Nahita LNB003 Instruction Manual Download Page 8

 

 

Pb- 

Zero adjustment 

Correction  of  errors  caused  by  sensor  (low 
temperature) measurement. 
Pb=  actual  temperature  value  -  instrument 
measurement value 

(-99.9

99.9

℃)

 

PK- 

Full degree 

adjustment 

Correct the error generated when the sensor (high 
temperature) is measured. 
PK=1000*  (actual  temperature  value  -  meter 
measurement value) / meter measurement value 

(-999

999) 0 

 
 
 

Internal parameter table -2

 

Parameter 

indication

 

Parameter 

name

 

Parameter function description

 

(Range) Factory Value

 

Lc

 

 

Password

 

When

Lc=9

,the  parameter  values 

can be viewed and modified.

 

rES 

Power down 

memory 

function 

0

No power down memory function 

1

Power-down memory function 

(0

1) 

FAn 

Fan Type 

selection 

0

The fan is a short axis fan 

1

Fan is a long shaft fan 

(0

1) 

ndc 

Compressor 

Operation 

mode 

0:  the  compressor  is  only  working  in  a 
discontinuous type. 
1:  compressor  according  to  the  value  of  CP  (see 
below)  to  determine  the  balanced  or  intermittent 
work of the compressor. 
2:  compressor  according  to  the  value  of  Htd  (see 
below)  to  determine  the  balanced  or  intermittent 
work of the compressor. 

(0

2) 0 

CP- 

Compressor 

working 

mode fixed 

switching 

point point 

When "ndc=1", 
If  the  "temperature  set  value 

  CP",  the 

compressor  works  in  an  intermittent  manner,  and 
vice versa. 

(0

100.0

30.0 

Htd 

Compressor 

working 

mode 

automatic 

switching 

point 

When "ndc=2", 
If  the  "temperature  set  value 

  ambient 

temperature  +  Htd",  the  compressor  works  in  an 
intermittent manner, and vice versa. 

(-50.0

50.0

0.0 

Crc 

Compressor 

Start and 

stop mode 

When the compressor is working in an intermittent 
manner, 
0:  Automatically  start  and  stop  the  compressor 
(according  to  the  ambient  temperature  and  set 
value); 
1:  Manually  start  and  stop  the  compressor 
(according  to  the  values  of  uP  and  dn  in  internal 
parameter table-1); 

(0

1) 0 

Cnp 

Prohibit 

compressor 

Working 

temperature 

point 

When  "temperature  set  value 

  Cnp",  the 

compressor is prohibited from working. 
Note:  This  mode  of  operation  has  the  highest 
priority,  that  is,  the  controller  executes  this 
command  first,  and  then  judges  the  balanced  or 
intermittent operation of the compressor.

 

(0

100.0

42.0 

Summary of Contents for LNB003

Page 1: ...Version 1 July 2021 Instruction Manual NAHITA BLUE SHAKING INCUBATOR REFERENCE LNB003...

Page 2: ...r the appearance of the product is intact and the random accessories matches the packing list If the product model you received is inconsistent with your booking or the appearance is damaged or there...

Page 3: ...et hands otherwise there is a risk of electric shock 4 Before any repair or maintenance is carried out the power must be disconnected to prevent electric shock or injury 5 Please wear gloves when repa...

Page 4: ...als such as gasoline or thinner Keep the inside and outside of the box clean often cleaning debris and smudges 1 The large screen LCD displays the temperature speed and working time continuously accur...

Page 5: ...W Controller Temp Control Mode LCD PID intelligent control Cyclotron Control Mode Automatic changes of rotation direction Setting Mode Touch button setting Temp Display Mode LCD display Speed Display...

Page 6: ...key thermometer symbol press enter temperature parameter setting state then click return to normal interface Speed function key with arrowhead circle press enter speed parameter setting state then pr...

Page 7: ...0 5 0 Ct Compressor start delay Compressor start delay protection time the minimum time interval from compressor stop to restart 0 600s 180 uP compressor Start threshold When the compressor is workin...

Page 8: ...essor 2 compressor according to the value of Htd see below to determine the balanced or intermittent work of the compressor 0 2 0 CP Compressor working mode fixed switching point point When ndc 1 If t...

Page 9: ...password prompt Lc The speed display area displays the password value You can change the password value to the required password value by adding the key decreasing key and shift key Then click the Sp...

Page 10: ...tion dIF 0 Specifies that the clockwise direction of rotation is positive dIF 1 Specifies that the counterclockwise direction of rotation is positive 0 1 0 FdS Speed feedback value Speed feedback coef...

Page 11: ...by shifting reducing increasing etc then click the Time button to enter the stop timing time the right display prompt p setting status Also modify to the desired setting value then click the Time butt...

Page 12: ...light up and enters after about 3 seconds Normal display status 2 Temperature Press the Temperature button the number on the right side of the temperature display area flashes use the shift button de...

Page 13: ...the operation Notes 1 If the set value of the timing time is changed during the running the controller restarts the timing according to the new set time 2 The timing mode can be selected by modifying...

Page 14: ...ng state the controller will automatically return to the normal display state 5 If the display window of the controller shows to indicate the fault of the temperature sensor or the controller itself p...

Page 15: ...ed smoothly Adjust the foot of the instrument to make the instrument smooth Foreign body barrier at the bottom of the plate Remove foreign body Control circuit fault Notify distributor to repair The m...

Reviews: