS DES BLESSURES CORPORELLES OU LA MORT CETTE FOURNAISE CONTIENT DE L ISOLANT EN FIBRE DE VERRE RECOUVERT D UNE FEUILLED ALUMINIUM ILEXISTEUNLIENENTR...

Page 84: ...ed for closet installation Flux d air Pl num 1 2 13 mm de chaque c t Filtre C t s Devant Dessus vacuation O et S NOTES S D gagement pour l entretien au moins 24 pouces 610 mm C Plancher combustible ex...

Page 85: ...re raisonnable La plupart des anciennes fournaises gaz fonctionnent avec un syst me d l vation de temp rature entre 70 et 100 F 39 56 C Cette fournaise est con ue pour fonctionner avec un syst me d l...

Page 86: ...x mat riaux combustibles comme indiqu sur la plaque d homologation de l appareil 5 La fournaise doit tre install e sur une surface de niveau Il est recommand de sur lever l arri re de la fournaise de...

Page 87: ...ement de l interrupteur de pression et du drain doivent respecter les directives d crites dans les sections appropri es de ce manuel INSTALLATION NON SUSPENDUE Maintenez les d gagements aux mat riaux...

Page 88: ...bles certifi s et les dimensions Pour conna tre les num ros de mod le et de s rie ainsi que les d gagements aux mat riaux combustibles consultez la plaque d homologation fix e sur la fournaise IMPORTA...

Page 89: ...ir incluant les filtres doit tre d au plus 1 0 de CE ou selon les sp cifications sur la plaque d homologation de l appareil H3 8 VITEZ DE PASSER DES CONDUITES DE GAZ ENTRE LES SOLIVES DANS LES ESPACES...

Page 90: ...ils combustion adjacents 4 Pr voyez un espace et un acc s su sants pour l enl vement du filtre air 5 Si un serpentin d vaporateur de climatisation est n cessaire installez le sur le c t de la fournais...

Page 91: ...es raccords non homologu s Suivez les directives du fabricant du syst me d vacuation quant l installation au d coupage l bavurage au collage au conditionnement et au support de ce syst me La fournaise...

Page 92: ...che de la fournaise 2 Placer une bague de r duction du diam tre appropri dans la tige du t La taille recommand e du r ducteur est de 5 8 po 15 9 mm 3 Placez un tuyau de 5 8 po 15 9 mm de diam tre et d...

Page 93: ...e habituellement incorpor e dans les produits pour permanente utilis s dans les salons de coi ure De l assouplisseur textile utilis dans les s che linge Du t trachlorure de carbone Des nettoyants et c...

Page 94: ...venance de l air de combustion et de ventilation de l int rieur ou de l ext rieur et du moyen d approvisionnement en air ext rieur le cas ch ant De plus la dimension devra tenir compte de tous les aut...

Page 95: ...out s ceux de la fournaise FIGURE5 PRISE D AIR EXT RIEUR DANS LE GRENIER OU UN ESPACE RESTREINT EXEMPLE 3 Persienne de ventilation chacune des extr mit s du grenier ou dispositifs de ventilation ou ch...

Page 96: ...Air Duct Terminates 12 305mm above floor Terminaison du conduit d air comburant 12 305 mm au dessus du plancher Fournaise Persienne de ventilation Conduit de ventilation Conduit d air comburant Persi...

Page 97: ...me NPA 54 ANSI Z223 1 de la derni re dition du National Fuel Gas Code aux tats Unis de m me qu tous les codes locaux LE NON RESPECT DE TOUTES LES DIRECTIVES D VACUATION PROVOQUERAIT UN FONCTIONNEMENT...

Page 98: ...exhaust The intake should have a 1 or 2 snorkel intake fitting Figure 7 2 2 75 70 65 60 55 50 45 60 1 60 55 50 45 40 35 30 2 2 75 70 65 60 55 50 45 3 100 95 90 85 80 75 70 80 2 2 50 45 40 35 30 25 20...

Page 99: ...n trottoir ou d une entr e pav e situ s entre deux maisons unifamiliales et servant aux deux maisons moins de 7 pieds 2 1 m au dessus d un trottoir ou d une entr e pav e situ s sur une propri t publiq...

Page 100: ...on d installation recommand e Les principaux avantages sont Avec le syst me d vent direct il n est pas n cessaire de faire des modifications ou d utiliser un ensemble En ayant des conduits d air combu...

Page 101: ...prise d air comburant Ceci contribuera emp cher la recirculation des gaz de combustion Figure 9 VERTICALE Si l vacuation se fait verticalement travers un toit aucun raccord de terminaison n est requis...

