5
Operation start / stop key: press the device to start running; then click stop.
1. Temperature internal parameters setting
Press the "temperature" key for about 3 seconds, the temperature display area displays the
password prompt "Lc", and the speed display area displays the password value.
By adding keys, reducing keys and shift keys, modify to the required password value. Then
click the "temperature" key, if the password value is not correct, the controller automatically
returns to the normal display state; if the password value is correct, then enter the temperature
internal parameters setting state, and then click "temperature" key to modify each parameter
in turn. After modification, press the "temperature" button for 3 seconds and exit the internal
parameter setting state, and the parameter value is automatically saved.
Internal parameter table -1
Parameter
indication
Parameter
name
Parameter function description
(Range) Factory Value
Lc
Password
The parameter value can be viewed and
modified when "Lc=3".
0
AL-
Upper deviation
Over
temperature
alarm
When the "temperature measurement >
temperature setting value +AL", the alarm light is
turned on, the buzzer calls, and the heating output
is disconnected.
(0
~
20.0
℃
)
5.0
Ct-
Compressor
start delay
Compressor start delay protection time, the
minimum time interval from compressor stop to
restart.
(0
~
600s)
180
uP-
compressor
Start threshold
When the compressor is working in an
intermittent manner,
If the "temperature measurement value
≥
temperature set value + uP" and the compressor
start delay time is up, start the compressor.
Note: This parameter is valid only in the manual
start and stop compressor mode, and is invalid in
the automatic mode.
(-10.0
~
10.0
℃
)
0.4
dn-
Compressor
Closing the
threshold
When the compressor is working in an
intermittent manner,
Turn off the compressor if "temperature
measurement value
≤
temperature set value +
dn".
Note: This parameter is valid only in the manual
start and stop compressor mode, and is invalid in
the automatic mode.
(-10.0
~
(uP-0.1))
0.2
Lt-
Floodlight
off-delay
The light is opened and the time delay Lt time is
automatically closed. "Lt=0", the delay is invalid,
the lights must be turned off manually.
(0
~
9999min)
0
St-
Sterilizing lamp
off-delay
The sterilization lamp is opened and the time
delay St time is automatically closed. "St=0", the
delay is invalid and the lamp must be manually
closed.
(0
~
9999min)
0
T-
Control cycle
Heating control cycle.
(1
~
60s) 5
P-
Proportional
band
Time proportional adjustment.
(0.1
~
50.0) 15.0
I-
Integration time
The integral function is adjusted.
(1
~
2000s) 380
d-
Differential time
Differential action regulation.
(0
~
2000s) 100