30
of
45
Installation, operation, and maintenance manual-ABE Rev 1_2023
8.1.2.
BACNET LIST
Object-name
Object Type
Object
Instance
Description
Unit-code
ControlMode
Analog
0
0=Local, 1=Remote,
2=Communication
SupplyTempSp
Analog
1
Supply temperature setpoint, if
ControlMode=2
If TempUnit=0,°C
If TempUnit=1,°F
SupplyAirFlowSp
Analog
2
Supply airflow setpoint, if
Control Mode=2
Cubic Foot Minute
SupplyAirTemp
Analog
3
Supply temperature
If TempUnit=0,°C
If TempUnit=1,°F
OutsideAirTemp
Analog
4
Outdoor temperature
If TempUnit=0,°C
If TempUnit=1,°F
ReturnAirTemp
Analog
5
Return temperature
If TempUnit=0,°C
If TempUnit=1,°F
ExhaustAirTemp
Analog
6
Exhaust temperature
If TempUnit=0,°C
If TempUnit=1,°F
SupplyAirFlow
Analog
7
Supply airflow
Cubic Foot Minute
ReturnAirFlow
Analog
8
Return airflow
Cubic Foot Minute
RecuperatorTime
Analog
9
Recovery cycle time
Second
RecupTimeTo Turn
Analog
10
Recovery cycle countdown
Second
Cycle count
Analog
11
Number of cycles
Temp Unit
Binary
0
Temperature unit
0=°C, 1=°F
UnitCMD
Binary
1
Unit control, if ControlMode=2
Unit Enable
Binary
2
Unit in operation
DamperStatus
Binary
3
Dampers status
VFDStatus
Binary
4
VFD status
RecuperatorEnable
Binary
5
Recovery status
RecSensorDetection
Binary
6
Recovery sensor status
RecuperatorMotorCMD
Binary
7
Recuperator motor status
UnitAlarm
Binary
8
Unit alarm
Summary of Contents for ABE Series
Page 21: ...21 of 45 Installation operation and maintenance manual ABE Rev 1_2023 8 1 1 HMI STRUCTURE ...
Page 35: ...35 of 45 Installation operation and maintenance manual ABE Rev 1_2023 ...
Page 36: ...36 of 45 Installation operation and maintenance manual ABE Rev 1_2023 ...
Page 37: ...37 of 45 Installation operation and maintenance manual ABE Rev 1_2023 ...
Page 38: ...38 of 45 Installation operation and maintenance manual ABE Rev 1_2023 ...
Page 39: ...39 of 45 Installation operation and maintenance manual ABE Rev 1_2023 ...
Page 45: ...45 of 45 Installation operation and maintenance manual ABE Rev 1_2023 ...