Page 102: ...aison peut tre situ e l extr mit d une terrasse en bois Les conduits dispos s sous la terrasse en bois doivent tre bien isol s et suspendus de fa on emp cher l accumulation et le gel du condensat Lors...

Page 103: ...CONDUITS D AIR COMBURANT ET D VACUATION D DI S 12 305 mm AU DESSUS DU D ACCUMULATION DE NEIGE 3 76 mm MIN 30 762 mm MAX 3 76 mm MIN R DUIRE DE 3 PVC 2 PVC SOUS LA LIGNE DE TOITURE PRISE D AIR COMBURA...

Page 104: ...e au dessus de l ensemble compteur r gulateur 3 pieds 91 cm une hauteur de 15 pieds 4 5 m au dessus de l ensemble compt eur r gulateur I D gagement la sortie d vent du r gulateur de service 3 pieds 9...

Page 105: ...au dessus de l ensemble compteur r gulateur 3 pieds 91 cm une hauteur de 15 pieds 4 5 m au dessus de l ensemble compt eur r gulateur I D gagement la sortie d vent du r gulateur de service 3 pieds 91cm...

Page 106: ...es 2 1 2 pintes US ou 2 1 4 litres Vous devez prendre les mesures n cessaires pour drainer le condensat Un ensemble de purgeur de condensat est fourni avec la fournaise Consultez les figures 16 20 pou...

Page 107: ...e combustion est enti rement scell NOTE Tous les tuyaux d coulement doivent tre coup s la longueur appropri e et pencher vers le purgeur de condensat pour viter que les tuyaux d coulement n emprisonne...

Page 108: ...AIR COMBURANT DESTIN AUX BR LEURS CE QUI PROVOQUERAIT UNE COMBUSTION INCOMPL TE ET UN FONCTIONNEMENT IRR GULIER DE LA FOURNAISE AVERTISSEMENT FIGURE 16 OPTION D VACUATION ASCENDANTE ET DE DRAINAGE VAC...

Page 109: ...os coude sur le purgeur de condensat Si n cessaire coupez l exc s de tuyau Fixez le tuyau avec les brides en plastique dans le sac de pi ces 2 l aide du raccord de r duction branchez une extr mit du t...

Page 110: ...sup rieure servira d vent ce qui vitera la formation d un bouchon de vapeur et servira de trop plein si le tuyau de drainage bloque Un bout de tuyau de dimensions semblables branch la branche d extr...

Page 111: ...chau age pour purgeur de ruban chau ant lectrique ou d antigel pour VR est recommand e pour ces installations D terminez l emplacement de la fournaise de mani re ce que le condensat puisse s couler ve...

Page 112: ...devrait convenir toutes les orientations de la fournaise 3 Un raccord ou un adaptateur de 1 2 s ajustera parfaitement sur le tuyau de caoutchouc de 1 2 Un raccord ou un adaptateur de 3 4 s ajustera p...

Page 113: ...GAZ QUI L ALIMENTE NE RESPECTE PAS LES NORMES COMMERCIALES TABLIES IMPORTANT Pour maintenir l tanch it dans l espace entourant le br leur la conduite de gaz qui traverse le panneau lat ral de la fourn...

Page 114: ...s doivent tre maintenues lorsque tous les autres appareils gaz fonctionnent au maximum H17 3 4A IMPORTANT NE PAS EXC DER UNE PRESSION D ALIMENTATION DE 13 CE AVEC L UN OU L AUTRE COMBUSTIBLE La soupap...

Page 115: ...ITUDE DIMENSION D INJECTEUR DMS NATUREL PL 40 60 80 0 2000 0 610 m 45 55 2000 3000 610 914 m 56 3000 4000 914 1219 m 4000 5000 1219 1524 m 5000 6000 1524 1829 m 6000 7000 1829 2134 m 7000 7800 2134 23...

Page 116: ...ation de bulles indique une fuite COUPEZ LE GAZ ET R PAREZ LES FUITES IMM DIATEMENT 8 R tablissez l alimentation en gaz et testez le bossage de pression d arriv e l aide d un d tecteur de fuites 9 Si...

Page 117: ...la vis de r glage en plastique vers la droite pour augmenter la pression au collecteur et vers la gauche pour la r duire R glez toujours le r gulateur selon les sp cifications du fabricant de l quipe...

Page 118: ...ajust e ou la grandeur de l injecteur du br leur peut tre modifi e pour compenser cet cart Consultez les fournisseurs de gaz pour obtenir les contenus calorifiques sp cifiques Tout r glage la pressio...

Page 119: ...de l lectricit partie 1 et tout autre code local applicable Aux tats Unis tous les branchements lectriques doivent tre conformes la derni re dition de la norme ANSI NFPA 70 du National Electrical Code...

Page 120: ...le fil neutre et le fil VERT qui doit tre raccord la mise la terre Si la bo te de jonction doit tre d plac e de son emplacement original l autre c t de l appareil 1 Enlevez le capuchon de plastique du...

Page 121: ...se temp rature Une fois que la chaleur est d marr e partir de la demande automatique la chaleur ne s teindra pas avant que la temp rature soit atteinte R glage en usine FIGURE 30 DIAGRAMME DU CONNECTE...

Page 122: ...at sera expos des courants d air froid la chaleur provenant de lampes ou d appareils la lumi re du soleil la chaleur provenant des conduits install s l int rieur des murs etc H24 17 THERMOSTAT IFC Y C...

Page 123: ...en mode chau age ou en mode refroidissement H20 2 NOTE Les bornes HUM et EAC ont une tension de 120 V Ne branchez pas d quipements 24 V directement ces bornes Le contr le int gr de la fournaise peut...

Page 124: ...iluer et vacuer le gaz qui s est d gag Lors du d marrage initial il arrive qu une odeur mane du registre dans une pi ce Afin d assurer une ventila tion su sante nous vous recommandons d ouvrir les por...

Page 125: ...condes 3 La sou erie entre en fonction lorsque la soupape de gaz est activ e Le contr le donne le signal de vitesse de faible chaleur au moteur lorsque la flamme est tablie et amorce une p riode d att...

Page 126: ...umidificateur etc Choisissez un emplacement bien l int rieur du courant d air principal 3 Faites fonctionner l appareil su samment longtemps pour obtenir des conditions stables pour les deux d bits d...

Page 127: ...810 1015 WSX060T3AA ESP in WC Feu Doux 1 Feu Wif 2 2 0T Froid 3 2 5T Froid 4 3 0T Froid 5 1 295 630 455 830 1015 0 9 335 665 495 865 1085 0 8 385 715 535 895 1110 0 7 430 750 580 940 1140 0 6 470 795...

Page 128: ...l appel du ventilateur n est pas jumel un appel de chau age ou de refroidissement Cette caract ristique permet la circulation d air continue entre les appels de chau age ou de refroidissement Si un ap...

Page 129: ...it valuer la capacit du syst me de conduits de fournir su samment de circulation d air si on envisage utiliser ce type de filtre RECOMMANDATION Les purificateurs d air lectroniques utilisant la pr cip...

Page 130: ...e couvercles de les vis fixant l changeur de chaleur au panneau de divison et l assemblage de la sou erie 4 Retirer les vis fixant l assemblage de la sou erie au panneau de division de la sou erie l a...

Page 131: ...ez les connecteurs de fils dans le vestibule inf rieur fixez les au panneau de division l aide du passe fils verrou tournant et rebranchez les connecteurs au harnais situ dans le vestibule inf rieur 1...

Page 132: ...ustion sur arr t apr s postbalayage Circulateur sur arr t apr s arr t en douceur 1 heure de d lai avant r initialisation de l auto verrouillage Clignotements 4 30 secondes entre deux essais de balayag...

Page 133: ...illage du cycle de l interrupteur de pression 8 clignotements Verrouillage caus par un trop grand nombre de pertes de flamme 9 clignotements Non utilis 10 clignotements Pr sence de flamme avec soupape...

Page 134: ...NUM RO DE FIL NOIR BLANC ROUGE NOIR BLANC VIDE 1 2 3 4 5 6 1 2 3 4 5 3 2 1 4 5 C1 H24 6 C2 VUE DU BO TIER C2 DU C T OPPOS DE L EXTR MIT D INSERTION DU FIL BO TIER EN PLASTIQUE 9 BROCHES CONNECTEUR AMP...

Page 135: ...5 REQUIS POSITION COLEUR NUM RO DE FIL NOIR NOIR ROUGE BLANC BLANC 1 2 3 4 5 4 1 3 2 5 3 2 1 C6 5 4 H24 11 C7 VUE DU BO TIER C7 DU C T OPPOS DE L EXTR MIT D INSERTION DU FIL BO TIER EN PLASTIQUE 9 BRO...

Page 136: ...x provinciaux ou de l tat applicables ainsi qu aux directives du manuel des Instructions d installation et d op ration 4 Des dommages pouvant r sulter du transport d actes de vandalisme d accidents ou...

Page 137: ...NTIE UNE PHOTOCOPIE DE LA FACTURE ORIGI NALE SERA REQUISE AFIN DE POUVOIR HONORER LA DEMANDE Lorsque vous commandez des pi ces donnez toujours l information suivante Mod le et num ro de s rie de l app...

Page 138: ...4 W020 1103 SAC DE PI CES DE RECHANGE 15 W370 0018 ENSEMBLE DE CONVERSION GN LP OUI Ces articles peuvent diff rer de ceux illustr s No de r f No de pi ce Description En stock 15 W370 0031 ENSEMBLE DE...

Page 139: ...i une agence d entretien ou le fournisseur de gaz Avant d e ectuer l entretien d branchez l alimentation lectrique de l appareil Lors de l entretien des contr les tiquetez tous les fils avant de les d...

Page 140: ...ROPRI TAIRE 148 4 1 FILTRE AIR 148 4 2 INSPECTION P RIODIQUE 148 4 3 INSPECTION ET ENTRETIEN ANNUEL 149 4 4 APPARENCE DE LA FOURNAISE 149 4 5 S QUENCE DE FONCTIONNEMENT 151 4 6 VARIATIONS 151 4 7 TERM...

Page 141: ...MORT OU DES BLESSURES GRAVES AVERTISSEMENT INDIQUE UNE SITUATION POTENTIELLEMENT DANGEREUSE QUI SI ELLE N EST PAS VIT E POURRAIT CAUSER DES BLESSURES MINEURES OU MOD R ES PEUT AUSSI TRE UTILIS POUR ME...

Page 142: ...lier n cessitant parfois les services d un installateur qualifi d une agence de service ou d un fournisseur de gaz la fournaise fonctionnera de fa on satisfaisante pendant plusieurs saisons de chau ag...

Page 143: ...S UN SERVICEOUUNENTRETIENINAD QUATSPEUVENTCAUSERDESDOMMAGESMAT RIELS DES BLESSURES CORPORELLES OU DES PERTES DE VIE CONSULTEZ CE MANUEL L INSTALLATION ET L ENTRETIEN DOIVENT TRE EFFECTU S PAR UN INSTA...

Page 144: ...s Ne laissez pas l humidit s accumuler dans l vent elle risquerait de geler Si vous constatez une telle accumulation d humidit dans l vent du r gulateur communiquez avec votre fournisseur de gaz H3 29...

Page 145: ...euble dans un endroit o se trouve de l isolant soyez conscient que certains mat riaux isolants sont combustibles Ne laissez aucun mat riau d isolation entrer en contact avec la fournaise 5 Tout ajout...

Page 146: ...de gaz ARR TEZ Tournez la soupape d arr t manuelle en position OFF arr t Si vous utilisez du gaz propane v rifiez s il y a une odeur de gaz pr s du sol puisque le propane et le butane sont plus lourds...

Page 147: ...our r duire la charge de chau age du syst me 4 Placez les meubles et les draperies de telle fa on que tous les registres d alimentation en air et les grilles de retour d air ne soient pas obstru s 5 S...

Page 148: ...vacuation combustion par un technicien de service qualifi Il est bon d e ectuer une inspection rapide de votre fournaise chaque fois que vous inspectez ou nettoyez le filtre air l ments inspecter V r...

Page 149: ...DRAINAGE Le syst me de drainage du condensat doit tre inspect et nettoy si n cessaire Si l ensemble de purgeur de condensat ou tout autre composant se bloque le condensat pourrait revenir dans l chang...

Page 150: ...carbone Le troisi me facteur est la r cup ration de la chaleur latente contenue dans les gaz de combustion lesquels sont compos s de vapeur d eau et de dioxyde de carbone En condensant les gaz de com...

Page 151: ...rupteur 5 Lorsque le chau age du thermostat W2 s teint et celui du W1 continu thermostat deux consignes le contr le d sactive la sortie de gaz lev e et fait imm diatement passer le ventilateur d vacua...

Page 152: ...tion Entrepreneur Personne ressource Adresse Code postal Num ro de t l phone Num ro en dehors des heures d ouverture Si di rent de l entrepreneur d installation Technicien de service Num ro de t l pho...

Page 153: ...W415 3101 B 01 09 23 153 MU...

Page 154: ...W415 3101 B 01 09 23 154 MU...

Page 155: ...W415 3101 B 01 09 23 155 MU...

Page 156: ...EPTION DE PRODUITS DE CONFORT 7200 Route Transcanadienne Montr al Qu bec H4T 1A3 24 Napoleon Road Barrie Ontario Canada L4M 0G8 214 Bayview Drive Barrie Ontario Canada L4N 4Y8 103 Miller Drive Critten...

Reviews: